Plan Review Details - Permit 07110619
Plan Review Stops For Permit 07110619
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-20 Cont ID  
Sent By jgomez Date 2008-10-20 Time 16:38 Rev Time 0.00
Received By jgomez Date 2008-10-20 Time 16:38 Sent To  
Notes
2008-10-20 16:39:09MET WITH MR. SHELDON TO GO OVER PROVISO ITEMS. PRODUCT
 APPROVALS ARE IN FILE SET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-04 Cont ID  
Sent By jgomez Date 2008-03-04 Time 10:17 Rev Time 0.00
Received By jgomez Date 2008-03-04 Time 10:17 Sent To PC
Notes
2008-03-04 10:25:42REVISION CHECKLIST:
  
 1- PROVIDE PRODUCT APPROVAL FOR GARAGE DOORS THAT MEET
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT.
  
 ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE PRODUCT
 APRPOVAL IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
 SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 2- CLEARLY MARKON ALLWINDOW/DOOR MULLIONPRODUCT
 APPROVALS THE SPECIFIC MULLION SIZEAND ANCHORING TO
 VERIFY COMPLIANCE WITH SEC. R301 AND THE CALCULATED
 DESIGN PRESSURES.
  
 (NOTE: THERE ARE MANY SIZES THAT DON'T RESIST THE
 DESIGN PRESSURES, THAT'S WHY THIS IS REQUESTED PRIOR TO
 INSTALLATION TO AVOID CONFLICTS OR DELAYS. THIS
 COMMENT APPLIES TO DOORS AND WINDOWS ALSO).
  
 3- CLEARLY MARK ON ALL WINDOWS AND DOORSPRODUCT
 APPROVALSTHE SPECIFIC WINDOW AND DOORS TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 AND THE
 CALCULATED DESIGN PRESSURES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By jgomez Date 2008-01-29 Time 15:53 Rev Time 0.00
Received By jgomez Date 2008-01-29 Time 15:53 Sent To  
Notes
2008-01-29 15:54:04PARCEL SOIL TEST REPORT. ONLY ONE COPY SUBMITTED.
 CONTRACTOR SAID COMPACTION TESTS WILL BE PROVIDED TO
 THE INSPECTOR AT TIME OF INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By jgomez Date 2008-01-24 Time 09:57 Rev Time 0.00
Received By jgomez Date 2008-01-23 Time 15:27 Sent To PC
Notes
2008-01-24 10:04:54BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE 2 COPIES OF SOIL TEST REPORT.THEY WERE
 NOTSUBMITTED WITH RE-SUBMITTAL PACKAGE.SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 2- REVISED ENERGY CALCULATIONS ARE TAKING THE CEILING
 FAN CREDIT.NEED TO PROVIDE REVISED ELECTRICALPLAN
 SHOWINGCEILING FAN SIZE IN ALL ROOMSTO VERIFY
 COMPLIANCE WITHTABLE 13-607.1.A.1 FBC 2004.
  
 3- REVISE DOOR BUCK DETAIL.1 1/2" LONG TAPCON IS NOT
 LONG ENOUGH TO BE USED ON A 2X BUCK. REVISE AS
 REQUIRED.
  
 NOTE: ADDED 2-11-08:REVISE BUILDING EXPOSUREFROM
 "B" TO "C" AND THE DESIGN PRESSURES AS REQUIRED BY SEC.
 R301.2.1.4(3).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By jgomez Date 2007-12-14 Time 16:55 Rev Time 0.00
Received By jgomez Date 2007-12-14 Time 16:55 Sent To PC
Notes
2007-12-14 16:57:48NEW SFR BUILDING REVIEW FIRST CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDERECORDED NOTICE OF COMMENCEMENT.SEC.
 713.13 FLORIDA STATUTE.
  
 2- PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT.
  
 3- SURVEYS TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 4- AREA CALCULATION NEED TO INCLUDE REAR PORCH AREA BY
 THE BREAKFAST AND LIVING ROOM AREA TO PROPERLY ASSESS
 THE PERMIT VALUATION AND RADON FEES.FEES WILL BE
 ADJUSTED ONCE TOTAL AREA IS INCLUDED.
  
