Plan Review Details - Permit 07120002
Plan Review Stops For Permit 07120002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By mjacobs Date 2008-01-25 Time 13:58 Rev Time 0.00
Received By mjacobs Date 2008-01-10 Time 09:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By mjacobs Date 2007-12-10 Time 11:12 Rev Time 0.00
Received By mjacobs Date 2007-12-10 Time 06:03 Sent To  
Notes
2007-12-10 11:12:09 
 BUILDING PLAN REVIEW
 PERMIT: 07120002
 ADD: 2580- METRO CENTRE DR. #1
 CONT: FISHER CONTRACTING CORP
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/10/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE THE
 PRODUCT APPROVAL FOR THE NEW STOREFRONT IN OFFICE #1.
  
 3) 11-4.24.2 THE BREAK ROOM SINK SHALL BE MOUNTED WITH
 THE COUNTER RIM NO HIGHER THAN 34 INCHES ABOVE THE
 FINISH FLOOR. THE DEPTH OF THE SINK SHALL BE 6 ?
 INCHES. A CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT
 OF THE BREAK ROOM SINK TO ALLOW A FORWARD APPROACH.
 SHEET A-6 DETAIL #2 SHOWS DOORS IN FRONT OF THE SINK,
 THIS WILL NOT MEET THE REQUIREMENTS OF THE FORWARD
 APPROACH PER 11-4.24.5.
  
 4)EACH WALL SHALL BE LABELED ON SHEET A-1 TO REFLECT
 THE WALL DETAILS ON SHEET A-4. ON SHEET A.1 TWO
 DIFFERENT TYPES OF WALLS HAVE THE SAME LABELED P-2.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE. 106.1.1.
  
 5)A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOW THE
 MEANS OF EGRESS FROM THE BUILDING IN CONFORMANCE WITH
 FBC CHAPTER 10.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 11:33 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-07 Cont ID  
Sent By btrobaug Date 2007-12-07 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2007-12-07 Time 07:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By mwennerg Date 2008-01-08 Time 16:04 Rev Time 0.00
Received By mwennerg Date 2008-01-08 Time 16:04 Sent To  
Notes
2008-01-08 16:05:12PLANS WERE APPROVED ON 12/17/07 AND STAMPED, SIGNED AND
 DATED AT THIS TIME. LS SHEET

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 12:10 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 11:48 Sent To  
Notes
2007-12-17 12:09:23*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL REVIEWERS HAVE BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 12:12 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 12:12 Sent To  
Notes
2008-01-04 12:14:22TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 11:48 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 13:43 Sent To  
Notes
2007-12-06 09:02:28TO "BOB"#8
2007-12-03 13:52:06WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-06 Cont ID  
Sent By tgordon Date 2007-12-06 Time 11:15 Rev Time 0.35
Received By tgordon Date 2007-12-06 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-07 Cont ID  
Sent By mperson Date 2008-01-07 Time 14:10 Rev Time 0.00
Received By mperson Date 2008-01-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By mperson Date 2007-12-12 Time 07:54 Rev Time 0.00
Received By mperson Date 2007-12-12 Time 07:54 Sent To  
Notes
2007-12-12 08:24:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PER OCCUPANCY GROUP B AND TABLE *403.1
 (FBC-PLUMBING) A DRINKING FOUNTAIN IS REQUIRED AND
 SHALL BE ACCESSIBLE PER THE FOLLOWING FBC-2004 W/07
 REV. CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. SHEET A.6 DETAIL #2: THE BREAKROOM SINK SHALL BE
 ACCESSIBLE AND COMPLY WITH THE FOLLOWING.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 *11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.(NO CABINET DOORS OR BASE)
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 *11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.(NO CABINET DOORS OR BASE)
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 NOTE:THIS DETAIL IS INDICATING DOORS IN FRONT OF THE
 SINK, THIS WILL NOT MEET THE REQUIREMENTS OF KNEE SPACE
 OR CLEAR FLOOR SPACE.
  
 3. SHEET A.6 DETAIL #16 CLEAR FLOOR SPACE: THE FOWARD
 APPROACH (48" MIN) IS BEING INDICATED WRONG. FOWARD
 APPROACH DOES NOT GO TO THE WALL. PER *11-4.24.5 CLEAR
 FLOOR SPACE.
  
 4. SHEET P.1 WATER/SEWER PLAN & SHEET P.2 SANITARY
 RISER DIAGRAM: THE MOP SINK MUST DRAIN DOWNSTREAM OF
 THE WET VENTED BATHROOM. PER *909.1, WET VENT PERMITTED
 AND SHALL BE VENTED PER *901.2.1, VENTING REQUIRED.
  
 5. SHEET P.1 EWH & REC PUMP DIAGRAM: PLEASE CHANGE THE
 WORDING ON THE "3/4" RELIEF (CPVC) TO FLOOR SINK BELOW"
 TO READ "3/4" RELIEF TO (CPVC) TO MOP SINK BELOW". PER
 *106.1.2, ADDITIONAL DATA.
  
 6. SHEET P.1 WATER/SEWER PLAN: PLEASE CLEARLY INDICATE
 THE LOCATION OF THE DISHWASHER AS IT IS INDICATED ON
 SHEET E.1. PER *106.1.2, ADDITIONAL DATA.
  
 7.SHEET P.2 WATER RISER DIAGRAM: PLEASE ADD THE
 FOLLOWING TO NOTES "PER FBC-2004 W/07 REV. SECTION
 *604.9 WATER HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE UTILIZED".
  
 8. SHEET P.2 PIPE HANGER DETAIL IN EXPOSED AREAS AND
 PIPE HANGER DETAIL UNDER STRUCTURAL FLOOR: DETAILS ARE
 INDICATING HEAVY DUTY PLASTIC CLEVIS HANGERS AND
 PLASTIC ALL THREAD ROD. PLEASE SUBMIT TWO COPIES OF
 MANUFACTURER'S SPECIFICATIONS WITH MAKE, MODEL NUMBER,
 STRESS & HEAT LOAD COMPLYING WITH SECTION *308.3
 MATERIALS.
  
 9. SHEET P.2 PLEASE CLARIFY THE FOLLOWING "NOTE: WATER
 LINES ARE 3/4" U.O.N." WHAT IS U.O.N.? U.O.N. IS NOT
 INDICATED IN THE PLUMBING SYMBOLS + ABBREVIATIONS. PER
 *106.1.2, ADDITIONAL DATA.
  
 10. SHEET P.2 SANITARY RISER DIAGRAM: THE DRAIN FOR
 THE DISHWASHER IS MISSING. PER *802.2 DISHWASHING
 MACHINES SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE SINK.
  
 11. SHEET P.2 SANITARY RISER DIAGRAM: THE FOLLOWING
 CORRECTIONS ARE REQUIRED FOR THE WASHING MACHINE.
  
 (A) *406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 NOTE: THE TRAP IS MISSING FROM THE REISER DIAGRAM.
  
 (B) *802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: PLEASE INDICATE THIS REQUIRED STANDPIPE ON THE
 RESUBMITTAL.
  
 (C) *708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 3".
  
 (D) *708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-07 Cont ID  
Sent By choops Date 2008-01-07 Time 15:42 Rev Time 0.00
Received By choops Date 2008-01-07 Time 15:42 Sent To  
Notes
2008-01-07 15:42:48*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.