Plan Review Details - Permit 07110599
Plan Review Stops For Permit 07110599
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 11:39 Sent To M
Notes
2008-07-09 11:39:36TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-05 Cont ID  
Sent By adarroug Date 2008-02-05 Time 11:41 Rev Time 0.00
Received By adarroug Date 2008-02-05 Time 11:41 Sent To M
Notes
2008-02-05 11:41:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 11:44 Rev Time 0.00
Received By tgordon Date 2007-11-27 Time 09:56 Sent To  
Notes
2007-11-27 09:57:08TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-10 Cont ID  
Sent By tgordon Date 2008-07-10 Time 10:36 Rev Time 0.40
Received By tgordon Date 2008-07-10 Time 10:36 Sent To  
Notes
2008-07-10 10:57:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO KITCHEN HOOD ROOF CURBS**
 *** DENIED ***
  
 1) DRAWING SUBMITTED IS TITLED HOOD DETAILS, THE DETAIL
 SHOWN IS THE ROOF CURB SHOULDN'T IT BE TITLED ROOF CURB
 DETAIL. PER 2004 FBC 106.1.1 CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS.
  
 2) PLEASE PROVIDE THE WIND LOAD CALCULATIONS FOR THE
 CURBS, PER 2004 FBC 1609.
  
 3) THE DETAIL SHOWS A 5 FT. FRESH AIR DUCT, WOULDN'T
 THIS BE AN EXHAUST DUCT ,IF SO PLEASE CORRECT.
  
 4) THE DETAIL SHOWS A 2'X2' 16 GA. ANGLE, PLEASE SHOW
 HOW THIS IS TO BE SECURED TO THE ROOF AND HOW THE DUCT
 IS TO BE SECURED TO THE SUPPORT, PER 2004 FBC 1609.
  
 5) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK 3231
 S. DIXIE HWY., AS THEIR MAY BE MORE THAN ONE KFC ON
 DIXIE HWY., PER WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By tgordon Date 2008-02-06 Time 14:34 Rev Time 0.30
Received By tgordon Date 2008-02-06 Time 14:33 Sent To  
Notes
2008-07-09 14:36:43RECIVED HOOD HANGING DETAIL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 11:42 Rev Time 0.30
Received By tgordon Date 2007-11-30 Time 11:41 Sent To  
Notes
2007-11-30 11:44:00ADDITIONAL MECHANICAL PERMITS REQUIRED FOR FIRE
 SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION.