Plan Review Details - Permit 07110726
Plan Review Stops For Permit 07110726
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 09:57 Rev Time 0.00
Received By shill Date 2008-03-19 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By shill Date 2008-01-04 Time 09:47 Rev Time 0.00
Received By shill Date 2008-01-04 Time 09:47 Sent To  
Notes
2008-01-04 09:54:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE FOR THE
 HURRICANE SHUTTERS OR PROVIDE ALL INFORMATION IN
 ANOTHER FORMAT.
  
 2.SEE ATTACHED POLICY REGARDING HURRICANE SHUTTERS ON
 COMMERCIAL BUILDINGS.PLEASE PROVIDE A PRESTORM
 HURRICANE SHUTTER INSTALLATION PLAN AS REQUIRED, SEE
 ITEM #13 (HIGHLIGHTED).THIS SHOULD BE DONE PRIOR TO
 RESUBMITTAL AND MAY BE DONE VIA EMAIL.WHEN A FINAL
 PLAN IS APPROVED, AN ORIGINAL SIGNED BY THE OWNER WILL
 BE REQUIRED.A PLAN MAY BE SUBMITTED AT THE INTAKE
 COUNTER AT CONSTRUCTION SERVICES RATHER THAN BY EMAIL
 IF DESIRED.
  
 3.THIS IMPROVEMENT CROSSES PROPERTY LINES.EITHER
 RECORD A UNITY OF TITLE OR SHOW COMPLIANCE WITH FBC
 TABLE 602, TABLE 704.8.
  
 4.GOVERNING CODES SHOULD INCLUDE 2007 AMENDMENTS
 EFFECTIVE JULY 1, 2007. WWW.FLORIDABUILDING.ORGSEE
 NOTES ON SHEETS LS1, A1, A3 AND POSSIBLY OTHER SHEETS;
 CHECK ALL REFERENCES.
  
 5.PROVIDE MORE INFORMATION IN REGARDS TO THE NEW 4X4
 SLAB, EXISTING CONFERENCE ROOM.ACCESSIBILITY
 REQUIREMENTS AND HOW THIS AFFECTS ACCESSIBILITY IS NOT
 CLEAR.FBC11-4.1.1(1)(A).
  
 6.THE APPLICATION STATES THAT RAILINGS WILL BE
 INSTALLED.THIS IS NOT CONSISTENT WITH THE SCOPE OF
 WORK SHOWN ON THE PLAN.EITHER REVISE THE PLAN TO
 INCLUDE THE RAILING OR REMOVE FROM THE SCOPE OF WORK ON
 THE PERMIT APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2008-04-07 Time 08:15 Sent To  
Notes
2008-04-07 08:15:40TITLE BLOCK LABELS ADDED TO PLANS BY ENG'S REP.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 15:47 Sent To  
Notes
2008-04-03 15:47:24** DENIED 3RD REVIEW **
  
 ** PLANS IN FAILED STATUS UNTIL COMMENT #1 BELOW IS
 ADDRESSED.
  
 1) NOTE: PLEASE SEE THE PLANS HAVE NOW COME BACK WITH
 REMOVING THE ENGINEERING FIRM FROM THE TITLE BLOCKS.
 THE PREVIOUS REVIEWS REQUIRED CERTIFICATE OF
 AUTHORIZATION TO BE PLACED ON PLANS WHICH WAS NOT DONE
 AND PLANS HAVE NOW BEEN REVISED REMOVING FIRM, HOWEVER
 NEW MEP PLANS NOW DO NOT CONTAIN ANY TITLE BLOCKS?? IF
 DOING WORK SOLELY AS AN INDIVIDUAL AS IT SEEMS IS NOW
 TAKING PLACE IS OK, HOWEVER PLANS STILL NEEDS TO
 CONTAIN ALL INFORMATION AS REQUIRED PER FAC
 61G15-23.002.
 THE TITLE BLOCKS NOW ONLY CONTAINS A NOTE WHICH STATES
 THE *SEAL IS AUTHORIZED BY ROBERT CAINE*
 THIS IS REQUIRED FOR ALL TRADES AND ALL SHEETS PER THIS
 DESIGNER.
  
