Plan Review Details - Permit 07110460
Plan Review Stops For Permit 07110460
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-11 Cont ID  
Sent By jgomez Date 2008-06-11 Time 16:13 Rev Time 0.00
Received By jgomez Date 2008-06-11 Time 16:13 Sent To PC
Notes
2008-06-11 16:15:24REMAINDER:COMPLY WITH PROVISO DATED 2-12-08 TO AVOID
 DELAYS IN CERTIFICATE OF OCCUPANCY. SEE ATTACHED COPY
 OF PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-02 Cont ID  
Sent By jgomez Date 2008-04-02 Time 13:40 Rev Time 0.00
Received By jgomez Date 2008-04-02 Time 13:40 Sent To E
Notes
2008-04-02 13:44:37BUILDING REVISION APPROVED. THE FOLLOWING ARE
 INFORMATIONAL NOTES:
  
 1-PLANS SENT TO ELECTRICAL BECAUSE REVISED ELECTRICAL
 PLAN WAS SUBMITTED.
  
 2- REMAINDER: PROVIDE INFORMATION REQUESTED ON PROVISO
 DATED 02/12/08 TO AVOID DELAYS. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By jgomez Date 2008-02-12 Time 14:18 Rev Time 0.00
Received By jgomez Date 2008-02-12 Time 14:17 Sent To Z
Notes
2008-02-12 14:24:07BUILDING REVIEW APPROVED WITH PROVISO:
 1-SURVEY NEEDSTO HAVE ORIGINAL SIGNATURE, NOT
 RUBBER STAMP, AS REQUIRED BYCHAPTER 472 FLORIDA
 STATUTE AND SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE
 CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-12 Cont ID  
Sent By btrobaug Date 2008-02-04 Time 08:49 Rev Time 0.00
Received By jgomez Date 2008-01-17 Time 16:56 Sent To PC
Notes
2008-01-17 17:01:14BUILDING REVIEW APPROVED WITH PROVISO.
  
 1-ARCHITECT TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2OF CITY AMENDMENTS TO FBC
 2004. IFUSING NAILS OR SCREWS, THENSPECIFY SIZE AND
 NUMBER. IF USING POLYFOAM, THEN PROVIDE PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72.SEE TILE
 PRODUCT APPROVAL FOR LISTED FOAM TO BE USED.
  
 ***NOTE:PROVIDE INFORMATION PRIOR TO INSTALLATION TO
 AVOID CONFLICTS OR DELAYS.
  
 2- SURVEY:
 A) REVISE DIMENSIONS TO MATCH ARCHITECTURAL SITE
 PLAN AND FOUNDATION PLAN. NO HAND WRITEN DIMENSIONS.
  
 B) NEED ORIGINAL SURVEYOR'S SIGNATURE AS REQUIRED BY
 CHAPTER 472 AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G17-7.0025. COPY OF SIGNATURE IS NOT ALLOWED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By jgomez Date 2007-12-10 Time 12:59 Rev Time 0.00
Received By jgomez Date 2007-12-10 Time 12:59 Sent To PC
Notes
2007-12-10 13:03:49RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW
 DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 2- SHEET T1.0:
 A) SPECIFY ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) CODE TO BE REFERENCED IS FBC 2004 WITH 2007
 REVISIONS, NOT 2006. UPDATE AS REQUIRED.
  
 C) COMPONENTS & CLADDING DESIGN WIND PRESSURES DON'T
 MATCH THE DESIGN PRESSURES SPECIFIED ON SHEET A3.0.
 REVISE AS REQUIRED TO MATCH.
  
 D) CONSULTING ENGINEER "STRUCTURAL SYSTEMS, INC" TO
 SIGN AND SEAL DRAWINGS AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND SEC. 61G15-23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE.
  
 E) REVISE MASONRY NOTE ON STRUCTURAL NOTES AND ON
 CONCRETE UNIT MASONRY NOTE F.SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE REGARDING THE MINIMUM MASONRY
 UNIT ALLOWABLE STRESS.
  
