Plan Review Details - Permit 07110587
Plan Review Stops For Permit 07110587
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-12-12 Cont ID  
Sent By shill Date 2007-12-12 Time 11:43 Rev Time 0.00
Received By lursu Date 2007-12-12 Time 11:43 Sent To  
Notes
2007-12-12 11:43:18PERMIT ASSIGNED TO THE NEW UNIT ADDRESS 115 FOR THE NEW
 RESTAURANT .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 14:39 Rev Time 0.00
Received By shill Date 2008-05-05 Time 14:39 Sent To  
Notes
2008-05-05 14:40:04REVISED SHEET A1 DATED 4/30/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-25 Cont ID  
Sent By shill Date 2008-04-25 Time 10:04 Rev Time 0.00
Received By shill Date 2008-04-25 Time 10:04 Sent To M
Notes
2008-04-25 10:14:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.IT APPEARS THAT THE RAMP SHOWN ON A1 (ADJACENT TO
 MECH 108) HAS BEEN REPLACED BY STAIRS.PROVIDE RISE
 AND RUN, FBC1009.3.IF THIS IS NOT A STAIR, PROVIDE
 INFORMATION AS TO WHAT IS GRAPHICALLY SHOWN ON THE PLAN
 AND HOW THE ELEVATION CHANGE WAS ADDRESSED.
  
 2.HANDRAILS REQUIRED ON BOTH SIDES, FBC1009.11,
 FBC11-4.9.4.SHOW ON THE FLOOR PLAN AND PROVIDE A
 DETAIL, INCLUDING EXTENSIONS.
  
 3.MEANS OF EGRESS IN COMPLIANCE WITH FBC CHAPTER 10
 IS TO BE PROVIDED TO ALL PORTIONS OF BUILDINGS,
 FBC1001.1.A PARTIAL WALL WAS CONSTRUCTED; SHOW
 DISTANCE BETWEEN WALLS (SPACE AVAILABLE FOR EGRESS
 PATH).
  
 4,THE CHAGES ON A1 AFFECT OTHER SHEETS.PLEASE
 REVISE.
  
 5.THIS IS A FULLY SPRINKLERED BUILDING.PLEASE
 ADDRESS ON THE PLAN HOW THE NEW WALLS AFFECT THE
 EXISTING SPRINKLERS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-12 Cont ID  
Sent By shill Date 2008-02-12 Time 14:17 Rev Time 0.00
Received By shill Date 2008-02-12 Time 14:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By shill Date 2007-12-07 Time 10:50 Rev Time 0.00
Received By shill Date 2007-12-07 Time 10:50 Sent To  
Notes
2007-12-07 10:50:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.REGARDING THE DOUBLE DOORS ADJACENT TO THE
 BATHROOMS, SEE FBC11-4.13.4.PLEASE SHOW COMPLIANCE
 AND DIMENSIONS ON THE PLAN.
  
 2.THIS IS A FULLY SPRINKLERED BUILDNG.HOW DOES THE
 NEW WALL IN THE STORAGE AREA AFFECT THE FIRE SPRINKLER
 LAYOUT?IF REQUIRED, SUBMIT A PLAN.
  
 3.MECHANICAL PLANS SHOW A TENANT SEPARATION WALL
 WHICH DOES NOT YET EXIST.SEE PERMIT NUMBER 07080934.
 THIS IS STILL UNDER APPLICATION.PLEASE ADDRESS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By dpalmer Date 2008-02-01 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2008-02-01 Time 16:15 Sent To  
Notes
2008-02-01 16:37:43PLANS STAMPED ON PREVIOUS REVIEW. SUITE/UNIT NUMBER WAS
 ADDED TO TITLE BLOCKS.
  