 ** DESIGN PROFESSIONAL MAY CALL TO SET UP A TIME TO
 COME IN AND PLACE ALL INFORMATION ON TITLE BLOCKS. THIS
 MAY BE DONE BY PRINT, STAMPED, STICKER/LABELS ETC IN A
 NEAT FASHION.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By dpalmer Date 2008-03-05 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 19:25 Sent To  
Notes
2008-03-05 19:26:012007-03-05 19:26:01
  
 ** DENIED2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE NUMBER WHICH WAS ADDED TO TITLE
 BLOCKS IN RESPONSE TO COMMENT WHICH REQUIRES THE
 CERTIFICATE OF AUTHORIZATION NUMBER ON PLANS IS NOT THE
 CA NUMBER. THIS MAY BE THE FLORIDA CORPORATE LICENSE
 NUMBER OR SOME OTHER NUMBER HOWEVER IS NOT THE
 ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE FS 471.023, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC
 13-415.2, 13-415.2.ABC.1.1.
 PLEASE SEE THE METHOD OF LIGHTING FIGURES SHOWN ON E-1
 DOES NOT INDICATE WHERE LEVELS ARE FROM
 PLEASE SEE THE LEVELS AS SUBMITTED EXCEED THE LEVELS
 PERMITTED IN EITHER TABLE B OR C IN SEVERAL LOCATIONS
 PLEASE SEE THE FIXTURE LEGEND ON E-1 AND E-2 DO NOT
 CORRELATE. THERE ARE SEVERAL FIXTURE/LUMINAIRE WATTAGES
 WHICH DO NOT MATCH. PLEASE COORDINATE.
  
 3) NOTE: PLEASE SEE THAT THE BUILDING AS DEFINED IS
 SHOWN LESS THEN 5K SQ FT HOWEVER LIGHTING CONTROL PER
 13-415.1.ABC.1.2 IS REQUIRED FOR SEPARATE SPACES.
 PLEASE SEE THAT CONFERENCE ROOM AND OTHER ROOMS AS
 LISTED IN THIS SECTION IS REQUIRED TO CONTAIN AUTOMATED
 CONTROL EVEN IF BUILDING IS UNDER 5K SQ FT. THIS IS A
 NEW COMMENT AS THIS WAS VERIFIED WITH THE FLORIDA
 BUILDING COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS
 SINCE LAST REVIEW.
  
 4) NOTE: PLEASE SEE KEY NOTE #2 ON SHEET E-0 WHICH
 MENTIONS TO SEE *EXXX* FOR REVISED LOAD CAPACITY OF NEW
 PANEL D1.
 THIS SEEMS TO BE A MISPRINT.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED NOT TO ATTACH SUPPORTING DOCUMENTS DOWN THE
 LEFT HAND SIDE OF PLANS YET THE PLANS CAME BACK IN WITH
 THESE DOCUMENTS ATTACHED TO PLANS ONCE AGAIN. THESE
 DOCUMENTS SHOULD BE PLACED IN SEPARATE BINDERS, FOLDERS
 ETC OF SOME KIND.
 THANK YOU ONCE AGAIN FOR YOUR ANTICIPATED COOPERATION.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-04 20:27:352008-03-04 20:27:35
  
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-12-11 Time 16:52 Sent To  
Notes
2007-12-12 08:41:01 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE RELEVANT CODES/DESIGN FOR THIS
 PROJECT IS REQUIRED TO BE STATED ON PLANS.
 PLEASE KNOW THE CODES STATE-WIDE CHANGED ON DECEMBER
 8TH, 2006. PLEASE ALSO KNOW THERE WERE ALSO REVISIONS
 TO THE FLORIDA BUILDING CODE SINCE THAT DATE ALSO.
 PLEASE SEE THE FOLLOWING IS REQUIRED TO BE STATED ON
 PLANS INCLUDING ELECTRICALSHEETS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE THERE ARE SEVERAL CODES SECTIONS WHICH
 ARE REFLECTED ON THE ELECTRICAL PANEL SCHEDULES FOR
 LOAD CALCULATIONS. PLEASE SEE THAT THESE ARE NOT FROM
 THE CURRENT CODE OF THE 2005 NEC.
 THESE ARE FROM THE PREVIOUS CODE. PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ON ALL MEP PLANS
 ARE MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FLORIDA STATUES 471.023. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES
 THIS NUMBER TO BE LOCATED ON TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE ON THE MEP
 PLANS IS NO LONGER VALID WITHIN THE STATE OF FLORIDA.
 PLEASE SEE RULING 61G15-23.001 WHICH WAS PASSED IN
 FEBRUARY 2004. THIS RULE REQUIRED ALL ENGINEERS WITH
 THE WORDING OF *CERTIFICATE* IN SAID SEAL TO HAVE SEALS
 CHANGED TO THE WORDING OF *LICENSE*. THERE WAS AND
 EXTENSION GRANTED TO DECEMBER 31ST, 2005 HOWEVER ALL
 PLANS AFTER THIS DATE MUST HAVE THE NEW SEAL.
 PLEASE OBTAIN NEW SEAL.
 THE SEAL IS NO LONGER ACCEPTABLE ON PLANS IN THE STATE
 AS THIS RULE WAS CHANGED ALMOST THREE YEARS AGO.
 ** PLEASE KNOW WHEN SEALING PLANS PLEASE BE SURE THE
 RAISED SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION
 ON SAID SEAL. THE SEAL IS VERY FAINT AND NOT EASILY
 READ. FS471.025
  