 5- SPECIFY DOOR LEADING TO THE LIVING AREA FROM THE
 GARAGE AREA TO SHOW COMPLIANCE WITH SEC. R309.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR BBQ HOOD LISTED
 AND APPROVED FOR EXTERIOR INSTALLATION AS SHOWN ON
 PLANS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 INFORMATION SUBMITTED DOESN'T SPECIFY THAT HOOD WAS
 DESIGNED AND APPROVED FOR EXTERIOR INSTALLATION.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS. NOA 03-0605.04 SUBMITTED IS FOR
 4", 6" AND 12" LINTELS, NOT FOR 8" LINTELS AS SPECIFIED
 ON PLANS.
  
 B) WINDOW MULLIONS. NONE SUBMITTED AT THIS TIME.
  
 C) ALL SIMPSON, SEMCO OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 ***NOTE:PROVIDETHE FLORIDA PRODUCT APPROVALCOVER
 PAGE AND PAGE SHOWING THE CONNECTOR ONLY. NO NEED TO
 SUBMIT THE FULL REPORT. SOME OF THE PRODUCT APPROVALS
 ONLY PROVIDED THE COVER PAGE AND THEY ARE MISSING THE
 PAGE WITH THE SPECIFIC CONNECTOR.
  
 D) 9'-0" WIDE GARAGE DOORS AS SHOWN ON PLANS.
 PRODUCT APPROVAL SUBMITTED ARE FOR 16' WIDE DOORS.
  
 E) FIXED WINDOW 6060 IN MASTER BEDROOM. PRODUCT
 APPROVAL SUBMITTED DOESN'T COVER THIS WINDOW SIZE.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2CITY AMENDMENTSTO FBC
 2004 TO VERIFY COMPLIANCE WITH UPLIFT RESISTANCE SHOWN
 ON THE PRODUCT APPROVAL.DON'T SPECIFY PER PRODUCT
 APPROVAL.IF USING NAILS OR SCREWS, THEN SPECIFY TYPE
 AND NUMBER. IF USING POLYFOAM, THEN PROVIDE PRODUCT
 APPROVAL. SEE NOA SUBMITTED FOR TYPE OF POLYFOAM TO BE
 USED.
  
 10- PROVIDE ROOF SHEATHING SPECIFICATIONS. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN.
 TYPE,SIZE AND SPACING OF NAIL TO BE USED, INCLUDING
 ROOF ZONES #3.
  
 11- PROVIDE AT LEAST ONE BATHROOM WITH DOORHAVING 29"
 MIN. CLEAR OPENING AS REQUIRED BY SEC. 11-11.1 FBC
 2004.
  
 12- SOME EXTERIOR ELEVATIONS ARE MISSING THE OPENING
 DESIGN PRESSURES. PROVIDE ALL THE DESIGN PRESSURES FOR
 ALL OPENINGS, INCLUDING THE GARAGE DOORS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 13- ONLY THE COVER PAGE WAS SIGNED AND SEALED. ALL
 DRAWINGS NEED TO BE SIGNED, SEALED AND DATED AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 14- ENERGY CALCULATIONS:
 A) REVISE CEILING ATTIC AREA. SEE SEC. 13-604.1.A.1
 FBC 2004 AND REVISE AS REQUIRED.
  
 B) REVISE OVERHANG LENGTH AND HEIGHT. SEE DRAWINGS
 FOR CORRECT INFORMATION AND REVISE AS REQUIRED.
  
 15- SHEET A1:
 A) UPDATE CODE REFERENCE REVISIONS. CURRENT
 REVISIONS ARE 2007, NOT 2006.
  
 B) CLARIFY/REVISE WHY MIN. SOIL BEARING PRESSURE IS
 N/A?.
  
 16- SHEET A3:
 A) CLARIFY/REVISEFOOTING SHOWN ON FOUNDATION PLAN
 BYONE CAR GARAGE.
  
 B) PROVIDE COMPLETE DESIGN PLANS, DETAILS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURE TO VERIFY
 COMPLIANCE WITH CHAPTER 20 FBC 2004.. OTHERWISE,
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
  
 17- SHEET A5:
 A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 FOR NUMBER/SIZE OF NAILS AND ALL LOADS FOR WHICH
 CONNECTORS ARE DESIGNED AND REVISE AS REQUIRED.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING ANALYSISWHEN
 NAILS AND LOADS DON'T MATCH THOSE TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 B) CLARIFY TYPE OF CONNECTOR SPECIFIED ON ROOF
 FRAMING PLAN BY FAMILY ROOM, LANAI AND BEDROOM #5 AREA.
 THERE ARE TWO DIFFERENT CONNECTORS SHOWN. SEE COMMENTS
 ON PLANS AND REVISE AS REQUIRED.
  
