Plan Review Details - Permit 07110597
Plan Review Stops For Permit 07110597
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-03 Cont ID  
Sent By jwitmer Date 2008-01-03 Time 11:29 Rev Time 2.22
Received By jwitmer Date 2008-01-03 Time 11:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-12 Cont ID  
Sent By jwitmer Date 2007-12-12 Time 16:07 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-02-05 Cont ID  
Sent By dpalmer Date 2008-02-05 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2008-02-05 Time 17:47 Sent To PC
Notes
2008-02-05 17:50:26REVISED SHEETS S-1, E-1 AND E-2
 SHEET S-1 WAS FOR REVISION OF ELEC ONLY, STILL NEED TO
 USE ORIGINAL PLANS FOR ANY STAMPS OR REVIEWED ITEMS
 FROM OTHER TRADES.
  
 REDLINED SHEET E-1 AS THE RISER HAS BEEN REVISED FOR
 NEW CONDUCTORS FROM MAIN TO FPL TRANSFORMER AND NOW
 SHOWS NEW *EQUIPMENT GROUNDING CONDUCTORS* FROM FPL TO
 FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6 AND 250.24 . IF THESE ARE INSTALLED
 THIS WOULD CREATE OBJECTIONABLE CURRENTS WHICH IS NOT
 PERMITTED BUT ALSO A SAFETY ISSUE WITH SERVICE. PLEASE
 REMOVE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 17:57 Sent To PC
Notes
2008-01-30 17:57:26** DENIED REVIEW/REVISION **
  
 1) NOTE: PLEASE SUBMIT A COMPLETE SET OF REVISED PLANS.
 PLEASE SEE THE EXISTING SHEETS S-1, E-1 STILL SHOW
 INFORMATION, LOCATIONS, AND EQUIPMENT WHICH IS NOT THAT
 OF THE EQUIPMENT ON-SITE OR THE EQUIPMENT LISTED ON
 E-2.
 PLEASE SEE THE ATS SPECIFIED ON SHEET E-2 DOES NOT
 CORRELATE WITH THAT OF THE SHEETS E-1 OR S-1 AND DOES
 NOT MATCH WITH THE MANUFACTURES SPECS/CUT SHEETS.
 PLEASE SUBMIT NEW PLANS AND NEW CUT SHEETS FOR ANY AND
 ALL CHANGES IN EQUIPMENT AND SPECS.
 110.3, 90.7 NFPA-70 2005
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE COMPLETE TITLE BLOCK INFORMATION FOR
 ENGINEER OF RECORD. PLEASE SEE AFC 61G15-23.002 FOR ALL
 REQUIRED INFORMATION SUCH AS PRINTED NAME , ADDRESS,
 PHONE , LICENSE ETC
 SOME INFORMATION IS SHOWN BUT NOT ALL.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 19:58 Sent To  
Notes
2007-12-20 20:04:12THE PRINTED NAME AND LICENSE # OF THE ENGINEER WAS
 STILL MISSING ON TITLE BLOCKS PER FAC 61G15-23.002
 THIS WAS WRITTEN ON SHEETS BY REVIEWER.
  
 REDLINED 702.11 AS THE DISCONNECTING MEANS TO MEET
 225.31-225.39AND 702.11 EXCEPTION SHALL BE READILY
 ACCESSIBLE, AND MEET 110.27.
  
 ONLY ONE SET OF ATS SPECS AND GEN SPECS SUBMITTED WHICH
 WERE ATTACHED TO OLD PLANS.MADE COPIES FOR 2ND SET
 AND ATTACHED TO NEW SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By dpalmer Date 2007-12-10 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2007-12-10 Time 09:12 Sent To  
Notes
2007-12-10 12:22:15**** DENIED ****
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS. MAY NOT STATE *LATEST CODE*.
 PLEASE LIST THE FOLLOWING AS ADOPTED BY THE FLORIDA
 STATUTES.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-110
 2003 NFPA-101
 2005 NFPA-70
  
 2) NOTE: PLEASE KNOW BASED ON RECENT INFORMATION FROM
 THE STATE THE LICENSE WHICH MUST BE USED TO APPLY FOR
 INSTALL AND DEAL NATURAL GAS OR LP.
 PLEASE PROVIDE LICENSING FOR INSTALL/SALES OF UNIT.
 PLEASE SEE FS 527.02
  
 3) NOTE: PLEASE SEE PLANS INDICATE THE GENERATOR AS
 EXISTING IN TWO DIFFERENT LOCATIONS. PLEASE CLEARLY
 INDICATE WHERE THE NEW GENERATOR IS BEING INSTALLED.
 PLEASE SEE NFPA-110CHAPTER 7 FOR LOCATION
 INSTALLATIONS.
  