 4) NOTE: PLEASE SEE THE PLANS APPEARS TO BE SIGNED WITH
 *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE OF
 THE DESIGNER PLEASE PROVIDE A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER FOR SIGNATURE VERIFICATION. THIS WILL
 BE PLACED IN SIGNATURE FILE FOR ANY FUTURE REFERENCES.
 PLEASE BE SURE THE NOTARIZED LETTER CONTAINS THE
 INFORMATION AS REQUIRED PER FS 117.05.
 FS 471.025
  
 5) NOTE: PLEASE SEE THE PLANS NOTE IN TWO LOCATIONS
 THAT THE CONTRACTOR IS RESPONSIBLE TO VERIFY LOAD ON
 EXISTING EQUIPMENT AND ADJUST CONDUCTORS, BREAKER SIZES
 ETC AS NEEDED.
 PLEASE KNOW THE RESPONSIBILITY IS THAT OF THE ENGINEER
 UNDER RESPONSIBILITY OF DESIGNS UNDER FAC 61G15-33.003
 AND 61G15-33.003.
 ALL LOADS ON EXISTING EQUIPMENT SHALL BE VERIFIED AT
 THIS TIME AS THE CODE REQUIRES THIS AS A MINIMUM.
 PLEASE SEE 220.87, 220.
 PLEASE SUBMIT LOAD ON THE EXISTING MDP WITH NEW AND
 EXISTING LOADS BEING ADDED.
 PLEASE MAKE ANY CHANGES TO EQUIPMENT, CONDUCTORS,
 BREAKERS ETC AS NEEDED.
  
 6) NOTE: PLEASE SEE THE LOCATION OF PANEL *D* AS NOTED
 ON PANEL SCHEDULE MENTIONS THIS PANEL IS LOCATED IN THE
 ELECTRICAL ROOM, HOWEVER THE PANEL ON PLANS IS SHOWN IN
 THE CONFERENCE ROOM.
 PLEASE VERIFY THIS LOCATION.
 PLEASE ALSO VERIFY THE LOCATION OF THE NEW PANEL AS THE
 PLANS APPEAR TO SHOW WHAT APPEARS TO BE SOME SORT OF
 BOX IN FRONT OF PANEL ON ONE SIDE.
 PLEASE SEE 110.26, 240.24 ETC FOR LOCATION OF PANELS
 AND MINIMUM CLEARANCES.
  
 7) NOTE: PLEASE CLARIFY THE PANEL SIZE AND BREAKER AS
 SHOWN. PLEASE SEE FOR EXAMPLE: THE PANEL IS BEING SHOWN
 AS 100AMP MCB (MAIN CIRCUIT BREAKER) ON SCHEDULE,
 HOWEVER RISER SHOWS THIS AS A 60AMP MLO (MAIN LUG
 ONLY).
 WHICH ONE IS IT?
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 8) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 AND PROVIDE NOTES ON
 PLANS PER 13-413.1.ABC.2.1 AND .2.2.
  
 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 AND
 PROVIDE LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE INTERIOR LIGHTING ALLOWANCES ALSO PER
 13-415.2.ABC .1.2 ETC.
 PLEASE BE SURE ALL CALCULATIONS CORRELATE WITH THE
 FIXTURE LEGEND AS SHOWN.
  