 F) UPDATE THERMAL MOISTURE PROTECTION NOTE A. SEE
 CHAPTER 13 FBC 2004 FOR CORRECT REFERENCE TO BE USED.
  
 3- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004
 FLORIDA RESIDENTIALCODE.TWO COPIES WITH ORIGINAL
 SIGNATURE AND SEAL. AND, ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER. SEC. 61G15-23.002(2) OF
 FLORIDA ADMINISTRATIVE CODE.
  
 4- DESIGNEROF RECORD TO SPECIFY ROOF TILE FASTENING.
 SEESEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. IF
 USING POLYFOAM, THEN PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72.
 IN ADDITION, MAKE SURE THAT TILE ADHESIVE IS TESTED AND
 APPROVED TO BE USED WITH GRACE ICE UNDERLAYMENT, WHICH
 IS THE TYPE OF UNDERLAYMENT THAT WAS SUBMITTED WITH
 THIS PACKAGE. PROVIDE TECHNICAL INFORMATION AS REQUIRED
 TO SHOW COMPATIBILITY WITH THE PROPOSED INSTALLATION.
 ON THE OTHER HAND, IF USING NAILS OR SCREWS, THEN
 CLEARLY SPECIFY TYPE AND NUMBER TO VERIFY COMPLIANCE
 WITH THE UPLIFT RESISTANCE SHOWN ON THE PRODUCT
 APPROVAL.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FIXED WINDOW SIZE AS SHOWN ON PLANS.
  
 B) WINDOW MULLIONS.
  
 C) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE WHERE CONNECTOR IS SHOWN.
  
 D) PRECAST LINTELS.
  
 E) GRACE ICE UNDERLAYMENT.INFORMATION SUBMITTED
 NEED TO HAVE THE INSTALLATION SPECIFICATIONS.
 COORDINATE INFORMATION WITH ITEM 4 ABOVE.
  
 F) SINGLE HUNG WINDOWS. PROVIDE INFORMATION THAT
 MATCHES INFORMATION GIVEN ON FL #2769.3. IT SHOWS 7/16
 GLAZING. INFORMATION SUBMITTED DOESN'T MATCH.
  
  
 6- PROVIDE STRUCTURAL WINDOW BUCK DETAILUSING 2X BUCK
 TO SHOW COMPLIANCE WITH PRODUCT APPROVAL SUBMITTED FOR
 SINGLE HUNG WINDOWS.PRODUCT APPROVAL SUBMITTEDONLY
 SHOWS ATTACHMENT TO 2X STRUCTURAL BUCK.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 7- SHEET D1.0: REVISE TYPE OF NAIL TO BE USED IN ROOF
 SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.REQUIRES 8D RING SHANK NAILS.
  
 8- OWES $7.26 FOR RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-07 Cont ID  
Sent By btrobaug Date 2008-04-07 Time 08:52 Rev Time 0.00
Received By btrobaug Date 2008-04-07 Time 07:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-02-15 Cont ID  
Sent By btrobaug Date 2008-02-15 Time 08:17 Rev Time 0.00
Received By btrobaug Date 2008-02-15 Time 08:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-04 Cont ID  
Sent By btrobaug Date 2008-02-04 Time 08:16 Rev Time 0.00
Received By btrobaug Date 2008-02-04 Time 07:01 Sent To B
Notes
2008-02-04 09:13:58 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE LOAD CALCULATIONS PER 220.83 INCLUDING
 EXISTING AND ADDED LOADS.106.3.5.4(8) FBC AS AMENDED.
  
 2} LOCATE THE NEW 125 AMP PANEL ON THE PLANS SO THAT
 COMPLIANCE WITH 230.70, 225.32 MAY BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-10 Cont ID  
Sent By btrobaug Date 2008-01-10 Time 14:08 Rev Time 0.00
Received By btrobaug Date 2008-01-10 Time 10:24 Sent To M
Notes
2008-01-10 14:06:46 
  
  
 APPLICATION # 07110460
 ELECTRICAL PLAN REVIEW
 10301 HERONWOOD LANE
 1/10/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED. SHEET E-1, UNLESS OTHERWISE NOTED.
  
