Plan Review Details - Permit 07110574
Plan Review Stops For Permit 07110574
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By mperson Date 2008-04-04 Time 08:19 Rev Time 0.00
Received By mperson Date 2008-04-04 Time 08:19 Sent To  
Notes
2008-04-04 08:20:54NOTE: GAS WAS RESUBMITTED WITH GEN/RES PERMIT
 #08030561.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 11:05 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 11:05 Sent To PC
Notes
2007-12-06 11:54:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
 NOTE: A SEPERATE RESIDENTIAL GENERATOR PERMIT IS
 REQUIRED FOR THE INDICATED GENERATOR, AS OF DATE ONE
 HAS NOT BEEN APPLIED FOR. PLEASE SEE ATTACHED SEARCH
 CRITERIA FOR SAID ADDRESS INDICATING THIS. PLEASE
 REFERENCE THE "CITY OF WEST PALM BEACH RESIDENTIAL
 GENERATOR PLAN REVIEW" REQUIREMENTS ATTACHED TO THESE
 COMMENTS FOR GEN/RES PERMIT.
  
 1. PLEASE SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY
 CLEARLY INDICATING THE LOCATION OF THE PROPOSED
 GENERATOR. INDICATION OF ALL DIMENTIONS FROM PROPERTY
 LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
 GENERATOR MANUFACTURER'S SPECIFICATIONS/CUT SHEETS FOR
 THE GENERATOR INDICATING THE BTU LOAD, MANUFACTURER
 SETBACK RECOMMENDATIONS FROM STRUCTURES, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL).
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE
 CORRESPONDING LENGTHS INDICATED. PLEASE COMPLY ON THE
 RESUBMITTAL.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 11:54 Rev Time 0.00
Received By mperson Date 2007-11-27 Time 08:35 Sent To  
Notes
2007-11-27 08:35:31TO "G" BOX