 4) NOTE: PLEASE CLARIFY THE LOADS OF THE GENERATOR.
 PLEASE SEE RISER NOTES THERE WILL BE A MANUAL TRANSFER
 SWITCH HOWEVER PLANS ALSO NOTE THERE WILL BE A AN
 AUTOMATED TRANSFER SWITCH. WHICH ONE IS BEING
 INSTALLED?
 PLEASE KNOW IF THERE ARE ANY LIFE SAFETY OR LEGALLY
 REQUIRED LOADS BEING FED FROM THIS SOURCE AS THE
 PRIMARY BACK UP, THEN ON-SITE FUEL IS REQUIRED PER
 701.11B3 AND 700.12B3.
 PLEASE KNOW IF THERE IS ANY LIFE SAFETY AND LEGALLY
 REQUIRED LOADS SERVED PLEASE SEE 700.6, 701.7 FOR
 TRANSFER EQUIPMENT
  
 5) NOTE: PLEASE SEE THE RISER IS NOW SHOWING A NEW MAIN
 DISCONNECT BEING INSTALLED ON WHAT APPEARS TO BE THE
 LINE SIDE OF THE PREVIOUS MAIN SERVICE SWITCHGEAR.
 PLEASE SEE NEC 110.9 AND SUBMIT AIC RATINGS FOR ANY NEW
 SERVICE EQUIPMENT.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEENOT ALL SHEETS ARE SIGNED, DATED
 AND SEALED BY THE DESIGNER OF RECORD AS REQUIRED PER FS
 471.003, 471.025
  
 7) NOTE: PLEASE COMPLETE INFORMATION ON TITLE BLOCKS
 FOR ALL SHEETS AS REQUIRED PER FAC 61G15-23.002
 PLEASE SEE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER OF THE ENGINEER OF RECORD.
  
 8) NOTE: PLEASE SEE THE SIZING OF CONDUCTORS MAY ONLY
 USE THE 75 DEGREE COLUMN AS 110.14 ONLY CONTAINS A
 RATING FOR LUGS.
 PLEASE KNOW DE-RATING MAY BE USE 90 DEGREE COLUMN.
  
 9) NOTE: PLEASE INCLUDE CONDUCTORS FROM NEW MAIN TO
 FPL.
 230, 310.16, 240.4
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By mwennerg Date 2007-12-28 Time 14:42 Rev Time 0.00
Received By mwennerg Date 2007-12-28 Time 14:42 Sent To  
Notes
2007-12-28 14:42:26NEW SHEET SIGNED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-24 Cont ID  
Sent By mwennerg Date 2007-12-24 Time 09:21 Rev Time 0.00
Received By mwennerg Date 2007-12-24 Time 09:21 Sent To  
Notes
2007-12-24 09:23:001) PLEASE ADD NOTE REGARDING COMPLIANCE WITH NFPA 101,
 2003, AND NFPA 110, 2002 WHEN RESUBMITTING FOR OTHER
 REVIEW CORRECTIONS.
  
 2) REMOVE NOTE REGARDING NO LIFE SAFETY BEING TIED INTO
 GENERATOR IF STATEMENT IS INCORRECT AS PER OUR
 CONVERSATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By mwennerg Date 2007-12-18 Time 13:43 Rev Time 0.00
Received By mwennerg Date 2007-12-18 Time 13:43 Sent To  
Notes
2007-12-18 13:50:45***DENIED***
  
 1) WORK TO COMPLY WITH NFPA 101, 2003 EDITION AND NFPA
 110, 2002 EDITION IN ADDITION TO APPLICABLE BUILDING
 CODES.
  
 2) PLEASE VERIFY ACTUAL LOCATION OF NEW GENERATOR.
 PLANS SHOW THE EXISTING GENERATOR IN THE MAIN
 ELECTRICAL ROOM AND A GENERATOR PAD IS ILLUSTRATED
 OUTSIDE ON THE EAST SIDE OF THE BUILDING.
  
 3) WHAT BUILDING LIFE SAFETY EQUIPMENT WILL BE TIED
 INTO NEW GENERATOR?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By rregueir Date 2007-12-12 Time 08:44 Rev Time 0.00
Received By rregueir Date 2007-12-12 Time 08:44 Sent To  
Notes
2007-12-12 08:45:10NO FUEL REVIEW. NATURAL GAS ONLY.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By kstevens Date 2007-12-28 Time 14:07 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 14:07 Sent To  
Notes
2007-12-28 14:08:12FIELD VERIFY ALL CLEARANCES. MINIMUM 3' REQUIRED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-12-21 Cont ID  
Sent By kstevens Date 2007-12-21 Time 09:43 Rev Time 0.00
Received By kstevens Date 2007-12-21 Time 09:43 Sent To  
Notes
2007-12-21 09:52:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2
 SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED. ALSO ALL THREE SHEETS
 ARE INDICATED AS SHEET E-2 OF 2 IN THE TITLE BLOCK.
 PLEASE CLARIFY.
  
