Plan Review Details - Permit 07110407
Plan Review Stops For Permit 07110407
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-23 Cont ID  
Sent By mjacobs Date 2008-06-23 Time 15:15 Rev Time 0.00
Received By mjacobs Date 2008-06-23 Time 14:26 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-03 Cont ID  
Sent By mjacobs Date 2008-05-03 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2008-05-03 Time 06:13 Sent To  
Notes
2008-05-03 06:40:55BUILDING PLAN REVIEW
 PERMIT: 07110407
 ADD: 1411 N. FLAGLER DR 8900B
 CONT: ANDERSON MOORE CONST.
 TEL: (561)753-7400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-3-08
 REVIEW: #2 REVISION
 ACTION: DENIED
  
 1)THE ORIGINAL PLANS SHOWS WALL P-3 BEHIND THE
 ELECTRICAL PANELS ON SHEET A.1. THE REVISION NOW SHOWS
 THE SAME WALL IN FRONT OF THE ELECTRICAL PANELS WHICH
 WILL MAKE THE PANELS INACCESSIBLE. IT SEEMS AS THOUGH A
 NEW ELECTRICAL CLOSET IS BEING CREATED BY ADDING THESE
 DOORS WHICH MAY BE AN ELECTRICAL VIOLATION. THE
 ELECTRICAL PAGES SHALL BE REVISED TO SHOW THE LOCATION
 OF THE DOORS IN RELATION TO THE PANELS FOR THE REQUIRED
 CLEARANCE FOR ELECTRICAL CLOSETS. THE ONLY CODE SECTION
 IN THE BUILDING CODE WHICH COVERS THIS SITUATION IS FBC
 2701.1 SCOPE.
 THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS,
 EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES
 COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT
 AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL
 ELECTRICAL CODE, EXCEPT ARTICLE 80.
 THE ELECTRICAL PLAN REVIEWER WILL HAVE TO REVIEW THIS
 CHANGE BEFORE THE DOORS ARE APPROVED. ADDITIONAL
 INFORMATION IS REQUIRED WPB AMENDMENTS 106.1.2
  
 **SAME PLANS SUBMITTED WITH SHET E.1 NEEDS ELECTRIC
 APPROVAL**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-11 Cont ID  
Sent By mjacobs Date 2008-04-11 Time 17:28 Rev Time 0.00
Received By mjacobs Date 2008-04-11 Time 14:53 Sent To  
Notes
2008-04-11 17:27:57BUILDING PLAN REVIEW
 PERMIT: 07110407
 ADD: 1411 N. FLAGLER DR 8900B
 CONT: ANDERSON MOORE CONST.
 TEL: (561)753-7400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-11-08
 REVIEW: REVISION
 ACTION: DENIED
  
