Plan Review Details - Permit 07110645
Plan Review Stops For Permit 07110645
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-07 Cont ID  
Sent By lmartine Date 2008-07-07 Time 11:10 Rev Time 0.00
Received By lmartine Date 2008-07-07 Time 11:10 Sent To  
Notes
2008-07-07 11:11:28ALL WORK SHOWN IS EXISTINGLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-07 Cont ID  
Sent By kconrad Date 2008-02-07 Time 20:05 Rev Time 0.00
Received By kconrad Date 2008-02-07 Time 16:34 Sent To  
Notes
2008-02-07 18:08:04PROJECT: 721 38TH STREET/ #07110645
  
 PROJECT DETAIL: CHANGE OF OCCUPANCY (R-3 TO R-4)
  
 CODE REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS, CHAPTER 1, 2004
 EDITION
  
  
 STATUS: FAIL
  
 COMMENTS:
  
 1) PLEASE PROVIDE CLARIFICATION OF THE PROPSED SCOPE OF
 WORK: INDICATE ARES OF EXISTING CONSTRUCTION AND NEW
 CONSTRUCTION.
  
 2) 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 FEBC
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4) PLEASE PROVIDE WINDOW AND DOOR PRODUCT APPROVALS X 2
 COPIES FOR NEW WINDOW/DOOR INSTALLATION.
  
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR NEW ROOF
 COVERING.
  
 6) PLEASE INDICATE THE DESIGN PRESSURES FOR THE
 OFFICE/BATHROOM DOORS AND OFFICE WINDOW.
  
 7) PLEASE INDICATE THE EXISTING BEDROOM WINDOW
 DIMENSIONS. THE WINDOWS SHALL COMPLY WITH FEBC, SECTION
 812.4.1.1:
  
 812.4.1.1MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A HIGHER
 HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 812.4.1, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTIONS:
 1. STAIRWAYS SHALL BE ENCLOSED IN COMPLIANCE WITH THE
 APPLICABLE PROVISIONS OF SECTION 703.1. 2. EXISTING
 STAIRWAYS INCLUDING HANDRAILS AND GUARDS COMPLYING WITH
 THE REQUIREMENTS OF CHAPTER 7 SHALL BE PERMITTED FOR
 CONTINUED USE SUBJECT TO APPROVAL OF THE CODE
 OFFICIAL.
 3. ANY STAIRWAY REPLACING AN EXISTING STAIRWAY WITHIN A
 SPACE WHERE, BECAUSE OF EXISTING CONSTRUCTION, THE
 PITCH OR SLOPE CANNOT BE REDUCED, SHALL BE PERMITTED
 FOR CONTINUED USE SUBJECT TO APPROVAL OF THE BUILDING
 CODE OFFICIAL.
 4. WHERE AN EXISTING CORRIDOR IS REQUIRED TO BE FIRE
 RATED, EQUIVALENCY CAN BE ACHIEVED BY EITHER
 SPRINKLERING THE BUILDING OR USING EQUIVALENCY AS PER
 NFPA 914 OR CHAPTER 7 OF THE FLORIDA BUILDING CODE,
 BUILDING FOR FIRE RESISTANCE. ALSO, SEE SECTION 1001.2
 OF THE FLORIDA BUILDING CODE, BUILDING. 5. EXISTING
 CORRIDOR DOORWAYS, TRANSOMS, AND OTHER CORRIDOR
 OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN SECTIONS
 605.5.1, 605.5.2, AND 605.5.3. 6. EXISTING DEAD-END
 CORRIDORS SHALL COMPLY WITH THE REQUIREMENTS IN SECTION
 605.6.
 7. WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 REQUIRED, AN EXISTING OPERABLE WINDOW WITH CLEAR
 OPENING AREA NO LESS THAN 4 SQUARE FEET (0.38 M2) AND
 WITH MINIMUM OPENING HEIGHT AND WIDTH OF 22 INCHES (559
 MM) AND 20 INCHES (508 MM), RESPECTIVELY, WITH MAXIMUM
 SILL HEIGHT AT 44 INCHES (1118 MM) ABOVE THE FLOOR OR
 APPROVED PERMANENT ELEVATED AREA, SHALL BE ACCEPTED AS
 AN EMERGENCY ESCAPE AND RESCUE OPENING.
  
 8) PLEASE INDICATE THE PROPOSED OCCUPANT LOAD:
  
 FBC 1004.1DESIGN OCCUPANT LOAD.
 IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER
 OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL
 BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER
 COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH
 1004.1.3.
  
