Plan Review Details - Permit 07110311
Plan Review Stops For Permit 07110311
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By jwitmer Date 2007-12-12 Time 08:43 Rev Time 2.22
Received By jwitmer Date 2007-12-12 Time 07:53 Sent To ENG
Notes
2007-12-12 08:44:44SPRINGHILL SUITES BY
 MARRIOTT
 2437 METROCENTRE BLVD
  
 FOUNDATION PERMIT# 07110311
  
 DEC.12, 2007
  
  
 BUILDING PROVISOS:
  
 BUILDING PROVISO:105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A DECREASE IN EXCESS
 OF 800SQ FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL
 AS A PERMIT CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By jwitmer Date 2007-11-29 Time 12:26 Rev Time 3.33
Received By jwitmer Date 2007-11-29 Time 12:26 Sent To  
Notes
2007-11-29 12:26:54BUILDING PLAN REVIEW
 PERMIT: 07110311
 ADD: 2437 METRO CENTRE BLVD E.
 CONT: DBC CONSTRUCTION
 TEL: (954)536-3959
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 INFORMATIVE, WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) YOUR PROJECT ISA THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIVE,106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E)INFORMATIVE, PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) THRESHOLD INSPECTION PLANFL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 5)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 6) BUILDING PROVISO:105.13. SPECIAL FOUNDATION
 PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 7) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 8) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 9) PLEASE REMOVE THE MEP SHEETS THAT ARE PART OF THE
 FOUNDATION PACKAGE, NOTE SEE ELECTRICAL NOTE THAT WILL
 REQUIRE BONDING. 106.1.2. ADDDITIONAL INFORMATION
 REQUIRED. 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT
 SECTIONS OF THIS CODE SPECIFY DIFFERENT MATERIALS,
 METHODS OF CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2007-12-11 Time 15:03 Sent To B
Notes
2007-12-11 15:03:41** SCOPE OF WORK FOR FOUNDATION GROUNDING ELECTRODE
 SYSTEM ONLY. NO SLAB WORK BEING PERFORMED FOR MEP OR
 BLDG TRADES.
 AN ELECTRICAL PERMIT BY A LICENSE ELECTRICAL CONTRACTOR
 INCLUDING INSPECTION OF SYSTEM IS REQUIRED.
 ONCE PERMIT IS ISSUED FOR FOUNDATION, ELECTRICAL
 CONTRACTOR MAY COME IN WITH PERMIT APPLICATION,
 REFERENCE THIS PERMIT NUMBER, PAY $50 SUB PERMIT FEE
 AND PERMIT WILL BE ISSUED AS TURN AROUND PERMIT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITU OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2007-11-29 Time 14:12 Sent To PC
Notes
2007-11-29 14:12:31** DENIED **
  
  
 1) NOTE: PLEASE PROVIDE PLANS/DETAILS FOR THE
 FOLLOWING.
  
 A) PLEASE PROVIDE THE GROUNDING ELECTRODE DETAIL FOR
 BUILDING ELECTRICAL SERVICE AND ATTACHMENT POINTS AS
 REQUIRED PER 250.50
  
 B) PLEASE KNOW THAT ANY STRUCTURAL FOUNDATION STEEL
 WHICH MAY BE INSTALLED AROUND POOL AREAS. PLEASE SEE
 NEC 680.26 FOR EQUAL-POTENTIAL BONDING GRID AND BONDING
 OF OTHER STEEL WHICH MAY BE IN AREAS ARE DESIGNATED PER
 NEC. IF NO STEEL OR OTHER FOUNDATION WORK IS BEING
 PERFORMED IN THESE AREAS THEN THIS WILL BE DONE UNDER
 SEPARATE PERMIT FOR BUILDING AND POOL.
  
 C) PLEASE PROVIDE DETAILS FOR ANY UNDERGROUND CONDUITS
 FOR SERVICE ENTRANCE, SITE OR OTHER CONDUITS WHICH MAY
 BE INSTALLED UNDER FOUNDATION SCOPE OF WORK AS SHOWN.
 AS UNDERGROUND INSPECTIONS ARE REQUIRED BY THE CODE FOR
 THESE, MUST HAVE PLANS AND PERMITS FOR THIS SCOPE. (IF
 APPLICABLE IN SCOPE OF FOUNDATION ONLY).
  
 2) NOTE: PLEASE BE SURE THESE DETAILS/PLANS ARE
 PROVIDED BY THE ENGINEER OF RECORD ON PLANS WHICH
 CONTAIN TITLE BLOCKS, ORIGINAL SIGNED, DATED AND SEALED
 AS REQUIRED PER FBC, FAC AND FS.
  
  
 ** ONCE AGAIN AS THERE ARE SOME ITEMS NOT YET SUBMITTED
 FOR REVIEW THERE MAY BE NEW COMMENTS GENERATED ON THE
 NEXT REVIEW AS THESE ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-12-24 Cont ID  
Sent By rchokshi Date 2007-12-24 Time 09:23 Rev Time 0.00
Received By rchokshi Date 2007-12-24 Time 09:22 Sent To  
Notes
2007-12-24 09:23:16PASSED PER E-MAILED RECEIVED FROM BRIAN MOREE &
 JONATHAN BRAMLEYTO ROBERT BROWN ON 12/21/07.BRIAN
 MOREE SAID IN HIS E-MAIL TO JONATHAN B. & ROBERT B.
 THATTHE DEVELOPER/ENGINEER HAVE PROVIDED SATISFACTORY
 BOND ( ORDINANCE NO: 4060-07 ) REQUIREMENTS PER BRIAN
 MOREE'S REVIEW.
  
 NOI REQUIREMENTS IS IN E-MAIL FROM TAD ROWE'S E-MAIL ON
 12/17/07.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-12-12 Cont ID  
Sent By rchokshi Date 2007-12-12 Time 11:30 Rev Time 0.00
Received By rchokshi Date 2007-12-12 Time 11:29 Sent To  
Notes
2007-12-12 11:30:23****FAILED*****
  
 PLEASE PROVIDE INFORMATIONASKED IN REV 1,11/28/07.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By rchokshi Date 2007-11-28 Time 14:01 Rev Time 0.00
Received By rchokshi Date 2007-11-28 Time 14:00 Sent To  
Notes
2007-11-28 14:00:56FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE PROVIDE ORDINANCE NO. 4060-07 INFO BELOW.
  
 ORDINANCE NO. 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 12:02 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 12:02 Sent To E
Notes
2007-12-10 12:02:49TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 14:01 Sent To ENG
Notes
2007-11-27 14:01:41TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By   Date 2007-11-29 Time   Rev Time 0.00
Received By adarroug Date 2007-11-13 Time 11:55 Sent To  
Notes
2007-11-13 11:55:53TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-20 Cont ID  
Sent By lfranco Date 2007-11-20 Time 14:13 Rev Time 0.00
Received By lfranco Date 2007-11-20 Time 14:13 Sent To ENG
Notes
***NONE***