Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-15 Cont ID  
Sent By mjacobs Date 2008-01-15 Time 11:40 Rev Time 0.00
Received By mjacobs Date 2008-01-15 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-01 Cont ID  
Sent By mjacobs Date 2007-12-01 Time 15:54 Rev Time 0.00
Received By mjacobs Date 2007-12-01 Time 14:54 Sent To  
Notes
2007-12-01 15:54:50 
 BUILDING PLAN REVIEW
 PERMIT: 07110531
 ADD: 8989 OKEECHOBEE BLVD
 CONT: COHEN INC.
 TEL: (561)362-4271
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 12/1/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)2004 FBC EXISTING301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 3)FBC 11-7.2(2)(I)A PORTION OF THE MAIN COUNTER
 SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM
 OF 36 INCHES HIGH.
  
 4)THE BREAK ROOM SINK SHALL MEET THE REQUIREMENTS OF
 FBC 11-4.24. SHOW THE KNEE CLEARANCE WILL BE ACHIEVED.
 THE CABINET DOORS IN FRONT OF THE SINK CANNOT HINDER
 THE REQUIREMENTS OF THIS SECTION. SUBMIT AN ELEVATION
 DETAIL DRAWING MEETING ALL DIMENSIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 14:32 Rev Time 0.00
Received By btrobaug Date 2008-01-22 Time 13:43 Sent To PC
Notes
2008-01-22 14:15:19 
  
  
  
 PROVISO
  
 THIS SHEET MUST BE REVISED TO SHOE THE AUTOMATIC SPACE
 CONTROLS REQUIRED BY 13-415.1.ABC.1.2 FBC, PRIOR TO
 FIRST ELECTRICAL INSPECTION. THE REVISED SHEET STAMPED
 BY THIS OFFICE MUST BE ON SITE. ALLOW AT LEAST A WEEK
 FOR THE REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 09:21 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 07:32 Sent To  
Notes
2007-11-29 09:21:24 
  
  
 APPLICATION #07110531
 ELECTRICAL PLAN REVIEW
 8989 OKEECHOBEE BLVD
 11/29/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 13-400.0.C.4 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED. SUBMIT DENSITY CALCULATIONS.
 THE FIXTURE SCHEDULE MUST REFLECT THE TYPE AND COUNT
 USED FOR COMPLIANCE.
  
 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 INDICATE COMPLIANCE ON THE PLAN. SEE SUBCHAPTER FOR
 MORE INFORMATION REGARDING REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-16 Cont ID  
Sent By mwennerg Date 2008-01-16 Time 14:22 Rev Time 0.00
Received By mwennerg Date 2008-01-16 Time 14:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 12:39 Rev Time 0.00
Received By mwennerg Date 2007-12-12 Time 12:39 Sent To  
Notes
2007-12-12 12:44:53***DENIED***
  
 1) MERCANTILE OCCUPANCY IS REFERENCED FOR INTERIOR WALL
 AND CEILING FINISHES, AND THE OCCUPANT LOAD IS BASED ON
 BUSINESS. PLEASE CORRELATE ALL INFORMATION USING THE
 CORRECT OCCUPANCY CLASSIFICATION FOR THIS SPACE.
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) THE BREAKROOM EXIT DOOR SHALL NOT BE OBSTRUCTED BY
 TYPICAL BREAKROOM FURNITURE.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 09:21 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 09:21 Sent To  
Notes
2008-01-10 09:21:59TO "BOB" # 17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 12:46 Rev Time 0.00
Received By mwennerg Date 2007-11-26 Time 15:18 Sent To  
Notes
2007-11-28 11:49:53TO "BOB"#7
2007-11-26 15:18:34WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 10:52 Rev Time 0.30
Received By tgordon Date 2007-12-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-14 Cont ID  
Sent By jleech Date 2008-01-14 Time 08:09 Rev Time 0.00
Received By jleech Date 2008-01-14 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By jleech Date 2007-12-11 Time 08:24 Rev Time 0.00
Received By jleech Date 2007-12-11 Time 07:37 Sent To  
Notes
2007-12-11 08:45:25DENIED;
 1. PAGE A-6.0 BREAK SINK DETAIL. NO CABINET DOORS
 PERMITED. SEE FBC BUILDING CHAPTER 11 SECTION 11-4.24.3
 KNEE CLEARANCE UNDER SINK.SHOW ON DETAIL ALL
 MEASUREMENTS REQUIRE TO COMPLY WITH SECTIONS 11-4.24.1
 THRU 11-4.24.7.
 2. DRINKING FOUNTAIN ON FLOOR PLAN PAGE A-1.1.
 3. WATER HEATER ON WATER RISER DIAGRAM SHOW THE
 TERMINATION POINTS FOR RELIEF LINE AND PAN DRAIN. SEE
 FBC-PLUMBING SECTIONS 504.6 AND 504.7.2.
 4. SHOW THERMAL EXPANTION CONTROL TO BE USED , SEE
 SECTION 607.3. SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 15:10 Rev Time 0.00
Received By choops Date 2007-11-28 Time 15:10 Sent To  
Notes
2007-11-28 15:10:27*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.