 9) PLEASE SHOW ACCESSIBLE ROUTE, PARKING, RAMPS AND
 ACCESSIBLE BATHROOMS AND INDICATE DIMENSIONS:
  
 812.5ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By kconrad Date 2007-12-04 Time 19:34 Rev Time 0.00
Received By kconrad Date 2007-12-04 Time 19:34 Sent To I
Notes
2007-12-04 19:36:50REQUIRE PLANS AS PER THE FBC 106.3.5. THE SAME SHALL
 COMPLY WITH THE MINIMUM REQUIREMENTS OF SECTION 812 OF
 THE FLORIDA EXISTING BUILDING CODE FOR THE CHANGE OF
 OCCUPANCY CLASSIFICATION.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By btrobaug Date 2008-07-03 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2008-07-03 Time 10:49 Sent To  
Notes
2008-07-03 10:50:40 
  
  
 THERE IS NO ELECTRICAL WORK TO BE DONE UNDER THIS
 PERMIT, ALL WIRING IS EXISTING./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By btrobaug Date 2008-02-04 Time 11:34 Rev Time 0.00
Received By btrobaug Date 2008-02-01 Time 06:58 Sent To FIRE
Notes
2008-02-04 11:34:05 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON SHEET 5
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, AND LOCATE ALL SERVICE EQUIPMENT ON
 THE PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS, SO
 THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED. PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND
 CONDUIT SIZE AND TYPE.
  
 2} GFI RECEPTACLES ARE REQUIRED IN THE KITCHEN PER
 210.8(B)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By mwennerg Date 2008-07-03 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 10:39 Sent To  
Notes
2008-07-03 10:39:54EXISTING CONDITION NO NEW ALTERATIONS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By mawillia Date 2008-02-06 Time 23:24 Rev Time 0.00
Received By mawillia Date 2008-02-06 Time 22:37 Sent To  
Notes
2008-02-06 23:24:20*****DENIED*****
  
  
 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05.BE ADVISED THAT THIS SCOPE OF WORK WILL REQUIRE A
 CONVERSION FROM THAT A OF RESIDENTIAL OCCUPANCY.NFPA
 101 - 2003 EDITION DOES NOT RECOGNIZE GROUP HOMES;
 THEREFORE LIST THE OCCUPANCY TYPE FOR THIS PROJECT (
 NEW DAY-CARE, NEW RESIDENTIAL BOARD AND CARE - SMALL
 FACILITY, ETC.) TO FURTHER BASE THE FIRE REVIEW.
  
 06.IF THE OCCUPANCY IS OTHER THAN RESIDENTIAL,
 ADDRESS NUMBERS (AS PER WEST PALM BEACH CODE) SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 STROKE. DISPLAY/SHOW THE ADDRESS NUMBER ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 38TH
 STREET.
  
 07.IN CONVERSIONS, DOORS SHALL BE PERMITTED TO BE 28
 " WIDE.
  
 08.BATHROOM DOORS SHALL BE AT LEAST 24" WIDE AND
 SHALL BE DESIGNED TO ALLOW OPENING FROM THE OUTSIDE
 DURING AN EMERGENCY WHEN LOCKED.
  
 09.ALL OTHER DOORS AND PATHS OF TRAVEL TO A MEANS OF
 ESCAPE SHALL BE AT LEAST 32" WIDE.
  
 10.EVERY CLOSET DOOR LATCH SHALL BE READILY OPENED
 FROM THE INSIDE.
  
 11.SLEEPING ROOMS THAT DO NOT HAVE A DOOR LEADING
 DIRECTLY TO THE OUTSIDE OF THE BUILDING, SHALL HAVE AN
 OUTSIDE WINDOW PROVIDING A CLEAR OPENING OF NOT LESS
 THAN 5.7 SQ.FT. WITH THE WIDTH NOT LESS THAN 20" AND
 THE HEIGHT NOT LESS THAN 24".THE BOTTOM OF THE
 OPENING SHALL BE NOT MORE THAN 44" ABOVE THE FLOOR.
  
 12.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR
 CLASS II.
  
 13.A MANUAL FIRE ALARM SYSTEM WITH OCCUPANT
 NOTIFICATION, SHALL BE PROVIDED AUTOMATICALLY WITHOUT
 DELAY, IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM
 CODE, 2002 EDITION.
  
