Plan Review Details - Permit 07110377
Plan Review Stops For Permit 07110377
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 16:29 Rev Time 0.00
Received By shill Date 2007-12-13 Time 16:29 Sent To  
Notes
2007-12-13 16:32:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ADDRESSED.
  
 2.SEE SHEET 10.-75PSF REQUIRES 12" SPACING,
 INSTALLATION SCHEDULE SPECIFIES 13.5".
  
 ANCHOR SPACING NOT COMPLIANT FOR DESIGN PRESSURES
 SPECIFIED.
  
 3.SHUTTER CONNECTION MOUNTING TYPE STATES TAPCON,
 SHOULD CORRELATE WITH ANCHOR SCHEDULES, SECTIONS 1
 THROUGH 13, OR ALTERNATIVE SECTIONS 1 THROUGH 14.
  
 4.WHAT IS THE SUBSTRATE?THE INSTALLATION SCHEDULE
 STATES "WOOD - CBS".DOES THIS MEAN THAT IT IS CBS ON
 THE BOTTOM, WOOD ON THE TOP?
  
 5.AN EDGE DISTANCE OF LESS THAN 3 1/2" FOR CBS
 REQUIRES USE OF A FACTOR, SEE SHEET 16.
  
 EDGE DISTANCE OF 1/2" AND 1 1/4" NOT ALLOWED.PLEASE
 SEE PRODUCT APPROVAL, SHEET 10, AND REVISE INSTALLATION
 SCHEDULE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By swurafti Date 2007-11-14 Time 14:01 Rev Time 0.00
Received By shill Date 2007-11-19 Time 16:22 Sent To  
Notes
2007-11-19 16:28:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT
 ISSUANCE.
  
 2.SEE SHEET 10.-75PSF REQUIRES 12" SPACING,
 INSTALLATION SCHEDULE SPECIFIES 13.5".
  
 3.SHUTTER CONNECTION MOUNTING TYPE STATES TAPCON,
 SHOULD CORRELATE WITH ANCHOR SCHEDULES, SECTIONS 1
 THROUGH 13, OR ALTERNATIVE SECTIONS 1 THROUGH 14.
  
 4.WHAT IS THE SUBSTRATE?THE INSTALLATION SCHEDULE
 STATES "WOOD - CBS".DOES THIS MEAN THAT IT IS CBS ON
 THE BOTTOM, WOOD ON THE TOP?
  
 5.AN EDGE DISTANCE OF LESS THAN 3 1/2" FOR CBS
 REQUIRES USE OF A FACTOR, SEE SHEET 16.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 14:00 Sent To B
Notes
2007-12-07 14:01:14TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 16:28 Rev Time 0.00
Received By shill Date 2007-11-15 Time 10:37 Sent To  
Notes
2007-11-15 10:38:11TO "MISC" BOX#1