 11) NOTE: WHEN SUBMITTING SUPPORTING DOCUMENTS SUCH AS
 CALCULATIONS, PRODUCT APPROVALS ETC PLEASE DO NOT
 ATTACH DOWN THE LEFT HAND SIDE OF THE PLANS.
 THIS WILL HELP IN PROCESSING OF PLANS. YOUR COOPERATION
 IS APPRECIATED.
 FBC ADMIN 106.1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-12 07:31:05 
 IN ELEC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By rchokshi Date 2008-03-03 Time 15:20 Rev Time 0.00
Received By rchokshi Date 2008-03-03 Time 15:20 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By rchokshi Date 2007-12-13 Time 08:43 Rev Time 0.00
Received By rchokshi Date 2007-12-13 Time 08:38 Sent To  
Notes
2007-12-13 08:43:17FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 3. YOU ARE PUTTING AN APPROACH, DRIVEWAY, SIDEWALK &
 CUTTING A CURB IN CITY'S RIGHT OF WAY. THEREFORE, YOU
 NEED CITY'S RIGHT OF WAY APPROVAL FROM WINDEL PALMER
 494-1040, 1000 45TH STREET, ENG DEPT.ONCE WE HAVE AN
 APPROVAL FROM WINDEL PALMER, WE WILL REVIEW YOUR
 DRAWINGS.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By mawillia Date 2008-04-14 Time 11:29 Rev Time 0.00
Received By mawillia Date 2008-04-14 Time 11:11 Sent To B
Notes
2008-04-14 11:25:56*****APPROVED*****
  
  
 PLAN SHEET E-0 STAMPED, INITIALED, AND DATED;PLAN
 SHEETS LS1, A2, AND A3 PREVIOUSLY FIRE-STAMPED
 (APPROVED) ON 03/22/08.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-03-22 Time 17:55 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 17:33 Sent To  
Notes
2008-03-22 17:54:32*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED.PLAN SHEETS LS1, A2, AND A3 WERE
 STAMPED, INITIALED, AND DATED; HOWEVER PLAN SHEET E-0
 TO BE FIRE-STAMPED WHEN THE ELECTRIC REVIEW COMMENTS
 HAVE BEEN ADDRESSED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By mawillia Date 2007-12-26 Time 17:44 Rev Time 0.00
Received By mawillia Date 2007-12-26 Time 17:08 Sent To  
Notes
2007-12-26 17:43:35*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE
 LANES).
  
 3.BUILDINGS OR PORTIONS OF THE BUILDINGS SHALL BE
 PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR,
 ALTERATION, OR ADDITIONS ONLY WHERE THE REQUIRED MEANS
 OF EGRESS AND REQUIRED FIRE PROTECTION ARE IN PLACE AND
 MAINTAINED.
  
 4.IF/WHEN IT IS NECESSARY TO TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM DURING ALTERATION, THE FIRE
 DEPARTMENT SHALL BE NOTIFIED WHEN THE SYSTEM IS SHUT
 DOWN AND WHEN IT IS RETURNED TO SERVICE.
  
 5.IF THE SCOPE OF WORK HAS CAUSE FOR THE FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM TO BE ALTERED, SEPARATE
 PLANS AND PERMIT WILL BE REQUIRED FOR THE REMODEL.
  
 6.THE INSTALLATION OF THE HURRICANE SHUTTERS, WHETHER
 IN THE OPEN OR CLOSED POSITION, SHALL NOT OBSCURE OR
 BLOCK VISIBLITY OF THE BUILDING'S ADDRESS NUMBERS.
  
  
 TO EXPEDITE THE P[LAN REVIEW PROCESS, INCLUDE A
 RESPONSE LETTER INDICATING WHERE ON THE PLAN EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 10:04 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 10:03 Sent To  
Notes
2008-04-01 10:06:44TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 09:01 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 09:01 Sent To  
Notes
2008-02-20 09:04:01TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-01-04 Time 08:59 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 09:53 Sent To  
Notes
2007-12-03 08:41:56TO "COMM" BD#12
2007-11-30 09:54:09WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-12 Cont ID  
Sent By rregueir Date 2008-04-12 Time 13:09 Rev Time 0.00
Received By rregueir Date 2008-04-12 Time 12:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By rregueir Date 2008-03-16 Time 16:02 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 15:27 Sent To  
Notes
2008-03-17 08:56:08REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 AS STATED IN PREVIOUS ELECTRICAL REVIEW, THE
 ENGINEERING FIRM'S CERTIFICATE OF AUTHORIZATION NUMBER
 MUST APPEAR ON PLANS ALONG WITH THE PRINTED NAME AND
 PRINTED LICENSE NUMBER OF THE ENGINEER.
  
