Plan Review Details - Permit 07110346
Plan Review Stops For Permit 07110346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-09 Cont ID  
Sent By kconrad Date 2008-01-09 Time 16:45 Rev Time 0.00
Received By kconrad Date 2008-01-08 Time 19:01 Sent To I
Notes
2008-01-09 16:12:10PROJECT: 428 WINTERS STREET/ #07110346
  
 PROJECT DETAIL: ENCLOSE CARPORT, INTERIOR ALTERATION &
 INSTALL NEW WINDOWS/DOORS.
  
 PLAN REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS,
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATIVE AMENDMENTS 2004
  
 STATUS: FAILED
  
 COMMENTS:
  
 1)1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLEASE PROVIDE PRODUCT APPROVALS FOR THE INDICATED
 FASTENERS/ANCHORS AND STRAPS AS PER:
  
 9B-72.005 SCOPE.
 (1) PRODUCTS IN THE FOLLOWING CATEGORIES AS DEFINED BY
 SUBCATEGORIES OF SUBSECTION 9B-72.010(31), F.A.C.,
 SHALL BE AVAILABLE FOR
 APPROVAL BY THE COMMISSION PURSUANT TO RULE 9B-72.090,
 F.A.C., FOR USE IN THE STATE:
 (A) PANEL WALLS;
 (B) EXTERIOR DOORS;
 (C) ROOFING PRODUCTS;
 (D) SKYLIGHTS;
 (E) WINDOWS;
 (F) SHUTTERS; AND
 (G) STRUCTURAL COMPONENTS.
  
 (2) THIS RULE APPLIES TO APPROVAL OF PRODUCTS AND
 SYSTEMS, WHICH COMPRISE THE BUILDING ENVELOPE AND
 STRUCTURAL FRAME, FOR
 COMPLIANCE WITH THE STRUCTURAL REQUIREMENTS OF THE
 FLORIDA BUILDING CODE.
 SPECIFIC AUTHORITY 553.842(1) FS. LAW IMPLEMENTED
 553.842(5) FS. HISTORY?NEW 11-22-06.
  
 3) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE
 FLORIDA EXISTING BUILDING CODE:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 FEBC, SECTION 611
  
 ENERGY CONSERVATION
 611.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 5) THE CMU/WOOD FRAME WALL DETAIL ON SHEET A-2DOES
 NOT INDICATE THE TYPE OF WALL ANCHOR TO BE USED. PLEASE
 PROVIDE ANCHOR SPECIFICATIONS.
  
 6) PLEASE INDICATE THE SPECIES AND GRADE OF LUMBER TO
 BE USED.
  
 7) PLEASE SUBMIT SHUTTER WORKSHEET AND FOOTPRINT.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By kconrad Date 2007-12-04 Time 14:40 Rev Time 0.00
Received By kconrad Date 2007-12-04 Time 14:40 Sent To I
Notes
2007-12-04 14:52:44PRODUCT APPROVALS SUBMITTED FOR WINDOWS/DOORS AND
 SHUTTERS. CONTACTED WILLIAM HATCHER, THE CONTRACTOR, TO
 ADVISE HIM THAT WE HAVE RESEARCHED THE PERMIT HISTORY.
 THE HISTORY DOES NOT REFLECT THE WORK THAT HAS BEEN
 COMPLETED: CARPORT CONVERTED TO A KITCHEN. THEREFORE,
 PLANS SHALL BE SUBMITTED INDICATING THE BUILDING,
 ELECTRICAL AND PLUMBING WORK. ALSO, DETAILS SHALL BE
 PROVIDED SHOWING THE CARPORT WALL SECTIONS/ELEVATIONS
 AND STRAPPING/ANCHOR DETAILS AS PER THE FBC 106.3.5.
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By kconrad Date 2007-11-21 Time 14:39 Rev Time 0.00
Received By kconrad Date 2007-11-21 Time 14:39 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By btrobaug Date 2007-12-21 Time 08:03 Rev Time 0.00
Received By btrobaug Date 2007-12-21 Time 07:43 Sent To Z
Notes
2007-12-21 08:02:55 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. INDICATE COMPLIANCE
 ON THE PLAN.
  
 3} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION. SHOW WORK BEING DONE AND
 COMPLIANCE WITH THE 2005 NEC IN THE AREA WHERE THE
 KITCHEN IS TO BE REMOVED.106.1.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 15:16 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 15:16 Sent To E
Notes
2007-12-18 15:16:50TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-17 Cont ID  
Sent By adarroug Date 2007-12-17 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-12-17 Time 14:02 Sent To B
Notes
2007-12-17 14:02:56TO "KCONRAD" DESK/RESUB

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By mperson Date 2007-12-24 Time 14:49 Rev Time 0.00
Received By mperson Date 2007-12-24 Time 14:49 Sent To B
Notes
2007-12-24 15:46:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A
 PLUMBING PERMIT IS BEING APPLIED FOR. PLEASE PROVIDE
 THE FOLLOWING INFORMATION.
  
 A} THE NEW PROPOSED KITCHEN PLUMBING LAYOUT IS
 DIFFERENT FROM THE EXISTING KITCHEN. PLEASE SUBMIT THE
 EXISTING FLOOR PLAN LAYOUT CLEARLY INDICATING THE
 EXISTING KITCHEN AND WASHING MACHINE LOCATION ON A
 SEPERATE DRAWING, MINIMUM 1/8 INCH SCALE REQUIRED.
  
 2. SHEET A1: PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY)(9) PLUMBING, PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH
 CLEANOUT LOCATIONS.
 **NOTE: THE SUBMITTED SANIATARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOT ALL PIPES OR TRAPS ARE
 SIZED AND IS NOT CODE COMPLIANT.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
  
 (C) A VENT IS REQUIRED FOR THE WASHING MACHINE. PER
 *901.2.1, VENTING REQUIRED.
  
 (D) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 (E) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 3".
  
 (F) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4' A.F.F.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 16:01 Rev Time 0.00
Received By choops Date 2007-12-21 Time 16:01 Sent To P
Notes
2007-12-21 16:34:40***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)CLARIFY SCOPE OF WORK.WHAT ARE YOU ENCLOSING?
  
 3)PROVIDE A DEMOLITION PLAN SHOWING THE EXISTING
 KITCHEN.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720