Plan Review Details - Permit 07110219
Plan Review Stops For Permit 07110219
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-10 Cont ID  
Sent By shill Date 2007-12-10 Time 07:30 Rev Time 0.00
Received By shill Date 2007-12-10 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-08 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-02-08 Time 10:22 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-02-05 Cont ID  
Sent By btrobaug Date 2008-02-05 Time 10:34 Rev Time 0.00
Received By btrobaug Date 2008-02-05 Time 09:23 Sent To P
Notes
2008-02-05 09:48:45 
  
  
 APPLICATION #07110219
 ELECTRICAL PLAN REVIEW
 218 ALMERIA ROAD
 2/5/08
 WEST PALM BEACH, FL.
  
 THESE ARE REPEAT COMMENTS FROM THE 11/29/07 REVIEW,
 THAT PREVIOUSLY WERE RESPONDED TO. NOW REAPPEAR WITH
 THE LAST RESUBMITTAL. SEE ASTERISK FOR FURTHER
 COMMENT.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225, 250 AND 230 CAN BE REVIEWED. *THE SITE
 PLAN SP1, INDICATES "125 AMPBOX", SHEET E3 INDICATES
 ALL PANELS ARE 100 AMP. CORRELATE THE DRAWINGS TO
 REFLECT THE PROPOSED EQUIPMENT , LABEL AND LOCATE
 SAME.
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC. * THECALCULATION FOR
 THAT PANEL WERE NOT RESUBMITTED.WITH THE 1/10/08
 RESUBMITTAL.
  
 3} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL.
 106.3.5.4 FBC AS AMENDED.* THIS SCHEDULE WAS NOT
 RESUBMITTED.WITH THE 1/10/08 RESUBMITTAL
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.* THOSE SPECIFICATIONS HAVE BEEN SUBMITTED
 INDICATING A 18" SETBACK. THE NOTE ON SP1 INDICATES
 "GENERATOR 13" FROM HOUSE", WHICH IS WHAT GENERATED
 THIS COMMENT ORIGINALLY.
  
 6} THERE ARE REFERENCES TO "8/0 AND 12/0" CONDUCTORS ON
 THE RISER DIAGRAM. THESE ARE NOT LISTED AWG SIZES.* THE
 "8/0" GROUND APPEARS IN ALL FEEDS, SHEET E3.ALSO NOTE
 THE 3/0 FEEDERS, ALL PANELS, FOR A 100 AMP PANEL.
 INDICATE WHAT THE NOTE "1-1/4"C. #4GROUNDING ELECTRODE
 CONDUCTOR" IS IN REFERENCE TO, SITE ARTICLE TO
 REFERENCE HE INTENT OF THAT NOTE.
  
 7} THERE IS A "GROUNDING ELECTRODE CONDUCTOR" (250.66,
 SEE DEFINITION) IN THE FEED FROM THE TRANSFER SWITCH TO
 THE EM PANEL, AND ALL PANELS FED FROM THE MAIN. THIS
 SHOULD BE AN EQUIPMENT GROUNDING CONDUCTOR (250.122),
 AND SHOULD BE SIZED TO INDICATE COMPLIANCE. SEE
 PREVIOUS COMMENT, SAME CONDITION STILL EXISTS.
  
 PLEASE CHECK ALL DOCUMENTS ARE CORRECTED AND PRESENT IN
 THE PACKAGE THAT IS RESUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 14:14 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 12:25 Sent To P
Notes
2008-01-24 14:14:35 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT WAS FROM THE PREVIOUS TWO REVIEW.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.NOTE: HAVE NEVER SEEN GENERAC SPECIFY
 ANYTING LESS THAN18".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By btrobaug Date 2008-01-11 Time 10:49 Rev Time 0.00
Received By btrobaug Date 2008-01-11 Time 10:27 Sent To P
Notes
2008-01-11 10:47:11 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
  
 THIS COMMENT WAS FROM THE PREVIOUS REVIEW.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 13:23 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 12:47 Sent To M
Notes
2007-11-29 13:23:32 
  
 APPLICATION #07110219
 ELECTRICAL PLAN REVIEW
 218 ALMERIA ROAD
 11/29/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225, 250 AND 230 CAN BE REVIEWED.
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC
  
 3} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL.
 106.3.5.4 FBC AS AMENDED.
  
