| 2007-12-06 11:54:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | NOTE: A SEPERATE RESIDENTIAL GENERATOR PERMIT IS |
| | REQUIRED FOR THE INDICATED GENERATOR, AS OF DATE ONE |
| | HAS NOT BEEN APPLIED FOR. PLEASE SEE ATTACHED SEARCH |
| | CRITERIA FOR SAID ADDRESS INDICATING THIS. PLEASE |
| | REFERENCE THE "CITY OF WEST PALM BEACH RESIDENTIAL |
| | GENERATOR PLAN REVIEW" REQUIREMENTS ATTACHED TO THESE |
| | COMMENTS FOR GEN/RES PERMIT. |
| | |
| | 1. PLEASE SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY |
| | CLEARLY INDICATING THE LOCATION OF THE PROPOSED |
| | GENERATOR. INDICATION OF ALL DIMENTIONS FROM PROPERTY |
| | LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| | GENERATOR MANUFACTURER'S SPECIFICATIONS/CUT SHEETS FOR |
| | THE GENERATOR INDICATING THE BTU LOAD, MANUFACTURER |
| | SETBACK RECOMMENDATIONS FROM STRUCTURES, AND A LISTING |
| | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | (NRTL). |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE |
| | CORRESPONDING LENGTHS INDICATED. PLEASE COMPLY ON THE |
| | RESUBMITTAL. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |