| 2007-12-24 15:46:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A |
| | PLUMBING PERMIT IS BEING APPLIED FOR. PLEASE PROVIDE |
| | THE FOLLOWING INFORMATION. |
| | |
| | A} THE NEW PROPOSED KITCHEN PLUMBING LAYOUT IS |
| | DIFFERENT FROM THE EXISTING KITCHEN. PLEASE SUBMIT THE |
| | EXISTING FLOOR PLAN LAYOUT CLEARLY INDICATING THE |
| | EXISTING KITCHEN AND WASHING MACHINE LOCATION ON A |
| | SEPERATE DRAWING, MINIMUM 1/8 INCH SCALE REQUIRED. |
| | |
| | 2. SHEET A1: PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY)(9) PLUMBING, PLEASE |
| | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM |
| | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH |
| | CLEANOUT LOCATIONS. |
| | **NOTE: THE SUBMITTED SANIATARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOT ALL PIPES OR TRAPS ARE |
| | SIZED AND IS NOT CODE COMPLIANT. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING |
| | |
| | (C) A VENT IS REQUIRED FOR THE WASHING MACHINE. PER |
| | *901.2.1, VENTING REQUIRED. |
| | |
| | (D) 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | |
| | (E) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | **NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | 3". |
| | |
| | (F) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT 4' A.F.F. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |