| Plan Review Stops For Permit 07120023 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-22 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-22 |
Time |
17:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-29 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-29 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-01-29 11:09:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.THE SLAB DETAIL SHOWS A POOL HEATER.DETAILS ARE | | | TO BE CONSISTENT WITH AND CORRELATE WITH THE JOB. | | | OTHER DOCUMENTS AND THE PLANS INDICATE THAT NO HEATER | | | WILL BE INSTALLED.PLEASE RESOLVE THIS INCONSISTENCY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-31 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-31 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2007-12-31 11:43:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE A DETAIL FOR THE EQUIPMENT SLAB.PREFAB | | | SLABS REQUIRE ENGINEERING. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-02-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-20 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-20 |
Time |
16:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-28 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-28 |
Time |
11:22 |
Sent To |
P |
|
| Notes |
| 2008-01-28 11:33:03 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PLAN(UN NUMBERED) DESCRIBING THE PIPE SIZES, | | | INDICATES "NO HEATER", THE SHEET (UN NUMBERED) THAT | | | SHOWS ANCHOR POINTS INDICATES A HEATER, CORRELATE THE | | | PLANS TO SHOW PROPOSED WORK. | | | | | | 2} IF AN ELECTRIC HEATER IS BEING INSTALLED PROVIDE AN | | | ELECTRICAL LOAD CALCULATION. CONSULT THE ELECTRICAL | | | CONTRACTOR. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. ALSO NUMBER THE SHEETS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-10 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-10 |
Time |
16:08 |
Sent To |
P |
|
| Notes |
| 2007-12-10 16:14:39 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF THE | | | WORK APPLIED FOR. INDICATE THE LOCATION OF AFFECTED | | | ELECTRICAL EQUIPMENT, HAVE AN ELECTRICAL CONTRACTOR | | | SIGN ON THIS APPLICATION, OR SUBMIT AN ELECTRICAL | | | APPLICATION CONCURRENT WITH THIS APPLICATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-13 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-13 |
Time |
14:08 |
Sent To |
E |
|
| Notes |
| 2008-02-13 14:08:43 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-17 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-17 |
Time |
10:38 |
Sent To |
Z |
|
| Notes |
| 2008-01-17 10:39:10 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-31 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-03 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2007-12-03 16:28:56 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-20 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-20 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-20 |
Time |
16:43 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-01-29 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-01-29 |
Time |
08:40 |
Sent To |
B |
|
| Notes |
| 2008-01-29 08:52:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. NOTE: AT A MINIMUM PLANS MUST BE CORRELATED. THE | | | UN-NUMBERED RELOCATED EQUIPMENT AND PIPING SCHEDULE | | | INDICATES NO HEATER. THE POOL EQUIPMENT ANCHOR DETAIL | | | IS INDICATING A POOL HEATER. PLEASE CORRELATE THE PLANS | | | AND NUMBER THE PLAN SHEETS. PER FBC CHAPTER 1, CITY WPB | | | AMENDMENTS SECTION *106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | FBC CHAPTER 1, CITY WPB AMENDMENTS SECTION *106.3.4.3. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-11 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-11 |
Time |
16:35 |
Sent To |
B |
|
| Notes |
| 2007-12-11 16:44:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. A PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF WORK | | | APPLIED FOR. INDICATE THE TYPE OF POOL EQUIPMENT BEING | | | RELOCATED.THE SIZE OF THE EQUIPMENT PIPING. IF THERE IS | | | A GAS POOL A GAS PERMIT WILL ALSO BE REQUIRED. PLEASE | | | CLARIFY THIS ON THE RESUBMITTAL. | | | | | | 2. FBC-2004 SEC. 424.2.7.2, OR | | | FBCR-2004 SEC. R4101.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK. (DETAIL REQUIRED) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-24 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-24 |
Time |
08:36 |
Sent To |
E |
|
| Notes |
| 2008-01-24 08:37:23 | ***APPROVED - RESUB #1*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-04 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-04 |
Time |
15:59 |
Sent To |
E |
|
| Notes |
| 2007-12-04 16:03:32 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL | | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.AS THE | | | PROPERTY HAS DUAL FRONTAGES, THE POOL EQUIPMENT SHALL | | | BE A MINIMUM OF 21' AWAY FROM THE SOUTH PROPERTY LINE, | | | A MINIMUM OF 21' AWAY FROM THE NORTHERN PROPERTY LINE | | | AND A MINIMUM OF 1' FROM THE EAST PROPERTY LINE. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|