Plan Review Details - Permit 07110230
Plan Review Stops For Permit 07110230
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-16 Cont ID  
Sent By shill Date 2007-11-16 Time 08:35 Rev Time 0.00
Received By shill Date 2007-11-16 Time 08:35 Sent To  
Notes
2007-11-16 09:07:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE INCLUDE 2007 AMENDMENTS IN GOVERNING CODE
 (EFFECTIVE JULY 1, 2007).
  
 2.LS0G, CODE BRIEF, PLEASE DECLARE OCCUPANCY
 CLASSIFICATIONS AND SUBCLASSIFICATIONS AS APPLICABLE.
 FOR INSTANCE, STORAGE SHOULD BE S1 OR S2.
  
 3.CODE BRIEF, SHEET LS0G, AND OTHER PLACES REFER TO
 STANDARD BUILDING CODE OR SBC.PLEASE REVISE.
  
 4.PLANS STATE THAT THIS IS A NON SEPARATED MIXED USE,
 BUT LS02 AND OTHER PLACES SHOW AN OCCUPANCY SEPARATION.
 PLEASE REVISE.UNTIL COMPLETE PLANS ARE PROVIDED, IT
 IS NOT CLEAR WHETHER OR NOT THE FIRE RATED WALLS ARE
 REQUIRED TO BE MAINTAINED.
  
 5.DECLARE LEVEL OF ALTERATION, FBC CHAPTER 3.
  
 6.SOME OF THE INFORMATION ON THE PLAN IS FOR A
 RENOVATION (SUCH AS FINISHES, PARTITION PLAN ON A01).
 PLEASE BE ADVISED THAT THE APPLICATION IS FOR
 DEMOLITION. THEREFORE, THE NEW WORK SHOWN ON THE PLAN
 WILL BE EXCLUDED FROM THE SCOPE OF WORK FOR THIS
 PERMIT, WILL NOT BE REVIEWED, AND THE DEMO PERMIT WILL
 BE ISSUED WITH A PROVISO THAT CODE COMPLIANCE FOR
 RENOVATIONS WILL BE UNDER SEPARATE PERMIT.
  
 7.THIS IS AN AT RISK PERMIT (DEMO ONLY).
  
 8.LS02 SHOWS A PROPOSED NURSING AND ALF FACILITY.
 ISN'T THIS EXISTING?ALSO, LIFE SAFETY PLANS SUBMITTED
 DO NOT SHOW OCCUPANT LOAD PER AREA, WORST CASE TRAVEL
 DISTANCE, ETC.THIS INFORMATION WILL BE REQUIRED WITH
 THE RENOVATION PERMIT.
  
 9.A01 SHOWS WALL INFILL AT WALL UNITS.PLEASE NOTE
 THAT THIS IS NOT INCLUDED IN THIS DEMO PERMIT, AND A
 DETAIL WILL BE REQUIRED UNDER SEPARATE PERMIT.
  
 10.VALUE APPEARS LOW.PROVIDE A REAONABLE VALUATION
 OR AN ESTIMATE WILL BE DONE USING MARSHALL & SWIFT.
  
 11.PLEASE CONFIRM; THIS PERMIT IS FOR 4TH FLOOR DEMO
 ONLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-19 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 11:50 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By mwennerg Date 2007-11-21 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2007-11-21 Time 13:47 Sent To  
Notes
2007-11-21 13:48:49*DENIED***
  
 1) PLEASE SEE BUILDING COMMENT #6 REGARDING SCOPE OF
 WORK. PLANS SUBMITTED ARE CONFUSING IN REFERENCE TO
 THIS MATTER. APPLICATION INDICATES DEMOLITION OF 4TH
 FLOOR AND OTHER FLOOR RENOVATION DRAWINGS HAVE BEEN
 INCLUDED WITH THIS SUBMITTAL. IF THIS WORK INVOLVES
 PARTIAL FLOOR DEMO, PLEASE INDICATE AND BE SPECIFIC TO
 THE APPLICABLE FLOOR.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By jleech Date 2007-11-29 Time 12:19 Rev Time 0.00
Received By jleech Date 2007-11-09 Time 11:15 Sent To  
Notes
2007-11-15 14:44:32TO "BOB"#2
2007-11-09 11:15:32WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-27 Cont ID  
Sent By tgordon Date 2007-11-27 Time 14:27 Rev Time 0.30
Received By tgordon Date 2007-11-27 Time 14:27 Sent To  
Notes
2007-11-27 14:32:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PERMIT APPLICATION STATES 4TH FLOOR. PLANS SUBMITTED
 STATES 2ND, 3RD, AND 4TH FLOORS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By jleech Date 2007-11-29 Time 12:13 Rev Time 0.00
Received By jleech Date 2007-11-29 Time 12:13 Sent To  
Notes
2007-11-29 12:18:56DENIED;
 PERMIT APPLICATION DISCRIPTION, FOR DEMO. INTERIOR, 4TH
 FL.
 PLANS SHOW 2ND, 3RD, AND FORTH FLOOR DEMO PLAN AND NEW
 WORK.
 PLEASE CORRECT PLANS OR PERMIT APPLICATION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 13:15 Rev Time 0.00
Received By choops Date 2007-11-16 Time 13:15 Sent To  
Notes
2007-11-16 13:16:06*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.