 1)THE ORIGINAL PLANS SHOWS WALL P-3 BEHIND THE
 ELECTRICAL PANELS ON SHEET A.1. THE REVISION NOW SHOWS
 THE SAME WALL IN FRONT OF THE ELECTRICAL PANELS WHICH
 WILL MAKE THE PANELS INACCESSIBLE. IT SEEMS AS THOUGH A
 NEW ELECTRICAL CLOSET IS BEING CREATED BY ADDING THESE
 DOORS WHICH MAY BE AN ELECTRICAL VIOLATION. THE
 ELECTRICAL PAGES SHALL BE REVISED TO SHOW THE LOCATION
 OF THE DOORS IN RELATION TO THE PANELS FOR THE REQUIRED
 CLEARANCE FOR ELECTRICAL CLOSETS. THE ONLY CODE SECTION
 IN THE BUILDING CODE WHICH COVERS THIS SITUATION IS FBC
 2701.1 SCOPE.
 THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS,
 EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES
 COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT
 AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL
 ELECTRICAL CODE, EXCEPT ARTICLE 80.
 THE ELECTRICAL PLAN REVIEWER WILL HAVE TO REVIEW THIS
 CHANGE BEFORE THE DOORS ARE APPROVED. ADDITIONAL
 INFORMATION IS REQUIRED WPB AMENDMENTS 106.1.2
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By mjacobs Date 2007-12-12 Time 18:02 Rev Time 0.00
Received By mjacobs Date 2007-12-12 Time 17:36 Sent To PC
Notes
2007-12-12 18:02:39PROCESS PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-11-30 Cont ID  
Sent By mjacobs Date 2007-11-30 Time 09:42 Rev Time 0.00
Received By mjacobs Date 2007-11-29 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-18 Cont ID  
Sent By btrobaug Date 2008-06-18 Time 12:25 Rev Time 0.00
Received By btrobaug Date 2008-06-18 Time 11:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-12 Cont ID  
Sent By btrobaug Date 2008-05-05 Time 10:15 Rev Time 0.00
Received By btrobaug Date 2008-05-05 Time 09:33 Sent To  
Notes
2008-05-12 11:17:48 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 240.24 LOCATION IN OR ON PREMISESOCCUPANCY EACH
 OCCUPANT SHALL HAVE READY ACCESS TO ALL OVERCURRENT
 DEVICES PROTECTING THE CONDUCTORS SUPPLYING THAT
 OCCUPANCY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-14 Cont ID  
Sent By btrobaug Date 2008-04-14 Time 09:13 Rev Time 0.00
Received By btrobaug Date 2008-04-14 Time 08:20 Sent To  
Notes
2008-04-14 08:36:45 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE ELECTRICAL PANELS SHOWN ON SHEET E.1 OF
 THE PERMIT SET OF PLANS IN THE LOCATION THE FIRE DOORS
 ARE TO BE INSTALLED. SUBMIT REVISED ELECTRICAL PLANS TO
 SHOW THE INTENT OF THE WORK BEING APPLIEDFOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-27 Cont ID  
Sent By btrobaug Date 2007-11-27 Time 17:17 Rev Time 0.00
Received By btrobaug Date 2007-11-27 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-06-19 Cont ID  
Sent By mawillia Date 2008-06-19 Time 13:09 Rev Time 0.00
Received By mawillia Date 2008-06-19 Time 12:53 Sent To  
Notes
2008-06-19 13:06:39*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET A.1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-08 Cont ID  
Sent By mwennerg Date 2008-05-08 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2008-05-08 Time 14:08 Sent To  
Notes
2008-05-08 14:12:52***DENIED***
  
 1) IT APPEARS THAT REQUIRED CLEARANCE AROUND THE
 ELECTRICAL PANEL MAY BE COMPROMISED. ACCESS TO
 ELECTRICAL SERVICE SHALL BE PROVIDED. NFPA 101, SEC.
 9.1.2
  
 2) IF AN EMERGENCY SHOULD OCCUR IN THE AREA SERVED BY
 THE ELECTRICAL SERVICE, HOW WILL EMERGENCY PERSONNEL
 DETERMINE THE LOCATION OF THE SERVICE AND ACCESS THE
 PANEL?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-21 Cont ID  
Sent By mawillia Date 2008-04-21 Time 12:11 Rev Time 0.00
Received By mawillia Date 2008-04-21 Time 12:04 Sent To  
Notes
2008-04-21 12:10:22*****REVISION, DATED 4/2/08, APPROVED*****
  
  
 REVISED PLAN SHEET A.1 TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEWE(S) HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 11:58 Rev Time 0.00
Received By mawillia Date 2007-12-12 Time 11:44 Sent To B1
Notes
2007-12-12 11:56:01*****APPROVED*****
  
  
 PLAN SHEETS A.1, A.2, AND E.2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 11:32 Sent To  
Notes
2008-06-13 11:33:02TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 10:22 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 10:22 Sent To  
Notes
2008-04-24 10:22:29TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 15:23 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 15:23 Sent To  
Notes
2008-04-07 15:26:40TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 11:44 Rev Time 0.00
Received By mawillia Date 2007-11-15 Time 15:22 Sent To  
Notes
2007-11-19 10:06:55TO "BOB"#15
2007-11-15 15:22:56WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By tgordon Date 2008-04-08 Time 08:26 Rev Time 0.30
Received By tgordon Date 2008-04-08 Time 08:26 Sent To  
Notes
2008-04-08 08:26:58REVISION TO MECH. PLAN PAGE M.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 09:30 Rev Time 0.30
Received By tgordon Date 2007-11-28 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-11 Cont ID  
Sent By jleech Date 2007-12-11 Time 07:30 Rev Time 0.00
Received By jleech Date 2007-12-11 Time 07:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-19 Cont ID  
Sent By choops Date 2007-11-19 Time 15:44 Rev Time 0.00
Received By choops Date 2007-11-19 Time 15:44 Sent To  
Notes
2007-11-19 15:44:34*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.