 FAC RULE 61G15-23.002(2): EACH SHEET OF PLANS AND
 PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. A
 TITLE BLOCK ON EACH SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE ENGINEER OR IF
 APPLICABLE, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER, AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS WILL
 SATISFY THIS REQUIREMENT.
  
 PLEASE CORRECT MISSING INFORMATION. THIS ENGINEERING
 BUSINESS REQUIRES A CERTIFICATE OF AUTHORIZATION
 LICENSE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By rregueir Date 2007-12-12 Time 13:07 Rev Time 0.00
Received By rregueir Date 2007-12-12 Time 09:44 Sent To  
Notes
2007-12-12 13:07:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. COVER SHEET INDICATES THERE SHOULD BE TWO MECHANICAL
 PAGES, M-1 AND M-2. HOWEVER, ONLY PAGE M-1 COULD BE
 FOUND IN PLANS. PLEASE CLARIFY AND/OR PROVIDE MISSING
 INFORMATION. FBC 106.1.1
  
 2. PG LS1 DECLARES THIS TO BE A LEVEL 2 ALTERATION. ALL
 RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBC, EB
 609.1. PROVIDE OUTSIDE AIR CALCULATIONS WHICH INCLUDE
 OCCUPANCY CLASSIFICATIONS OF SPACES, OCCUPANT LOADS OF
 SPACES AND OUTSIDE AIR REQUIRED FOR EACH SPACE AS
 INDICATED IN FBC, M TABLE 403.3.
  
 3. M-1: THERE ARE NO DUCT SIZES SHOWN ON PLANS. PROVIDE
 ALL DUCT SIZES TO SHOW A COMPLETE DESIGN OF THE DUCT
 SYSTEM. FBC, M 601.1 AND FBC 106.1.1.
  
 4. M-1: RETURN GRILL IN THE WAITING AREA DOES NOT HAVE
 ANY CORRESPONDING DUCTWORK SHOWN. SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED IN THIS AREA IN ACCORDANCE
 WITH FBC, M 601.4. ALSO, THERE ARE A FEW LOCATIONS
 WHERE THERE ARE MULTIPLE GRILLS SHOWN ON PLAN WITH ONLY
 SOME HAVING DUCTWORK ROUTED TO THEM. EXAMPLE: WAITING
 AREA SHOWS 4 OR 5 SUPPLY GRILLS WITH ONLY 2 OF THEM
 BEING DUCTED. PLEASE CLARIFY. FBC, M 603.1 AND FBC
 106.1.1
  
 5. M-1: PROVIDE INFORMATION OR EQUIPMENT SCHEDULE FOR
 TOILET EXHAUST FAN. EXHAUST RATE SHALL BE AS REQUIRED
 BY FBC, M TABLE 403.3. ALSO, SHOW HOW FAN IS TO BE
 CONTROLLED TO ASSURE ALL AIR SUPPLIED TO THIS ROOM IS
 EXHAUSTED IN ACCORDANCE WITH FBC, M 403.2.1(3).
  
 6. SHOW THE TYPE AND R-VALUE OF SUPPLY AND RETURN DUCT
 TO BE USED. AIR DISTRIBUTION SYSTEM COMPONENTS ARE TO
 HAVE MINIMUM INSULATION LEVELS IN ACCORDANCE WITH FBC
 TABLE 13-410.1.ABC.2.2. NO INFORMATION COULD BE FOUND
 ON PLANS INDICATING THE TYPE OR R-VALUE OF ROOF
 INSULATION IN THE EXISTING BUILDING. THIS INFORMATION
 IS REQUIRED TO DETERMINE THE REQUIRED MINIMUM R-VALUE
 OF INSULATION FOR THE AIR DISTRIBUTION SYSTEM.
 NOTE: IF THIS IS AN ATTIC WITH CEILING INSULATION, ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS. AT LEAST ONE
 PORTION OF THE WORK AREA IS SHOWN WITH A DROPPED GRID
 CEILING AREA. INSULATION MAY NOT BE INSTALLED ON THIS
 CEILING IN ACCORDANCE WITH FBC 13-404.1.ABC.1.
  
