Plan Review Details - Permit 07110579
Plan Review Stops For Permit 07110579
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 10:55 Rev Time 0.00
Received By shill Date 2008-01-17 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 14:34 Rev Time 0.00
Received By shill Date 2007-12-13 Time 14:34 Sent To  
Notes
2007-12-13 14:35:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE POOL SAFETY NOTES DO NOT COMPLY WITH FBC
 R4101.17.OPTIONS 3 AND 4 ARE TO BE USED IN
 COMBINATION WITH A FENCE.
  
 2.PROVIDE A REASONABLE VALUE FOR THIS JOB OR AN
 ESTIMATE WILL BE DONE FOR YOU USING MARSHALL & SWIFT.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2008-01-09 Cont ID  
Sent By btrobaug Date 2008-01-09 Time 12:09 Rev Time 0.00
Received By btrobaug Date 2008-01-09 Time 12:08 Sent To P
Notes
2008-01-09 12:09:17 
  
 ELECTRICAL PERMIT #07120577 WAS ISSUED FOR THIS
 POOL./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By btrobaug Date 2007-12-06 Time 07:41 Rev Time 0.00
Received By btrobaug Date 2007-12-06 Time 07:22 Sent To P
Notes
2007-12-06 07:40:05 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE HEAT
 PUMPTHAT IS TO BE INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-01-11 Cont ID  
Sent By mperson Date 2008-01-11 Time 11:38 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 11:09 Sent To B
Notes
2008-01-11 11:10:46NOTE: POOL HEATER IS ELECTRIC.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 14:53 Rev Time  
Received By mperson Date   Time   Sent To B
Notes
2007-12-06 14:54:42NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 14:54 Sent To E
Notes
2008-01-04 14:54:25TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 14:35 Rev Time 0.00
Received By shill Date 2007-11-27 Time 08:36 Sent To  
Notes
2007-11-27 08:37:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-11 Cont ID  
Sent By mperson Date 2008-01-11 Time 11:00 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 11:00 Sent To G
Notes
2008-01-11 11:09:22****************PROVISO****************
 NOTE: TWO COPIES OF THE POOL HEATER MANUFACTURER'S
 SPECIFICATION SHEETS INDICATING THE MAKE, MODEL NUMBER
 AND LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY REQUIRED BEFORE FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 14:16 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 14:16 Sent To G
Notes
2007-12-06 14:53:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
  
 2) FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
  
 3) FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
  
 4) FBC-2004 SEC. 424.2.7.1, OR FBCR-2004 SEC.R4101.7.1
 POOL CIRCULATING PUMPS
 SHALL BE EQUIPPED ON THE INLET SIDE WITH
 AN APPROVED TYPE HAIR AND LINT STRAINER
 WHEN USED WITH A PRESSURE FIL- TER.
 (DETAIL OR ADD TO NOTES)
  
 5) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 6) FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)
  
 7) FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING.(ADD TO
 NOTES)
  
 8) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 9) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 10) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 11) FBC-2004 SEC. 13-612.1.ABC.2.3.3
 TIME CLOCKS SHALL BE INSTALLED ON
 PRIVATE POOLS.
  
 12) SHEET 2 AND 3 ARE INDICATING TWO DIFFERENT VENT
 PIPE SIZES TO MEET THE 3 SECOND RELEASE PER
 *424.2.6.6.3. PLEASE CORRELATE THE VENT PIPE SIZES ON
 THE RESUBMITTAL. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 16:23 Rev Time 0.00
Received By choops Date 2007-11-28 Time 16:23 Sent To E
Notes
2007-11-28 16:23:54***APPROVED***
  
 PROVISO:FENCE MUST MEET MINIMUM ENCLOSURE
 REQUIREMENTS: PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION,
 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.