 1} THE RISER DIAGRAM INDICATES A 225 AMP MAIN BREAKER
 AND 3/0 COPPER FEEDERS, WHICH ARE CORRECT FOR THAT
 BREAKER PER 310.15(B)(6). THE LOAD CALCULATIONS ARE
 SHOWN AS 246 AMPS, AND ALTHOUGH THE NOTE AT THE BOTTOM
 OF THE CALCULATION INDICATES A 300 AMP SERVICE, THAT
 DOES NOT CORRELATE WITH THE RISER. SERVICE-LATERAL
 CONDUCTORS SHALL HAVE SUFFICIENT AMPACITY TO CARRY THE
 CURRENT FOR THE LOAD AS CALCULATED IN ACCORDANCE WITH
 ARTICLE 220 AND SHALL HAVE ADEQUATE MECHANICAL
 STRENGTH. THE SERVICE SIZE MUST BE INCREASED TO SERVE
 THE LOAD, OR BE RECALCULATED TO INDICATE THE DEMAND IS
 LESS THAN 225 AMPS. SEE 220.83.
  
 2} THE 6/0 FEEDERS INDICATED ON THE RISER DO NOT
 CORRELATE WITH AWG SIZES IN THE NEC.
  
 3} THE DISCONNECT FOR THE A/C UNIT DOES NOT COMPLY WITH
 110.26 CLEARANCE REQUIREMENTS. * THIS COMMENT IS MADE
 AGAIN BECAUSE OF THE "CONCRETE EQUIPMENT PAD"IN FRONT
 OF THE DISCONNECT. SEE 110.26.
  
 NOTE: ITEMS 2 AND 3 COULD HAVE BEEN REDLINED AND FIELD
 CORRECTED WITH A REVISION. THE LOAD CALCULATION AND
 SERVICE SIZE CANNOT BE REDLINED, SO ITEMS 2 AND 3
 SHOULD BE CORRECTED AT THIS TIME TO SAVE REVISION
 FEES.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 14:12 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 13:31 Sent To M
Notes
2007-11-20 14:12:04 
  
 APPLICATION #07110460
 ELECTRICAL PLAN REVIEW
 10301 HERONWOOD LANE
 11/20/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
 ALL COMMENTS RELATE TO SHEET E1.0, UNLESS OTHERWISE
 NOTED.
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THIS IS TO VERIFY THE TOTAL LOAD IS IN COMPLIANCE WITH
 220.83, TOTAL LOAD DOES NOT EXCEED THE SERVICE RATING.
  
 2} THE RISER DIAGRAM FEEDERS AND PANEL RATING ARE NOT
 CONSISTENT WITH THE PLANS. THE PLAN INDICATES A 60 AMP
 PANEL, THE RISER A 50 AMP. THE 6/0 FEEDERS INDICATED ON
 THE RISER DO NOT CORRELATE WITH AWG SIZES IN THE NEC.
  
 3} CIRCUIT #9 ON THE PANEL SCHEDULE INDICATES EXTERIOR
 RECEPTACLES ON THE SAME CIRCUIT WITH THE BATH IN
 VIOLATION OF 210.11(C)(3).
  