 7. PLEASE SEE ELECTRICAL COMMENTS REGARDING THE
 SIGNATURE, SEAL AND MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE DESIGNER OF RECORD. MAKE
 NECESSARY CORRECTIONS PRIOR TO RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS OR FIND ANY OF THESE REVIEW
 COMMENTS TO BE UNCLEAR, PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By kstevens Date 2008-04-14 Time 07:28 Rev Time 0.00
Received By kstevens Date 2008-04-14 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 06:30 Rev Time 0.00
Received By kstevens Date 2008-03-25 Time 19:00 Sent To  
Notes
2008-03-26 06:47:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A4 ADA UNISEX TOILET DETAIL. SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, NOT SHOWN ON PLANS.
 OK
 ___FOR LAV
 A. 11-4.19.5 FAUCETS
 ****RESPONSE NOTED, BUT FAUCET TYPE NOT INDICATED.
  
 NOTE: SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 3. ALL PME SHEETS IF THE ENGINEER IS PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
 ****RESPONSE NOTED, BUT NO CERTIFICATE OF AUTHORIZATION
 FOR CAINE ENGINEERING INC. IS INDICATED ON THE STATE OF
 FLORIDA DBPR WEBSITE. THE NUMBER IN THE TITLE BLOCK IS
 NOT A CERTIFICATE OF AUTHORIZATION NUMBER.
  
 4. OK
 5. OK
  
 6. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE
 WATER PIPING SHOWING ALL PIPE SIZES, VALVES ETC.
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE.--WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI_WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 7. OK
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-15 Cont ID  
Sent By kstevens Date 2007-12-15 Time 10:56 Rev Time 0.00
Received By kstevens Date 2007-12-15 Time 10:56 Sent To  
Notes
2007-12-15 11:14:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. RELATIVE CODES THAT THE PROJECT IS TO BE DESIGNED TO
 ARE THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE ON
 THE PLANS.
  
 2. SHT A4 ADA UNISEX TOILET DETAIL. SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.5 FLUSH CONTROLS
 W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. FIG. 28. PLEASE SHOW ON DETAIL.
 ___FOR LAV
 A. 11-4.19.5 FAUCETS
  
 3. ALL PME SHEETS IF THE ENGINEER IS PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
  
 4. ALL PME SHEETS. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. THE SIGNATURE IS REQUIRED. IT APPEARS THAT
 INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 DATED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 SHALL BE SUBMITTED FOR OUR RECORDS. FAC 61G15-23.002(1)
 & FS 471.025.
  
 5. ALL PME SHEETS. THE SEAL USED IS NOT APPROVED. PER
 THE LETTER FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS, AS OF JAN. 1 2006, (AFTER A 2 YEAR GRACE
 PERIOD), THE SEAL SHALL BE CHANGED FROM THE WORD
 "CERTIFICATE" TO THE WORD "LICENSE". PLEASE SEAL WITH
 THE NEW SEAL, AND MAKE SURE ALL INFORMATION REQUIRED ON
 THE EMBOSSED SEAL IS IMPRESSED ON EACH SHEET.
  
 6. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE
 WATER PIPING SHOWING ALL PIPE SIZES, VALVES ETC.
 SECTION 106.3.5.1.3.
  
 7. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE
 SANITARY PIPING SHOWING ALL PIPE SIZES, TRAPS, & VENTS.
 SECTION 106.3.5.1.3.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-26 Cont ID  
Sent By choops Date 2008-02-26 Time 11:06 Rev Time 0.00
Received By choops Date 2008-02-26 Time 11:06 Sent To  
Notes
2008-02-26 11:06:32***APPROVED - RESUB #1***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By choops Date 2007-12-05 Time 10:08 Rev Time 0.00
Received By choops Date 2007-12-05 Time 10:08 Sent To  
Notes
2007-12-05 10:11:11***FAILED***
  
  
 1)A RECORDED UNITY OF TITLE SHALL BE PROVIDED,
 UNIFYING PCN 74-43-43-04-00-000-3080 AND PCN
 74-43-43-04-17-000-0020.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved