Plan Review Details - Permit 07110294
Plan Review Stops For Permit 07110294
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By mjacobs Date 2007-11-21 Time 14:00 Rev Time 0.00
Received By mjacobs Date 2007-11-21 Time 07:05 Sent To  
Notes
2007-11-21 14:00:34 
 BUILDING PLAN REVIEW
 PERMIT: 07110294
 ADD: 927 BELVEDERE RD
 CONT: H. CHNO CONSTRUCTION
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)606.1 GENERAL.
 A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 3)NOW AN ELEVATOR IS PROPOSED TO BE INSTALLED, THE
 BUILDING WILL BE REQUIRED TO HAVE AN AREA IF RESCUE
 ASSISTANCE MEETING THE REQUIREMENTS OF FBC SECTION
 11-4.3.11.
  
 4) THE ENTIRE SECOND FLOOR PLAN IS REQUIRED TO SHOW ALL
 MEANS OF EGRESS IN THE BUILDING.
  
 5)INDICATE ON THE PLANS IF THE BUILDING HAS A
 SPRINKLER SYSTEM. AN AUTOMATIC SPRINKLER SYSTEM SHALL
 BE PROVIDED FOR GROUP A-3 OCCUPANCY, WHERE THE OCCUPANT
 LOAD IS 300 OR MORE AND THE FLOOR IS LOCATED ON A FLOOR
 OTHER THAN THE LEVEL OF EXIT DISCHARGE. FBC 903.2.1.3.
 BUILDINGS AND OTHER STRUCTURES WHERE MORE THAN 300
 PEOPLE CONGREGATE IN ONE AREA ARE CATEGORY III WITH AN
 IMPORTANCE FACTOR OF 1.15 PER TABLE 1604.5
  
 6)IF THE ELEVATION OF THE BUILDING ON SHEET A-2 IS
 32?-6?, HOW CAN THE MEAN ROOF HEIGHT BE 13? ON SHEET
 A-1? NOTE: THE ASCE 7-98 IS IN THE 2001 CODE, THE FBC
 2004 REFERS TOASCE 7-02. SEE FBC CHAPTER 35 FOR MORE
 INFORMATION.
  
 7)THE PRODUCT APPROVAL SUBMITTED SHALL BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. CIRCLE OR HI-LIGHT
 ALL ITEMS TO BE USED FOR THE INSTALLATION OF THE NEW
 EXTERIOR DOOR 106.3.3*
  
 8)PROVIDE A DETAIL ELEVATION DRAWING OF THE NEW
 OPENING LEADING TO THE ASSEMBLY AREA ON THE SECOND
 FLOOR.
  
 9) THE MACHINE ROOM SHALL MEET THE REQUIREMENTS OF FBC
 3006.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 14:34 Rev Time 0.00
Received By btrobaug Date 2007-11-26 Time 13:48 Sent To  
Notes
2007-11-26 14:34:19 
  
 APPLICATION #07110294
 ELECTRICAL PLAN REVIEW
 927 BELVEDERE ROAD
 11/26/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 LIGHTS AND RECEPTACLES REQUIRED BY 620.23.
  
 2} INDICATE COMPLIANCE WITH 620.85, GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 3} INDICATE THE LOCATION AND FEEDER DESIGNATION (PANEL
 AND CIRCUIT) FOR THE DISCONNECTING MEANS REQUIRED PER
 620.51. THE ELEVATOR DRAWINGS INDICATE A PIT, THE
 ARCHITECTURAL DRAWINGS SEEM TO INDICATE MACHINE ROOM,
 PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By mwennerg Date 2007-11-29 Time 13:53 Rev Time 0.00
Received By mwennerg Date 2007-11-29 Time 13:52 Sent To  
Notes
2007-11-29 14:10:34***DENIED***
  
 1) FLOOR PLANS AND DETAILS INDICATE GONZALEZ BUILDING
 ON BELVEDERE RD, AND APPLICATION STATES CHICO & MAN AT
 927 BELVEDERE RD. PLEASE CLARIFY AND CORRELATE IF
 NECESSARY.
  
 2) WORK TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) PROVIDE MORE DETAILS REGARDING EXISTING FIRE
 PROTECTION EQUIPMENT IF ANY.
  
 5) TACTILE WARNING SIGNS REQUIRED IN ELEVATOR LOBBY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-05 Cont ID  
Sent By jleech Date 2007-12-05 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-11-14 Time 11:46 Sent To  
Notes
2007-11-16 15:44:49TO "BOB"#6
2007-11-14 11:55:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By tgordon Date 2007-11-27 Time 08:44 Rev Time 0.30
Received By tgordon Date 2007-11-27 Time 14:52 Sent To  
Notes
2007-11-27 15:02:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ELEVATOR PLAN PAGE 4 OF 4 STATES "VENTILATED
 TEMPERATURE CONTROLLED MACHINE ROOM". PLANS DO NOT
 STATE WITH WHAT THE ROOM IS TO BE VENTILATED AND
 TEMPERATURE CONTROLLED. PLEASE SHOW ON PLAN IF THIS IS
 DONE BY AN A/C SYSTEM OR HOW,SHOW ALL DETAIL AND
 PROVIDE ALL INFORMATION. SEE 2004 FBC 3006.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By jleech Date 2007-12-05 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-12-05 Time 07:12 Sent To  
Notes
2007-12-05 07:24:52DENIED;
 SHEET 2 OF 4 FIRST NOTE; IF A DRAIN IS INSTALLED IN THE
 ELEVATOR PIT, IT MUST GO TO A HOLDING TANK, NOT TO
 SANITARY OR STORM. PLEASE EXPLAIN IN DETAIL ON PLANS
 THE METHED OF CONTAINMENT TO BE USED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 15:06 Rev Time 0.00
Received By choops Date 2007-11-28 Time 15:06 Sent To  
Notes
2007-11-28 15:06:49*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved