Plan Review Details - Permit 07110489
Plan Review Stops For Permit 07110489
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By dwise Date 2009-04-16 Time 18:34 Rev Time 0.00
Received By dwise Date 2009-04-16 Time 18:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-11 Cont ID  
Sent By shill Date 2008-12-11 Time 10:57 Rev Time 0.00
Received By shill Date 2008-12-11 Time 10:57 Sent To  
Notes
2008-12-11 11:07:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT APPEARS THAT THERE HAS BEEN A CHANGE OF ENGINEER
 OF RECORD. PLEASE SEE FAC61G15-27 REGARDING SUCCESSOR
 ENGINEER. THE NEW ENGINEER HAS USED THE PREVIOUS
 ENGINEER'S DRAWING; HAS THE NEW ENGINEER FOLLOWED THE
 PROVISIONS OF THIS SECTION?
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-10 Cont ID  
Sent By shill Date 2007-12-10 Time 07:26 Rev Time 0.00
Received By shill Date 2007-12-10 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By dwise Date 2009-04-16 Time 18:36 Rev Time 0.00
Received By dwise Date 2009-04-16 Time 18:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By btrobaug Date 2008-11-24 Time 15:20 Rev Time 0.00
Received By btrobaug Date 2008-11-24 Time 15:03 Sent To P
Notes
2008-11-24 15:20:48 
  
 REVISION DENIED
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO
 THE DESIGNER TO BE REDRAWN. 471-481 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-28 Cont ID  
Sent By btrobaug Date 2007-11-28 Time 14:01 Rev Time 0.00
Received By btrobaug Date 2007-11-28 Time 13:54 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 10:28 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 10:28 Sent To  
Notes
2007-12-06 10:29:54CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-11-19 Cont ID  
Sent By ssherman Date 2007-11-19 Time 14:42 Rev Time 0.00
Received By ssherman Date 2007-11-19 Time 14:42 Sent To  
Notes
2007-11-19 14:43:06HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 11:01 Sent To Z
Notes
2008-11-14 11:01:29TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 11:11 Sent To Z
Notes
2007-12-13 11:11:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 09:43 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 16:27 Sent To  
Notes
2007-11-19 16:27:53TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-04-16 Cont ID  
Sent By dwise Date 2009-04-16 Time 18:35 Rev Time 0.00
Received By dwise Date 2009-04-16 Time 18:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-12-11 Cont ID  
Sent By kstevens Date 2008-12-11 Time 09:41 Rev Time 0.00
Received By kstevens Date 2008-12-10 Time 16:58 Sent To B
Notes
2008-12-11 09:49:02REVISION DENIED
 REFERENCE:
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE REVISION TO A SIGNED AND SEALED PLAN SHALL BE
 SIGNED & SEALED BY THE ENGINEER OF RECORD OR IF SIGNED
 & SEALED BY ANOTHER ENGINEER THEN SAID ENGINEER SHALL
 FOLLOW THE PROCESS INDICATED IN CHAPTER 61G15-27
 PROCEDURES FOR THE ADOPTION OF ANOTHER'S WORK. UPON
 CONTACTING THE ORIGINAL ENGINEER OF RECORD, THE
 ENGINEER INDICATED THAT HE HAD NO NOTIFICATION OF HIS
 WORK BEING ADOPTED BY ANOTHER ENGINEER. THE NEW
 ENGINEER SHALL SUBMIT A LETTER TO THE ORIGINAL ENGINEER
 OF RECORD INDICATING THAT HE HAS TAKEN OVER THE PLANS
 OF THE ORIGINAL ENGINEER AS REQUIRED IN 61G15-27. A
 COPY OF THE LETTER SHALL BE SUBMITTTED WITH THE
 REVISIONS AND WILL BE VERIFIED AT THAT TIME. FS
 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 10:28 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 10:27 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-24 Cont ID  
Sent By mcruz Date 2008-11-24 Time 10:54 Rev Time 0.00
Received By mcruz Date 2008-11-24 Time 10:54 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 09:37 Rev Time 0.00
Received By choops Date 2007-12-18 Time 09:37 Sent To PC
Notes
2007-12-18 09:37:50***APPROVED - RESUB #1***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 12:04 Rev Time 0.00
Received By choops Date 2007-11-28 Time 12:04 Sent To E
Notes
2007-11-28 12:07:30***FAILED***
  
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 2)SOME DIMENSIONS ON SURVEY ARE NOT LEGIBLE (THEY
 ARE TOO LIGHT).PLEASE CLARIFY, MAKE ALL INDICATIONS
 LEGIBLE.
  
 3)MINIMUM REAR SETBACK REQUIREMENT OF 4.9' TO THE
 POOL EQUIPMENT.THE PROPOSED DOES NOT MEET THIS
 REQUIREMENT.NOTE:THE EQUIPMENT CAN GO AS CLOSE AS
 1' TO THE WEST SIDE PROPERTY LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720