Plan Review Details - Permit 07110453
Plan Review Stops For Permit 07110453
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-02 Cont ID  
Sent By shill Date 2008-01-02 Time 14:03 Rev Time 0.00
Received By shill Date 2008-01-02 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By shill Date 2007-12-10 Time 08:01 Rev Time 0.00
Received By shill Date 2007-12-10 Time 08:01 Sent To  
Notes
2007-12-10 08:03:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS481.
  
 2.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 3.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 4.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER.
  
 5.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE
 OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING
 MARSHALL & SWIFT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-13 Cont ID  
Sent By btrobaug Date 2007-12-13 Time 14:15 Rev Time 0.00
Received By btrobaug Date 2007-12-13 Time 13:48 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 14:18 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 13:28 Sent To M
Notes
2007-11-29 14:18:41 
  
 APPLICATION #07110453
 ELECTRICAL PLAN REVIEW
 214 ALHAMBRA PLACE
 11/29/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE FLOOR PLAN (SHEET #4) INDICATES A RECEPTACLE
 THAT THE PERMANENTLY INSTALLED GENERATOR CONNECTS WITH
 TO POWER THE EMERGENCY PANEL. SUBMIT DOCUMENTS THAT
 INDICATE A CORD CONNECTION IS ACCEPTABLE FOR THIS TYPE
 OF INSTALLATION. THE DIAGRAM SUBMITTED WITH THE
 MANUFACTURERS PACKAGE INDICATES A HARD WIRED SYSTEM TO
 A AUTOMATIC TRANSFER SWITCH. CLARIFY THE TRANSFER IS TO
 BE MANUAL.
  
 2} VERIFY THE GENERATOR SETBACK SHOWN ON THE PLAN
 COMPLIES WITH THE MANUFACTURERS RECOMMENDED SETBACK.
 PROVIDE A WRITTEN RESPONSE TO THIS COMMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-18 Cont ID  
Sent By mperson Date 2007-12-18 Time 14:42 Rev Time 0.00
Received By mperson Date 2007-12-18 Time 14:42 Sent To B
Notes
2007-12-18 14:43:22NOTE: REFERENCE GAS PERMIT #07100379.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By mperson Date 2007-12-04 Time 12:56 Rev Time 0.00
Received By mperson Date 2007-12-04 Time 12:56 Sent To B
Notes
2007-12-04 14:00:26NOTE: REFERENCE GAS PERMIT #07100379 SUBMITTED 10/12/07
 FOR GAS COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 10:46 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 10:46 Sent To  
Notes
2007-12-13 10:49:59TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By shill Date 2007-12-10 Time 08:03 Rev Time 0.00
Received By shill Date 2007-11-19 Time 11:21 Sent To  
Notes
2007-11-19 11:22:01TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 13:36 Rev Time 0.20
Received By tgordon Date 2007-11-30 Time 13:36 Sent To G
Notes
2007-11-30 13:38:40*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 09:47 Rev Time 0.00
Received By choops Date 2007-11-28 Time 09:47 Sent To E
Notes
2007-11-28 09:48:45***APPROVED***
  
 PROVISO: GENERATOR MUST BE A MINIMUM OF 1' FROM THE
 EAST SIDE PROPERTY LINE, AND A MINIMUM OF 11' FROM THE
 REAR PROPERTY LINE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved