Plan Review Details - Permit 07110748
Plan Review Stops For Permit 07110748
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By jgomez Date 2007-12-18 Time 11:46 Rev Time 0.00
Received By jgomez Date 2007-12-18 Time 07:43 Sent To PC
Notes
2007-12-18 12:31:22RESIDENTIAL ALTERATION, BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD. (561)233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE WHEN CHANGING THE USE OF THE
 BUILDING.BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF IMPACT FEES ARE DUE.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.3 FBC 2004.
 ***NOTE: PLEASE MAKE SURE UPDATED REVISED FORM IS USED
 TO AVOID UNNECESSARY DELAYS.
  
 4- QUALITY OF PLANS NEED TO COMPLY WITH SEC. 106.1.3
 CITY AMENDMENTS TO FBC 2004.DRAWINGS NEED TO BE
 CLEAR, DRAWN TO SCALE AND DESIGNER RESPONSIBLE FOR THE
 DRAWINGS NEED TO PROVIDENAME AND SIGN THE DRAWINGS AS
 REQUIRED.
  
 5- PROVIDE COMPLETE DESIGN INFORMATION ON DRAWINGS.
 SPECIFY ALL DESIGN PRESSURES FOR NEW DOORS OPENINGS AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 6- PROVIDE COMPLETE DETAILS/ SPECIFICATION SHOWING HOW
 GARAGE DOOR OPENINGS WILL BE CLOSED TO ALLOW FOR NEW
 USE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 REGARDING
 WIND LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 7- PROVIDE COMPLETE FRAMING DETAIL AND STRUCTURAL BUCK
 DETAIL FOR 2X BUCK AS REQUIRED BY PRODUCT APPROVAL
 SUBMITTED.NEED TO PROVIDE COMPLETE SUPPORT TO DOOR
 FRAMING TO COMPLY WITH SEC. R613.1.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR STORM SHUTTERS. ALSO, CLEARLYMARK/CIRCLE
 ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS. EG:
 WALL MOUNTED AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH PRODUCT APPROVAL PROPOSED
 INSTALLATION.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.UPGRADE TOTAL VALUATION OR IT WILL BEUPGRADED
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By btrobaug Date 2007-12-04 Time 11:55 Rev Time 0.00
Received By btrobaug Date 2007-12-04 Time 10:57 Sent To M
Notes
2007-12-04 11:55:35 
  
  
 APPLICATION #07110748
 ELECTRICAL PLAN REVIEW
 516 51ST STREET
 12/3/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} SHOW COMPLIANCE WITH THE RECEPTACLE SPACING
 REQUIREMENTS OF 210.52.
  
 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 3} COMPLY WITH 210.70 LIGHTING REQUIREMENTS, INTERIOR
 AND EXTERIOR.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-12-18 Cont ID  
Sent By jgomez Date 2007-12-18 Time 12:31 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2007-11-30 15:10:40OK PER J PAPA 11-30-07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-18 Cont ID  
Sent By jgomez Date 2007-12-18 Time 12:32 Rev Time 0.00
Received By jgomez Date 2007-12-03 Time 09:31 Sent To  
Notes
2007-12-03 09:31:27TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 14:51 Rev Time 0.30
Received By tgordon Date 2007-12-04 Time 14:51 Sent To Z
Notes
2007-12-04 15:09:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC 13-101.2.
  
 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1.
  
 3) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE
 2004 FBC/R R303.3 EXCEPT.
  
 4) SHOW THE CFM'S. AT ALL SUPPLY AIR GRILLS, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW THE SEER OF THE A/C SYSTEM ON THE MECHANICAL
 PLAN.
  
 6) SHOW THE TOTAL COOLING BTU'S FOR THE A/C SYSTEM ON
 THE MECHANICAL PLANS.
  
 7) SHOW THE HEATER KW OR STATE NO HEAT ON THE
 MECHANICAL PLAN.
  
 8) THE MECHANICAL PLANS NEED THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN (ALLAN WERITZ), AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 1 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 06:27 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 06:27 Sent To B
Notes
2007-12-13 07:18:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE. ONE
 SET OF PLUMBING DRAWINGS ARE IN PENCIL. PER *106.1.3
 QUALITY OF BUILDING PLANS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) (9) PLUMBING, PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH
 CLEANOUT LOCATIONS.
 **THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT HAVE ALL WASTE AND TRAPS SIZED.
  
 3. NOTE: SIZE THE INDICATED POTABLE WATER. PER
 *106.1.2, ADDITIONAL DATA.
  
 4. THE INDICATED VENT TERMINATING THROUGH THE WALL
 SHALL COMPLY WITH THE FOLLWING AND BE INDICATED AS SUCH
 ON THE RESUBMITTAL.
 *904.6 EXTENSION THROUGH THE WALL. VENT TERMINALS
 EXTENDING THROUGH THE WALL SHALL TERMINATE A MINIMUM OF
 10 FEET (3048 MM) FROM THE LOT LINE AND 10 FEET (3048
 MM) ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL
 NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH
 SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE
 PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR
 BLOCKING THE VENT OPENING.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By choops Date 2007-12-03 Time 13:04 Rev Time 0.00
Received By choops Date 2007-12-03 Time 13:04 Sent To E
Notes
2007-12-03 13:05:02***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720