 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 6} THERE ARE REFERENCES TO ?8/0 AND 12/0? CONDUCTORS ON
 THE RISER DIAGRAM. THESE ARE NOT LISTED AWG SIZES.
  
 7} THERE IS A ?GROUNDING ELECTRODE CONDUCTOR? (250.66,
 SEE DEFINITION) IN THE FEED FROM THE TRANSFER SWITCH TO
 THE EM PANEL, AND ALL PANELS FED FROM THE MAIN. THIS
 SHOULD BE AN EQUIPMENT GROUNDING CONDUCTOR (250.122),
 AND SHOULD BE SIZED TO INDICATE COMPLIANCE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-02-08 Cont ID  
Sent By mperson Date 2008-02-08 Time 13:49 Rev Time 0.00
Received By mperson Date 2008-02-08 Time 13:49 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 11:58 Rev Time 0.00
Received By mperson Date 2008-02-05 Time 11:58 Sent To PC
Notes
2008-02-05 13:05:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 4TH TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 **PREVIOUS COMMENTS**
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **OK** COMMENT ADDRESSED
  
 5. **OK** COMMENT ADDRESSED.
  
 6. **NO, COMMENT NOT ADDRESSED
 **OK** COMMENT ADDRESSED, HOWEVER THE GAS PLANS FOR
 THE GENERATOR ARE TO BE SUBMITTED SEPERATELY AS A
 REVISION TO GAS PERMIT NUMBER 07020476 WITH FEES PAID
 AND SUBMITTED WITH THE GENERATOR PERMIT.
  
 ****UNTIL GAS PLANS ARE SUBMITTED AS A REVISION TO GAS
 PERMIT #07020476 WITH REVISION FEES PAID AS REQUSTED IN
 THE PREVIOUS PLAN REVIEW DATED 1/25/08, THERE WILL NOT
 BE A GAS PLAN REVIEW. ALSO PLEASE REFERENCE A COPY OF
 THE NOTARIZED LETTER FROM "GUARANTEED PLUMBING INC."
 CLOSING OUT GAS PERMIT #07110221 ATTACHED TO THESE
 COMMENTS INDICATING THE NEED FOR THE GAS BE SUBMITTED
 AS A REVISION.
  
 7. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-01-25 Cont ID  
Sent By mperson Date 2008-01-25 Time 11:16 Rev Time 0.00
Received By mperson Date 2008-01-25 Time 11:16 Sent To PC
Notes
2008-01-25 11:17:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 **PREVIOUS COMMENTS**
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **NO** COMMENT NOTED HOWEVER.
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 **THERE WERE NO MANUFACTURER'S SPECIFICATIONS
 SUBMITTED FOR THE PROPOSED GENERATOR INDICATING
 RECOMMENDED SETBACKS FROM STRUCTURES.
  
 ***NOTE: REFERENCE THE GENERAC "NEW INSTALLATION
 GUIDELINES FOR GENERAC STATIONARY GENERATORS" ATTACHED
 TO THE GAS COMMENTS THAT STATES GENERATOR AT A MINIMUM
 IS 18" AND COMPLY.
  
 5. **OK** COMMENT ADDRESSED.
  
 6. **OK** COMMENT ADDRESSED, HOWEVER THE GAS PLANS FOR
 THE GENERATOR ARE TO BE SUBMITTED SEPERATELY AS A
 REVISION TO GAS PERMIT NUMBER 07020476 WITH FEES PAID
 AND SUBMITTED WITH THE GENERATOR PERMIT.
  
 7. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-01-14 Cont ID  
Sent By mperson Date 2008-01-14 Time 13:59 Rev Time 0.00
Received By mperson Date 2008-01-14 Time 13:59 Sent To PC
Notes
2008-01-14 14:45:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 **PREVIOUS COMMENTS**
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **NO** COMMENT NOTED HOWEVER.
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 **THERE WERE NO MANUFACTURER'S SPECIFICATIONS
 SUBMITTED FOR THE PROPOSED GENERATOR INDICATING
 RECOMMENDED SETBACKS FROM STRUCTURES.
  