 C) SPECIFY CONNECTORS FOR TRUSS GIRDER IN REAR PORCH
 BY THE BREAKFAST AREA. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 D) NEED TO SPECIFY WOOD TO MASONRY CONNECTOR FOR
 TRUSS GIRDER ABOVE MASTER BEDROOM AREA.THD28-2 IS A
 WOOD TO WOOD CONNECTOR. REVISE AS REQUIRED. SEE CATALOG
 FOR PROPER CONNECTOR.
  
 E) ROOF FRAMING PLAN ABOVE ENTRY PORCH IS INCORRECT.
 COLUMNS ARE SHOWN OUTSIDE OF ROOF AREA. REVISE AS
 REQUIRED.
  
 18- SHEET A7:
 A) REVISE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS.NEED TO PROVIDE FULL SUPPORT TO THE FRAMING.
 SEE SEC. R613.6.1.1 OF 2004 FLORIDA RESIDENTIAL CODE
 AND REVISE DETAIL AS REQUIRED.
  
 B) REVISE CONNECTOR SPECIFIED ON TYP. WALL SECTION.
 "HUGHES"IS OUT OF BUSINESS. REVISE AS REQUIRED. ALSO,
 REVISE "SEMCO" CONNECTOR SPECIFIED ON SECTION SHOWN ON
 SAME DRAWING ON THE BOTTOM LEFT HAND SIDE.COORDINATE
 WITH TRUSS ANCHOR SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 07:39 Rev Time 0.00
Received By btrobaug Date 2008-01-22 Time 07:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 08:22 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 07:48 Sent To M
Notes
2007-12-03 09:07:52 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 2} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS. THE SINGLE ALARMLOCATED IN
 THE HALL SERVING 3 BEDROOMS DOES NOT MEET THE INTENT OF
 THIS CODE.
  
 3} 210.52 (H), HALLWAYS IN DWELLING UNITS, HALLWAYS OF
 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET.ADD PER THIS ARTICLE.
  
 4} CIRCUITS 19 AND 21 IN PANEL "B" MUST BE 20 AMP TO
 COMPLY WITH 210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2007-12-03 07:55:35 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 15:50 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 15:50 Sent To E
Notes
2008-08-13 15:50:28TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 09:45 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 09:45 Sent To B
Notes
2008-02-21 09:45:52TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 09:48 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 09:48 Sent To B
Notes
2008-02-12 09:49:11TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 15:32 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 15:32 Sent To E
Notes
2008-02-11 15:32:40TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 13:17 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 13:16 Sent To B
Notes
2008-01-29 13:17:25TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 16:58 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 16:58 Sent To E
Notes
2008-01-15 16:58:31TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-14 Cont ID  
Sent By jgomez Date 2007-12-14 Time 16:57 Rev Time 0.00
Received By jgomez Date 2007-11-27 Time 08:39 Sent To  
Notes
2007-11-27 08:39:25TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 16:22 Rev Time 0.30
Received By tgordon Date 2007-12-03 Time 16:22 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By jleech Date 2008-01-23 Time 09:13 Rev Time 0.00
Received By jleech Date 2008-01-23 Time 09:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By jleech Date 2007-12-06 Time 15:13 Rev Time 0.00
Received By jleech Date 2007-12-06 Time 15:05 Sent To B
Notes
2007-12-06 15:15:08DENIED;
 SANITARY RISER DIAGRAM IS NOT SHOWING BATHROOM # 2. NOT
 TO FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-29 Cont ID  
Sent By choops Date 2007-11-29 Time 08:40 Rev Time 0.00
Received By choops Date 2007-11-29 Time 08:40 Sent To E
Notes
2007-11-29 08:46:42***APPROVED***
  
 PROVISO:1) TOTAL IMPERMEABLE SURFACE WITHIN THE FRONT
 YARD (FRONT PROPERTY LINE TO FRONT OF STRUCTURE) MAY
 NOT EXCEED 962.5 SQ.FT.2) PLANT MATERIAL SHALL MEET
 MINIMUM STANDARDS FOUND IN SECTION 94-442 AND 94-445 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.