| Plan Review Stops For Permit 07110453 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-01-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-02 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-02 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-10 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-10 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2007-12-10 08:03:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS481. | | | | | | 2.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH | | | FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS, | | | AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING, | | | UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS | | | FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF | | | THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD | | | LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE USED. | | | | | | 3.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. | | | | | | 4.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL | | | DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB | | | SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. | | | | | | 5.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE | | | OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING | | | MARSHALL & SWIFT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-13 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-13 |
Time |
13:48 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-29 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-29 |
Time |
13:28 |
Sent To |
M |
|
| Notes |
| 2007-11-29 14:18:41 | | | | | | | APPLICATION #07110453 | | | ELECTRICAL PLAN REVIEW | | | 214 ALHAMBRA PLACE | | | 11/29/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} THE FLOOR PLAN (SHEET #4) INDICATES A RECEPTACLE | | | THAT THE PERMANENTLY INSTALLED GENERATOR CONNECTS WITH | | | TO POWER THE EMERGENCY PANEL. SUBMIT DOCUMENTS THAT | | | INDICATE A CORD CONNECTION IS ACCEPTABLE FOR THIS TYPE | | | OF INSTALLATION. THE DIAGRAM SUBMITTED WITH THE | | | MANUFACTURERS PACKAGE INDICATES A HARD WIRED SYSTEM TO | | | A AUTOMATIC TRANSFER SWITCH. CLARIFY THE TRANSFER IS TO | | | BE MANUAL. | | | | | | 2} VERIFY THE GENERATOR SETBACK SHOWN ON THE PLAN | | | COMPLIES WITH THE MANUFACTURERS RECOMMENDED SETBACK. | | | PROVIDE A WRITTEN RESPONSE TO THIS COMMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-18 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-18 |
Time |
14:42 |
Sent To |
B |
|
| Notes |
| 2007-12-18 14:43:22 | NOTE: REFERENCE GAS PERMIT #07100379. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-04 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-04 |
Time |
12:56 |
Sent To |
B |
|
| Notes |
| 2007-12-04 14:00:26 | NOTE: REFERENCE GAS PERMIT #07100379 SUBMITTED 10/12/07 | | | FOR GAS COMMENTS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-13 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-13 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2007-12-13 10:49:59 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-10 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-19 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2007-11-19 11:22:01 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-30 |
Time |
13:36 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-11-30 |
Time |
13:36 |
Sent To |
G |
|
| Notes |
| 2007-11-30 13:38:40 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT | | | PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL | | | COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA | | | 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES | | | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT | | | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES | | | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT | | | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-28 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-28 |
Time |
09:47 |
Sent To |
E |
|
| Notes |
| 2007-11-28 09:48:45 | ***APPROVED*** | | | | | | PROVISO: GENERATOR MUST BE A MINIMUM OF 1' FROM THE | | | EAST SIDE PROPERTY LINE, AND A MINIMUM OF 11' FROM THE | | | REAR PROPERTY LINE. |
|
|