 5. **OK** COMMENT ADDRESSED.
  
 6. **NO** COMMENT NOTED HOWEVER.
 NOTE: THERE IS AN OPEN GAS PERMIT #07020467 PRINTED FOR
 THIS ADDRESS FOR "GUARANTEED PLUMBING INC.". PLEASE
 CLARIFY WHY THE SUBMITTED GAS FOR THE GENERATOR WAS NOT
 SUBMITTED AS A REVISION TO THAT PERMIT. IS IT THE
 INTENT TO VOID OUT THAT PERMIT? PLEASE SUBMIT AN
 ORIGINAL NOTARIZED LETTER BY SAID CONTRACTOR INDICATING
 WHICH PERMIT IS TO BE VOIDED.
  
 **NOTE: UNTIL A NOTARIZED LETTER FROM SAID CONTRACTOR
 IS SUBMITTED INDICATING WHICH GAS PERMIT IS TO BE
 VOIDED THE GENERATOR PERMIT WILL NOT BE PRINTED.
  
 7. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By mperson Date 2007-12-04 Time 10:51 Rev Time 0.00
Received By mperson Date 2007-12-04 Time 10:51 Sent To B
Notes
2007-12-04 11:32:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PER THE SUBMITTED MANUFACTURER'S SPECIFICATION
 SHEETS THE GENERATOR BTU'S ARE INDICATED WRONG AS
 107,000. THE CORRECT BTU LOAD FOR THE GENERATOR IS
 315,000. PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 2. THE TOTAL BTU'S FOR THE GAS SYSTEM ARE BEING
 INDICATED WRONG AS 207,000. THE CORRECT TOTAL BTU LOAD
 FOR THE GAS SYSTEM IS 415,000. PLEASE CORRECT THIS ON
 THE RESUBMITTAL.
  
 3. PER FUEL GAS TABLE 402.4(2) THE SCHEDULE 40
 METALLIC PIPE NEEDS TO BE INCREASED FROM 1" TO 1-1/4"
 FROM THE METER TO THE GENERATOR. PLEASE CORRECT THIS ON
 THE RESUBMITTAL.
  
 4. PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 5. CLEARLY INDICATE THE GENERATORS LOCATION ON A SITE
 PLAN OR SURVEY INDICATING DIMENSIONS FROM PROPERTY
 LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
  
 6. NOTE: THERE IS AN OPEN GAS PERMIT #07020476 PRINTED
 FOR THIS ADDRESS BY GUARANTEED PLUMBING INC.. PLEASE
 CLARIFY WHY THE SUBMITTED GAS FOR THE GENERATOR WAS NOT
 SUBMITTED AS A REVISION TO THAT PERMIT. IS IT THE
 INTENT TO VOID OUT THAT PERMIT? PLEASE SUBMIT AN
 ORIGINAL NOTARIZED LETTER BY SAID CONTRACTOR INDICATING
 WHICH PERMIT IS TO BE VOIDED.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 08:54 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 08:54 Sent To E
Notes
2008-02-07 08:55:14TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 16:22 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 16:22 Sent To E
Notes
2008-01-15 16:22:44TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 16:03 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 16:03 Sent To E
Notes
2008-01-10 16:03:42SENT TO BT'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By shill Date 2007-12-10 Time 07:30 Rev Time 0.00
Received By shill Date 2007-11-09 Time 08:31 Sent To  
Notes
2007-11-09 08:32:06TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 12:07 Rev Time 0.25
Received By tgordon Date 2007-11-30 Time 12:07 Sent To G
Notes
2007-11-30 12:10:24*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 13:35 Rev Time 0.00
Received By choops Date 2007-11-14 Time 13:35 Sent To E
Notes
2007-11-14 13:35:54***APPROVED***
  
  
 SENT TO "E" - GEN. BOX