 14.IN CONVERSIONS, SPRINKLERS SHALL NOT BE REQUIRED
 IN SMALL BOARD AND CARE HOMES, SERVING EIGHT OR FEWER
 RESIDENTS, WHEN ALL OCCUPANTS HAVE THE ABILITY TO AS A
 GROUP TO MOVE RELIABLY TO A POINT OF SAFETY WITHIN 3
 MINUTES.PLEASE ADVISE AS TO THE NUMBER OF RESIDENTS
 PROJECTED.
  
 15.THE SEPARATION WALLS OF THE SLEEPING ROOMS SHALL
 BE CAPABLE OF RESISTING FIRE FOR AT LEAST 1/2 HOUR.
  
 16.SLEEPING ROOM DOORS SHALL BE SUBSTANTIAL DOORS,
 SUCH AS THOSE OF 1 3/4-IN THICK, SOLID BONDED WOOD CORE
 CONSTRUCTION OR OF OTHER CONSTRUCTION OF EQUAL OR
 GREATER STABILITY AND FIRE INTEGRITY.
  
 17.DOORS SHALL MEET THE FOLLOWING REQUIREMENTS:(1)
 DOORS SHALL BE PROVIDED WITH LATCHES OR OTHER
 MECHANISMS SUITABLE FOR KEEPING THE DOORS CLOSED;(2)
 NO DOOR SHALL BE ARRANGED TO PREVENT THE OCCUPANT FROM
 CLOSING THE DOOR;(3) DOORS SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UNLESS THE BUILDING IS PROTECTED
 THROUGHOUT BY AN APPROVED, AUTOMATIC SPRINKLER SYSTEM.
  
 18.NO STOVE OR COMBUSTION HEATER SHALL BE LOCATED TO
 BLOCK ESCAPE IN CASE OF FIRE CAUSED BY THE MALFUNCTION
 OF THE STOVE OR HEATER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-11 Cont ID  
Sent By tgordon Date 2008-02-11 Time 15:46 Rev Time 0.00
Received By tgordon Date 2008-01-31 Time 09:17 Sent To  
Notes
2008-02-07 13:55:442/7/08--TO "BOB"#7
2008-01-31 09:18:01TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-02-11 Cont ID  
Sent By tgordon Date 2008-02-11 Time 15:46 Rev Time 0.30
Received By tgordon Date 2008-02-11 Time 15:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-07-07 Cont ID  
Sent By lmartine Date 2008-07-07 Time 11:12 Rev Time 0.00
Received By lmartine Date 2008-07-07 Time 11:12 Sent To  
Notes
2008-07-07 11:13:32ALL WORK SHOWN IS EXISTING, NO NEW PLUMBING WORK.
 LM

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By jleech Date 2008-02-11 Time 14:23 Rev Time 0.00
Received By jleech Date 2008-02-11 Time 13:35 Sent To  
Notes
2008-02-11 14:43:29DENIED;
 1. LIST ON PLANS THE NUMBER OF RESIDENTS THAT WILL LIVE
 IN HOUSE. PER FBC-2004 EXISTING BUILDING CODE SECTION
 810.
 2. MINIMUM PLUMBING FIXTURES REQUIRES A DRINKING
 FOUNTAIN AND A SERVICE SINK. SEE FBC PLUMBING TABLE
 403.1.
 3. BATHROOMS MUST BE HANDICAP ACCESSIBLE PER EXISTING
 BUILDING CODE SECTION 812.5. SHOW TURNING RADIUS IN
 EACH BATHROOM, AND DETAILS OF W/C, LAVATORY, AND SHOWER
 OR TUB PER FBC BUILDING CHAPTER 11, SECTIONS 11-4.15
 DRINKING FOUNTAIN, 11-4.16 TOILET, 11-4.19 LAVATORYS
 AND MIRRORS, AND 11-4.21 SHOWERS.
 4. A BACKFLOW WILL ALSO BE REQUIRED AT THE WATER METER
 PER UTILITY DEPARTMENT ORDINANCE # 2853-95. PLEASE ADD
 NOTE TO PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By choops Date 2008-01-31 Time 14:13 Rev Time 0.00
Received By choops Date 2008-01-31 Time 14:13 Sent To E
Notes
2008-01-31 14:16:39***N/R - NO WORK PROPOSED, CHANGE OF OCCUPANCY
 ONLY...APPROVED BY ZONING DEPARTMENT***
  
  
  
  
 SENT TO "E" - SF RACK