 3. OK
 4. OK
  
 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES
 TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING).
 SECTION 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF
 THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2.
 ****RESPONSE WAS THE SUBMITTAL OF A SINGLE SHEET THAT
 DOES NOT INDICATE WHAT BRAND OR MODEL GENERATOR THE
 SHEET IS FOR. ALSO 3' IS HAND WRITTEN ON THE SHEET, BUT
 NOT FROM THE MANUFACTURE. PLEASE SUBMIT THE COMPLETE
 INSTRALLTAION INSTRUCTIONS FOR THE GENERATOR BEING
 INSTALLED. CLEARANCES FROM ALL STRUCTURES SHALL BE
 INDICATED.
  
 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT
 INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. OK DEDICATED METER
 9. OK
 10. OK
 11. OK
 12. OK
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By kstevens Date 2007-12-11 Time 09:07 Rev Time 0.00
Received By kstevens Date 2007-12-11 Time 09:07 Sent To  
Notes
2007-12-11 09:23:29DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE CODE IN EFFECT AT THE TIME OF DESIGN.
 (FBC-2004 W/2007 AMENDMENTS)
  
 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2
 SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1.
  
 3. SHTS S-1, E-1 & E-2 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR NAME AND LICENSE NUMBER ON EACH SHEET.
 FAC 61G15-23.002(2) & FS 471.025.
  
 4. SHT E-2 SHALL BE SIGNED, SEALED, DATED AS REQUIRED
 BY FLORIDA STATUTES & SECTION 106.1.
  
 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES
 TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING).
 SECTION 106.1.2.
  
 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF
 THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2.
  
 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT
 INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3
 FUEL GAS CODE.
  
 8. PLEASE INDICATE IF THE GAS METER IS A DEDICATED
 METER FOR THE GENERATOR ONLY. IF NOT PLEASE INDICATE
 THE TOTAL BTU LOAD ON THE SYSTEM, AND SHOW THE TOTAL
 DEVELOPED LENGTH FOR ALL OTHER GAS LINES OFF THE METER.
 INDICATE WHERE THE OTHER GAS LINE CONNECTS AT THE
 METER.
  
 9. GAS ISOMETRIC SHEET SHOWS A CLOCK VALVE. PLEASE
 INDICATE WHAT A CLOCK VALVE IS AND SUBMIT MANUF.
 SPECIFICATION FOR THE CLOCK VALVE.
  
 10. GAS ISOMETRIC SHEET A SHUT OFF VALVE AND UNION ARE
 REQUIRED IMMEDIATELY UPSTREAM OF THE REGULATOR. SECTION
 409.4.
  
 11. THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE GAS PIPING SHALL BE ON THE GAS ISOMETRIC
 RISER DIAGRAM. SECTION 106.1.3.
  
 12. SUBMIT THE MANUF SPECIFICATION SHEETS FOR THE GAS
 REGULATOR. INDICATE THE MODEL NUMBER USED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 16:24 Sent To E
Notes
2008-02-01 16:24:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 12:17 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 12:17 Sent To E
Notes
2008-01-23 12:17:42TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 15:32 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 15:32 Sent To  
Notes
2007-12-27 15:32:30TO "BOB" # 6

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 11:35 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 11:35 Sent To G
Notes
2007-12-27 11:35:59TO KEN STEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:51 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:51 Sent To  
Notes
2007-12-20 17:51:26SENT TO COM BOARD # 01 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 19:26 Rev Time 0.00
Received By mawillia Date 2007-11-27 Time 14:54 Sent To  
Notes
2007-12-07 11:17:2912/7/07 TO "COMM" BD#58--EXPEDITED--
2007-11-27 14:54:37TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By rregueir Date 2007-12-12 Time 08:43 Rev Time 0.00
Received By rregueir Date 2007-12-12 Time 08:43 Sent To  
Notes
2007-12-12 08:43:25NO MECHANICAL REVIEW. NATURAL GAS ONLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-12-07 Cont ID  
Sent By astelly Date 2007-12-07 Time 07:59 Rev Time 0.00
Received By astelly Date 2007-12-07 Time 07:59 Sent To  
Notes
***NONE***