 *** ALL EXISTING ELECTRICAL SHWON ON PLANS WITH
 EXCEPTION OF ONE NEW CIRCUIT FOR NEW LIGHTS. NO REVIEW
 DONE ON EXISTING ELECTRICA.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By dpalmer Date 2007-12-05 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2007-12-05 Time 16:28 Sent To  
Notes
2007-12-06 15:54:07ELECTRICAL PLANS ARE OK, HOWEVER ADDRESS IS AN ISSUE
 AND WILL BECOME FAILED BY THE ADDRESSING REVIEWER. ONCE
 THE CORRECT ADDRESS FOR SUITE/UNIT NUMBER HAS BEEN
 DETERMINED AND SIGNED OFF BY ADDRESSING THE SUITE/UNIT
 # MAY BE ADDED TO TITLE BLOCKS. THERE IS NO NEED TO
 REPRINT ELECTRICAL SHEETS FOR THIS.
2007-12-05 16:29:37NO REVIEW DONE ON ANY ELECTRICAL WHICH IS SHOWN AS ALL
 EXISITNG BY THE ENGINEER OF RECORD.
 ONLY ADDING ONE NEW CIRCUIT FOR 10LTS AND RELOCATING
 AHU DISCONNECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 10:57 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 10:26 Sent To  
Notes
2008-02-21 10:56:58*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS A2, A3, ANDE2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By mawillia Date 2007-12-24 Time 15:48 Rev Time 0.00
Received By mawillia Date 2007-12-24 Time 14:55 Sent To  
Notes
2007-12-24 15:48:49*****DENIED*****
  
 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 THE VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE
 LANES).
  
 06.PROVIDE THE OCCUPANT LOAD , AS IN THE NUMBERS OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED.
  
 07.PLEASE SHOW TRAVEL DISTANCE TO EXITS ON THE LIFE
 SAFETY PLAN SHEET.
  
 08.ANY DOOR IN A REQUIRED MENS OF EGRESSFROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 09.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERRMS OF CLASS A, CLASS B, OR CLASS C.
  
 10.PLANS DON' T INDICATE IF THE PROJECT SITE IS FIRE
 SPRINKLERED.IF SO SPRINKLERED AND THERE IS A CAUSE
 FOR THIS SYSTEM TO BE ALTERED DUE TO THE SCOPE OF WORK,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-04-08 Cont ID  
Sent By mperson Date 2008-04-08 Time 13:10 Rev Time 0.00
Received By mperson Date 2008-04-08 Time 13:10 Sent To PC
Notes
2008-04-08 13:11:45REVISION: "OK" SHEET P1 GAS RISER.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-04-04 Cont ID  
Sent By mperson Date 2008-04-04 Time 11:17 Rev Time 0.00
Received By mperson Date 2008-04-04 Time 11:17 Sent To PC
Notes
2008-04-04 13:14:33GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1 GAS RISER: THE CUT SECTIONS OF PIPE FROM
 THE METER TO THE SEDIMENT TRAP DO NOT HAVE
 CORRESPONDING LENGTHS INDICATED. THE DISTANCE FROM THE
 POINT OF DELIVERY TO THE MOST DISTANT OUTLET IN
 INCORRECTLY BEING INDICATED AS 100 FEET. THE CALCULATED
 DISTANCE OF THE INDICATED CUT SECTIONS CORRESPONDING
 LENGTHS IS NOW 105 FEET AND THATS WITHOUT THE CUT
 SECTIONS FROM THE METER TO THE SEDIMENT TRAP. PLEASE
 CORRECT PLANS WITH ALL CORRESPONDING LENGTHS TO ALL CUT
 SECTIONS OF PIPE AND THE CORRECT LONGEST LENGTH OF THE
 SYSYEM. PER FBC FUEL GAS 401.1 SCOPE.
  
 2. SHEET P1 GAS RISER: THE GAS BRANCH SUPPLY TO THE
 FOLLOWING APPLIANCES ARE INCORRECTLY SIZED. PLEASE
 CORRECT PER FBC FUEL GAS TABLE 402.4 (2). PLEASE
 REFERENCE FBC FUEL GAS TABLE 402.4(2) ATTACHED TO THESE
 COMMENTS FOR THE NEXT REVISION SUBMITTAL.
  
 A} ITEM #18, SHOULD BE 1 INCH.
  
 B} ITEM #19, SHOULD BE 1-1/4 INCH.
  
 C} ITEM #27, SHOULD BE 1 INCH.
  
 D} ITEM #32, SHOULD BE 1 INCH.
  
 E} ITEM #29, SHOULD BE 1-1/4 INCH.
  
