Plan Review Details - Permit 07120038
Plan Review Stops For Permit 07120038
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By mperson Date 2007-12-20 Time 13:45 Rev Time 0.00
Received By mperson Date 2007-12-20 Time 13:45 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By mperson Date 2007-12-10 Time 15:36 Rev Time 0.00
Received By mperson Date 2007-12-10 Time 15:36 Sent To PC
Notes
2007-12-10 15:49:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 **PERMIT APPLICATION IS STATING INSTALL NOT REPLACE.
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE OR CHANGE THE PERMIT
 APPLICATION TO "REPLACE LIKE FOR LIKE" ON THE
 RESUBMITTAL:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 15:23 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 15:23 Sent To G
Notes
2007-12-18 15:23:47TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By mperson Date 2007-12-10 Time 15:49 Rev Time 0.00
Received By mperson Date 2007-12-04 Time 11:42 Sent To  
Notes
2007-12-04 11:42:23TO "G" BOX