Plan Review Details - Permit 07110480
Plan Review Stops For Permit 07110480
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-14 Cont ID  
Sent By mperson Date 2008-07-14 Time 08:20 Rev Time 0.00
Received By mperson Date 2008-07-14 Time 08:20 Sent To PC
Notes
2008-07-14 08:25:18REVISION: "OK" NEW LONGEST LENGTH OF 300'. (SEE RED
 LINE CHANGES TO CSST IN ATTIC)
  
 ****************PROVISO****************
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-12-05 Cont ID  
Sent By mperson Date 2007-12-05 Time 08:51 Rev Time 0.00
Received By mperson Date 2007-12-05 Time 08:51 Sent To PC
Notes
2007-12-05 09:03:39****************PROVISO****************
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 15:17 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 15:17 Sent To G
Notes
2008-07-10 15:18:06TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-05 Cont ID  
Sent By mperson Date 2007-12-05 Time 09:04 Rev Time 0.00
Received By mperson Date 2007-11-19 Time 13:44 Sent To  
Notes
2007-11-19 13:44:32TO "G" BOX