 F} ITEM #30, SHOULD BE 1-1/4 INCH.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-02-29 Cont ID  
Sent By kstevens Date 2008-02-29 Time 14:29 Rev Time 0.00
Received By kstevens Date 2008-02-29 Time 14:29 Sent To  
Notes
2008-02-29 14:29:45SEPARATE GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 18:16 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 18:15 Sent To  
Notes
2008-02-22 18:16:44DENIED--FROM PREVIOUS REVIEW:SEE COMMENTS FROM
 PLUMBING PLAN REVIEW.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2007-12-14 Time 18:15 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 18:14 Sent To  
Notes
2008-02-22 18:15:52DENIED.--SEE COMMENTS IN THE PLUMBING PLAN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 08:45 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 08:45 Sent To B
Notes
2008-05-02 08:45:49TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 08:43 Sent To B
Notes
2008-04-09 08:43:48TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 09:35 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 09:35 Sent To G
Notes
2008-04-08 09:36:38TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 13:18 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 13:18 Sent To G
Notes
2008-04-03 13:18:59TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 10:37 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 10:37 Sent To P
Notes
2008-02-28 10:37:31TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:20 Sent To  
Notes
2008-01-29 11:24:04TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-24 Cont ID  
Sent By mawillia Date 2007-12-24 Time 14:55 Rev Time 0.00
Received By mawillia Date 2007-11-27 Time 11:16 Sent To  
Notes
2007-11-30 16:22:59TO "COMM" BD#18
2007-11-27 11:16:15WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2008-04-26 Time 09:31 Sent To  
Notes
2008-04-26 09:33:01MECH DESIGN NOT AFFECTED BY ARCHITECTURAL REVISION #2
 ON PAGE A1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 11:14 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By rregueir Date 2007-12-07 Time 14:16 Rev Time 0.00
Received By rregueir Date 2007-12-07 Time 09:02 Sent To  
Notes
2007-12-07 14:16:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1: ON THE ?RELOCATED? SIDE OF THE PLAN, AHU 2 IS
 SHOWN AT BOTH THE EXISTING LOCATION AND THE NEW
 LOCATION. PLEASE SHOW THE AHU ONLY IN THE NEW LOCATION
 FOR CLARIFICATION OF THE SCOPE OF WORK. FBC 106.1.1
  
 2. PG M1: MECHANICAL NOTE #13 CALLS FOR CONDENSATE
 DISPOSAL IN THE ROOF DRAIN. HOW IS CONDENSATE FOR AN
 AHU ON THE 1ST FLOOR TO DRAIN ON THE ROOF? PLEASE SHOW
 MEANS OF CONDENSATE DISPOSAL IN ACCORDANCE WITH FBC, M
 307.2.1. ALSO, SHOW MEANS OF AUXILIARY DRAIN PROTECTION
 PER FBC, M 307.2.3.
  
 3. RELOCATION OF AHU 2 WILL ALSO REQUIRE THE RELOCATION
 OR NEW INSTALLATION OF A DUCT SMOKE DETECTOR IN
 ACCORDANCE WITH FBC, M 606.2.1. THIS DETECTOR SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC, M 606.4.1. SHOW COMPLIANCE WITH
 THESE SECTIONS.
  
 4. PG M1: MANY OF THE NOTES WHICH INDICATE THE SCOPE OF
 WORK RELATED TO RELOCATION OF AHU 2 ARE CURRENTLY PART
 OF THE SCOPE OF WORK WITHIN A SEPARATE PERMIT
 APPLICATION WITH DIFFERENT CONTRACTORS AND DIFFERENT
 DESIGNERS. PERMIT #07080934 IS FOR THE PURPOSE OF
 ADDING A FIRE RATED TENANT SEPARATION WALL TO SPLIT THE
 RETAIL SPACE FROM THE RESTAURANT. PLEASE VERIFY THAT
 THE SCOPE OF WORK RELATED TO ONE PERMIT IS NOT IN
 CONFLICT OR BEING DUPLICATED ON THE OTHER. FBC 106.1.1
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-29 Cont ID  
Sent By kstevens Date 2008-02-29 Time 14:27 Rev Time 0.00
Received By kstevens Date 2008-02-29 Time 14:27 Sent To  
Notes
2008-02-29 14:28:26SEPARATE GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 17:44 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 17:44 Sent To  
Notes
2008-02-22 18:13:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 A. ALL SHEETS. THE TITLE BLOCK OF THE ARCHITECT FIRM
 SHALL INCLUDE THE FIRM LICENSE NUMBER. FAC
 61G1-16.004(2) & FS 481.219, 481.2055.
 ****NO RESPONSE, BUT NOT SHOWN IN THE TITLE BLOCKS FOR
 THE M-E-P SHEETS.
  
