Plan Review Details - Permit 07110748
| Plan Review Stops For Permit 07110748 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-12-18 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-12-18 |
Time |
07:43 |
Sent To |
PC |
|
| Notes |
| 2007-12-18 12:31:22 | RESIDENTIAL ALTERATION, BUILDING REVIEW FIRST | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD. (561)233-5115)TO VERIFY IF | | | IMPACT FEES ARE DUE WHEN CHANGING THE USE OF THE | | | BUILDING.BRING BACK STAMPED PLANS AND COPY OF PAID | | | RECEIPT IF IMPACT FEES ARE DUE. | | | | | | 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-101.3 FBC 2004. | | | ***NOTE: PLEASE MAKE SURE UPDATED REVISED FORM IS USED | | | TO AVOID UNNECESSARY DELAYS. | | | | | | 4- QUALITY OF PLANS NEED TO COMPLY WITH SEC. 106.1.3 | | | CITY AMENDMENTS TO FBC 2004.DRAWINGS NEED TO BE | | | CLEAR, DRAWN TO SCALE AND DESIGNER RESPONSIBLE FOR THE | | | DRAWINGS NEED TO PROVIDENAME AND SIGN THE DRAWINGS AS | | | REQUIRED. | | | | | | 5- PROVIDE COMPLETE DESIGN INFORMATION ON DRAWINGS. | | | SPECIFY ALL DESIGN PRESSURES FOR NEW DOORS OPENINGS AS | | | REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 6- PROVIDE COMPLETE DETAILS/ SPECIFICATION SHOWING HOW | | | GARAGE DOOR OPENINGS WILL BE CLOSED TO ALLOW FOR NEW | | | USE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 REGARDING | | | WIND LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 7- PROVIDE COMPLETE FRAMING DETAIL AND STRUCTURAL BUCK | | | DETAIL FOR 2X BUCK AS REQUIRED BY PRODUCT APPROVAL | | | SUBMITTED.NEED TO PROVIDE COMPLETE SUPPORT TO DOOR | | | FRAMING TO COMPLY WITH SEC. R613.1.1 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR STORM SHUTTERS. ALSO, CLEARLYMARK/CIRCLE | | | ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS. EG: | | | WALL MOUNTED AND SPECIFIC ANCHOR TYPE AND SPACING TO BE | | | USED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO | | | VERIFY COMPLIANCE WITH PRODUCT APPROVAL PROPOSED | | | INSTALLATION. | | | | | | 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW.UPGRADE TOTAL VALUATION OR IT WILL BEUPGRADED | | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-04 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-04 |
Time |
10:57 |
Sent To |
M |
|
| Notes |
| 2007-12-04 11:55:35 | | | | | | | | | | APPLICATION #07110748 | | | ELECTRICAL PLAN REVIEW | | | 516 51ST STREET | | | 12/3/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} SHOW COMPLIANCE WITH THE RECEPTACLE SPACING | | | REQUIREMENTS OF 210.52. | | | | | | 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3). | | | | | | 3} COMPLY WITH 210.70 LIGHTING REQUIREMENTS, INTERIOR | | | AND EXTERIOR. | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-12-18 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2007-11-30 15:10:40 | OK PER J PAPA 11-30-07 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-12-18 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-12-03 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2007-12-03 09:31:27 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-04 |
Time |
14:51 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-04 |
Time |
14:51 |
Sent To |
Z |
|
| Notes |
| 2007-12-04 15:09:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC 13-101.2. | | | | | | 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J | | | CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1. | | | | | | 3) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE | | | 2004 FBC/R R303.3 EXCEPT. | | | | | | 4) SHOW THE CFM'S. AT ALL SUPPLY AIR GRILLS, SEE 2004 | | | WPB AMEND. 106.3.5.4 (10). | | | | | | 5) SHOW THE SEER OF THE A/C SYSTEM ON THE MECHANICAL | | | PLAN. | | | | | | 6) SHOW THE TOTAL COOLING BTU'S FOR THE A/C SYSTEM ON | | | THE MECHANICAL PLANS. | | | | | | 7) SHOW THE HEATER KW OR STATE NO HEAT ON THE | | | MECHANICAL PLAN. | | | | | | 8) THE MECHANICAL PLANS NEED THE SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN (ALLAN WERITZ), AND | | | CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE | | | W.P.B. AMEND. 106.1.3. | | | | | | 1 MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-13 |
Time |
06:27 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-13 |
Time |
06:27 |
Sent To |
B |
|
| Notes |
| 2007-12-13 07:18:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE. ONE | | | SET OF PLUMBING DRAWINGS ARE IN PENCIL. PER *106.1.3 | | | QUALITY OF BUILDING PLANS. | | | | | | 2. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.4 | | | RESIDENTIAL (ONE AND TWO-FAMILY) (9) PLUMBING, PLEASE | | | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM | | | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH | | | CLEANOUT LOCATIONS. | | | **THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES | | | NOT HAVE ALL WASTE AND TRAPS SIZED. | | | | | | 3. NOTE: SIZE THE INDICATED POTABLE WATER. PER | | | *106.1.2, ADDITIONAL DATA. | | | | | | 4. THE INDICATED VENT TERMINATING THROUGH THE WALL | | | SHALL COMPLY WITH THE FOLLWING AND BE INDICATED AS SUCH | | | ON THE RESUBMITTAL. | | | *904.6 EXTENSION THROUGH THE WALL. VENT TERMINALS | | | EXTENDING THROUGH THE WALL SHALL TERMINATE A MINIMUM OF | | | 10 FEET (3048 MM) FROM THE LOT LINE AND 10 FEET (3048 | | | MM) ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL | | | NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH | | | SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE | | | PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR | | | BLOCKING THE VENT OPENING. | | | | | | 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-03 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-03 |
Time |
13:04 |
Sent To |
E |
|
| Notes |
| 2007-12-03 13:05:02 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|
|