Plan Review Details - Permit 07110497
Plan Review Stops For Permit 07110497
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-27 Cont ID  
Sent By btrobaug Date 2007-12-27 Time 12:31 Rev Time 0.00
Received By btrobaug Date 2007-12-27 Time 12:21 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 16:17 Rev Time 0.00
Received By btrobaug Date 2007-11-26 Time 15:19 Sent To FIRE
Notes
2007-11-26 16:03:33 
  
 APPLICATION # 07110497
 ELECTRICAL PLAN REVIEW
 3501 ELECTRONICS WAY
 11/26/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PER 700.12(F)(4)??THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.? INDICATE SAME ON PLANS.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2, ALL
 SHEETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-27 Cont ID  
Sent By mawillia Date 2007-12-27 Time 15:09 Rev Time 0.00
Received By mawillia Date 2007-12-27 Time 14:54 Sent To  
Notes
2007-12-27 15:07:41*****APPROVED*****
  
  
 PLAN SHEETS LS-1 AND LS-2 WERE STAMPED, INITIALED, AND
 DATED;READY FOR PERMIT ISSUANCE.
  
  
  
  
  
  
 CAPT.MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-27 Cont ID  
Sent By mawillia Date 2007-11-27 Time 10:41 Rev Time 0.00
Received By mawillia Date 2007-11-27 Time 10:09 Sent To  
Notes
2007-11-27 10:30:07*****UNSAT*****
  
  
 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THE UPDATED
 PLAN SHEET(S) ARE TO BE SUBMITTED WITH NO INK, PENCIL,
 HAND-DRAWN OR WHITE-OUTED MARKINGS.
  
 2.CITY AMENDMENT 104.2.1.ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 3.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 4.SINCE THE SCOPE OF THE WORK IS GREATER THAN
 $5,000.00, AS PER FLORIDA ADMINISTRATIVE CODES, A
 PROFESSIONAL ENGINEER SHALL SIGN HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, ETC TO BE FILED FOR PUBLIC RECORD. THE
 STAMPED ENGINEERED SEAL SHALL HAVE THE WORDING
 "LICENSE" IN LIEU OF "CERTIFICATE".
  
  
  
  
 CAPT.MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 17:11 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 17:11 Sent To E
Notes
2007-12-19 17:11:58TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-27 Cont ID  
Sent By mawillia Date 2007-11-27 Time 10:42 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 16:19 Sent To  
Notes
2007-11-19 16:19:23TO "E" BOX