| 2007-12-04 08:08:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS LINE 11A STATES RETURN AIR DUCTS |
| | ARE IN A CONDITIONED SPACE AND THE AIR HANDLER IN |
| | INSTALLED IN THE INTERIOR, THE MECHANICAL PLANS SHOW |
| | THE RETURN AIR DUCTS AND AIR HANDLER ARE IN THE ATTIC. |
| | PLEASE CORRECT ENERGY CAL'S. SEE 2004 FBC |
| | 13-610.2.A.1. |
| | |
| | 2) ENERGY CALCULATIONS LINE 15 IS TAKING MULTIZONE |
| | CREDIT, AS THE ENERGY CAL'S. ARE FOR THE ADDITION ONLY |
| | OTHER PARTS OF THE BUILDING MAY NOT BE INCLUDED. YOU |
| | MAY DO THE ENERGY CAL'S. FOR THE WHOLE BUILDING OR |
| | REMOVE THE MZ-C. SEE 2004 FBC 13-607.2.A.3.2. |
| | |
| | 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 4) THE JOB ADDRESS NEEDS TO BE ON THE MECHANICAL PLAN, |
| | SEE 2004 WPB AMEND. 106.1.3. |
| | |
| | 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON |
| | THEM, SEE W.P.B. AMEND. 106.1.3. |
| | |