 4} THE DISCONNECT FOR THE A/C UNIT DOES NOT COMPLY WITH
 110.26 CLEARANCE REQUIREMENTS. INDICATE IF THIS IS A
 NEW OR RELOCATED SYSTEM.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 10:56 Sent To Z
Notes
2008-06-09 10:56:49TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 11:10 Sent To M
Notes
2008-04-29 11:12:40TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 16:12 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 16:12 Sent To Z
Notes
2008-03-26 16:12:45TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 15:34 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 15:34 Sent To E
Notes
2008-02-01 15:35:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-08 Time 16:42 Rev Time 0.00
Received By adarroug Date 2008-01-08 Time 16:42 Sent To Z
Notes
2008-01-08 16:43:39TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By jgomez Date 2007-12-10 Time 13:03 Rev Time 0.00
Received By jgomez Date 2007-11-19 Time 10:25 Sent To  
Notes
2007-11-19 10:26:42TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By tgordon Date 2008-04-30 Time 08:44 Rev Time 0.30
Received By tgordon Date 2008-04-30 Time 08:44 Sent To  
Notes
2008-04-30 08:44:59REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-11 Cont ID  
Sent By tgordon Date 2008-01-11 Time 09:40 Rev Time 0.30
Received By tgordon Date 2008-01-11 Time 09:40 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 15:20 Rev Time 0.20
Received By tgordon Date 2007-11-28 Time 15:19 Sent To P
Notes
2007-11-28 15:25:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PERMIT #07110463 HAS BEEN APPLIED FOR AND
 AN A/C SYSTEM IS BEING INSTALLED, BUT NO MECHANICAL
 PLANS WERE SUBMITTED FOR REVIEW. PLEASE SUBMIT
 MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY OF WPB
 AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-16 Cont ID  
Sent By jleech Date 2008-01-16 Time 08:03 Rev Time 0.00
Received By jleech Date 2008-01-16 Time 08:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 07:33 Rev Time 0.00
Received By jleech Date 2007-12-04 Time 07:26 Sent To B
Notes
2007-12-04 07:37:33DENIED;
 ADD NOTE TO PAGE A-2, " REMOVE ALL PIPING FROM 1/2 BATH
 BACK TO THE BUILDING DRAIN. NO DEAD ENDS PERMITED.
 INSPECTION REQUIRED". SEE FBC PLUMBING SECTION 704.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2008-06-10 Cont ID  
Sent By choops Date 2008-06-10 Time 14:46 Rev Time 0.00
Received By choops Date 2008-06-10 Time 14:46 Sent To B
Notes
2008-06-10 14:46:40***APPROVED - REVISION - ADDING PRIVACY WALL AROUND A/C
 UNIT, STEEL DETAILS FOR RACK BEAM CHANGE
 (STRUCTURAL)***
  
  
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 4 Status F Date 2008-03-28 Cont ID  
Sent By choops Date 2008-03-28 Time 12:01 Rev Time 0.00
Received By choops Date 2008-03-28 Time 12:01 Sent To B
Notes
2008-03-28 12:04:07***FAILED - REVISION - ADDING PRIVACY WALL AROUND A/C
 UNIT, STEEL DETAILS FOR RACK BEAM CHANGE
 (STRUCTURAL)***
  
  
 1)PRIVACY WALL DETAIL (SHEET A1.0) SHOWS PRIVACY
 WALL TO BE 6 FEET IN HEIGHT, ALL OTHER PLANS SHOW
 PROPOSED PRIVACY WALL AT 5 FEET IN HEIGHT.PLEASE
 CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By choops Date 2008-02-12 Time 15:16 Rev Time 0.00
Received By choops Date 2008-02-12 Time 15:16 Sent To  
Notes
2008-02-12 15:17:03***APPROVED - RESUB #2***
  
 RESTAMPED PLANS

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-09 Cont ID  
Sent By choops Date 2008-01-09 Time 11:32 Rev Time 0.00
Received By choops Date 2008-01-09 Time 11:32 Sent To E
Notes
2008-01-09 11:32:30***APPROVED - RESUB #1***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By choops Date 2007-11-19 Time 13:24 Rev Time 0.00
Received By choops Date 2007-11-19 Time 13:24 Sent To E
Notes
2007-11-19 13:31:51***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.PURSUANT TO SECTION
 94-305(B)(4) OF THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS):MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED
 SETBACK.
  
 NOTE:ADDITION MUST MAINTAIN INTERIOR ACCESS WITH
 EXISTING STRUCTURE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720