 B. ROUTE THE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTAURANT DIVISION FOR REVIEW. EACH SET OF
 PLANS SHALL HAVE A STAMPED/REVIEWED SHEET SUBMITTED
 WITH THE TWO PAGE "SPECIFICATION WORKSHEETS" ATTACHED
 TO THE SHEET STAMPED BY DBPR PRIOR TO RESUBMITTING.
 SECTION 102.2.1.
 ****NO RESPONSE, THE SPECIFICATION WORKSHEETS HAVE NOT
 BEEN ATTACHED TO THE SHEET STAMPED BY DBPR.
  
 C. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. FOR ALL EXISTING PIPE.
 ****RESPONSE NOTED, BUT THE LENGTH OF PIPE FROM THE
 MAIN GAS LINE TO THE DROP IS NOT INDICATED ON THE
 RISER. ALL PIPING DOWNSTREAM OF RANGE/OVEN (30) SHALL
 BE DELETED, OR THE DEVELOPED LENGTH WILL BE INDICATED
 TO THE MOST REMOTE APPLIANCE AND THE PIPE SIZE AND ALL
 LENGTHS OF SECTIONS AS WELL AS MAXIMUM BTU LOAD WILL BE
 INDICATED FOR THE TWO PLUGED APPLIANCES. MANY PIPE
 SIZES ARE INCORRECT FOR THE DROPS AND 2-1/2" IS
 REQUIRED UP TO THE DROP PICKING UP THE FRYERS (27).
 (THIS HAS BEEN SIZED USING A MAXIMUM 100 FEET TOTAL
 DEVELOPED LENGTH. IF THE TOTAL DEVELOPED LENGTH IS
 INDICATED AS MORE THEN THE PIPING WILL BE SIZED BY THE
 NEXT LINE UP IN THE TABLE WHICH IS 125 FEET.) TABLE
 402.4(2).--MORE INFORMATION IS REQUIRED. IS ALL THE
 GAS PIPING TO BE RUN BELOW THE CEILING? OR IS THERE NO
 CEILING IN THE PREP KITCHEN? PLEASE CLARIFY. SECTION
 106.1.2.
  
 2. OK
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, INFORMATION TO BE VERIFIED ONCE
 COMMENT 1. INFORMATION RECIEVED
  
 4. OK
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS WERE
 SUBMITTED.
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT PLEASE VERIFY IF THERE IS A
 CEILING IN THE PREP KITCHEN.
  
 **********NEW COMMENT**********
  
 1B. SHT P1 NOTE STATES "SYSTEM SIZED BY FBC 2004 FUEL
 GAS CODE TABLE A.3.1(4)",WHICH IS IN CONFLICT WITH
 THE NOTE THAT STATES "GAS PIPING SIZED AS PER FBC-2004
 FUEL GAS TABLE 402.4(2)". PLEASE DELETE NOTE
 REFERENCING TABLE A.3.1.4(4) AS THERE IS NO TABLE
 A.3.1.4(4) IN THE FBC-2004 FUEL GAS CODE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 18:40 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 18:40 Sent To  
Notes
2007-12-14 18:50:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. ALL SHEETS. THE TITLE BLOCK OF THE ARCHITECT FIRM
 SHALL INCLUDE THE FIRM LICENSE NUMBER. FAC
 61G1-16.004(2) & FS 481.219, 481.2055.
  
 B. ROUTE THE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTAURANT DIVISION FOR REVIEW. EACH SET OF
 PLANS SHALL HAVE A STAMPED/REVIEWED SHEET SUBMITTED
 WITH THE TWO PAGE "SPECIFICATION WORKSHEETS" ATTACHED
 TO THE SHEET STAMPED BY DBPR PRIOR TO RESUBMITTING.
 SECTION 102.2.1.
  
 C. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. FOR ALL EXISTING PIPE.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By mflis Date 2008-02-07 Time 13:27 Rev Time 0.00
Received By mflis Date 2008-02-07 Time 13:27 Sent To  
Notes
2008-02-07 13:28:48ZONING REVIEW: PASSED
  
 MATT FLIS - 8221445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By mflis Date 2007-12-14 Time 13:38 Rev Time 0.00
Received By mflis Date 2007-12-14 Time 13:38 Sent To  
Notes
2007-12-14 13:39:43ZONING REVIEW: FAILED
  
 * PLANS INDICATE NEW RAILING AT STREET SIDE / EXTERIOR
 TO BUILDING; PLEASE PROVIDE NOTE AND/OR DETAIL
 INDICATING MATERIAL, HEIGHT, AND DESIGN OF RAILING. IS
 THIS TO MATCH EXISTING? WILL THIS MEET FBC GUARDRAIL
 REQ'S?
  
 MATT FLIS - 822-1445