Plan Review Details - Permit 07110196
Plan Review Stops For Permit 07110196
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-07-20 Cont ID  
Sent By jgomez Date 2010-07-20 Time 15:48 Rev Time 0.00
Received By jgomez Date 2010-07-20 Time 15:48 Sent To  
Notes
2010-07-20 15:57:14NEW GARAGE FLAT ROOF PRODUCT APPROVAL SUBMITTED UNDER
 PERMIT NUMBER 10070494.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-18 Cont ID  
Sent By jgomez Date 2008-08-18 Time 14:03 Rev Time 0.00
Received By jgomez Date 2008-08-18 Time 09:30 Sent To PC
Notes
2008-08-18 14:13:40BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- FLAT ROOF SYSTEM:
 A) SPECIFYWHICH APPROVED ASSEMBLY OF NA 08-0512.06
 IS GOING TO BE USED.
 B) ON SELECTED ASSEMBLY SPECIFY WHICHBASE SHEET
 FASTENING OPTION IS GOING TO BE USED.COORDINATE WITH
 THE RAS 117 C CALCULATIONS SUBMITTED.
 C) ENGINEERWHO PERFORMED THE RAS 117 CALCULATIONS
 NEEDS TO PROVIDE ALL HIS INFORMATION AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
 D) RAS 117 CALCULATIONS SUBMITTED: CLARIFY WHERE IS
 SECTION 10.4 FBC 2004 TAKEN FROM?
  
 2- ENERGY CALCULATIONS FOR GARAGE BUILDING:
 A) SUBMITREVISED FORM 600C-04R.
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 C) COMPLETE ALL INFORMATION ON BACK OF FORM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-18 Cont ID  
Sent By jgomez Date 2008-06-24 Time 13:20 Rev Time 0.00
Received By jgomez Date 2008-06-24 Time 13:19 Sent To PC
Notes
2008-06-24 13:20:54BUILDING REVIEW APPROVED WITH PROVISO:
 1-VERIFY THAT 5'-0" SPIRAL STAIRS IS INSTALLED.
 2- SOIL TEST REPORT STATESSOILBEARING CAPACITY OF
 2,000PSF.ENGINEER OF RECORD REQUIRES 2,500 PSF SOIL
 BEARING CAPACITY. SEE FOUNDATION NOTES ON SHEET S-5.
 REVISE AS REQUIRED.
 3- PROVIDE COMPLETE PRODUCT APPROVAL FOR UNDERLAYMENT
 USED IN BALCONY ASSEMBLY.SEE SHEET A3.4.
 4- PROVIDE PRODUCT APPROVAL FOR FLAT ROOF IF DOING ANY
 FLAT ROOF RE-ROOFING. SEE SHEET A2.2..
 5- REVISE ENERGY CALCULATIONS FOR GARAGE BUILDINGTO
 SHOWR-VALUE INSULATION ON WALLS AND CEILINGS. SEE
 ARCHITECTURAL DRAWINGS.
 6- TRUSS PACKAGE TO HAVE NAME OF ENGINEER OF RECORD ON
 INDEX SHEET AS REQUIRED BYSEC. 61G15-31.003(5).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-25 Cont ID  
Sent By jgomez Date 2008-04-25 Time 18:52 Rev Time 0.00
Received By jgomez Date 2008-04-25 Time 17:28 Sent To PC
Notes
2008-04-25 19:00:54RESIDENTIAL (R3) ADDITION AND ALTERATION, BUILDING
 REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP
 TO AVOID EXPIRATION OF DOCUMENT.
  
 2- NEED TO PROVIDE COPY OF IMPACT FEES PAID RECEIPT.
 (REPEAT COMMENT).ONLY PLANS WITH IMPACT FEES STAMP
 WAS SUBMITTED THIS TIME.NEED TO PROVIDE BOTH.
  
 3-ACCORDING TOSPIRAL STAIRS INFORMATION SUBMITTED,
 ONLY 5'-0" DIAMETER STAIRS OR LARGER COMPLY WITH THE
 MINIMUM REQUIREMENTS.ARCHITECTURAL PLANS SHOW 4'-9"
 DIAMETER FOR STAIR OPENING. PLANS NEED TO BE REVISED AS
 REQUIRED TO ACCOMMODATEMIN. 5'-0" DIAMETER STAIRS. TO
 COMPLY WITH SEC. R311.5.8.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 SPECIFY TOTAL NUMBER OF RAISERS REQUIRED TO VERIFY
 COMPLIANCE WITH MAXIMUM RISER HEIGHT.
  
 4- PROVIDE COMPLETE DETAILS/SPECS FOR ORNAMENTAL
 GUARDRAIL TO VERIFY COMPLIANCE WITH TABLE R301.5 AND
 SEC. R312.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTEDFROM RAILING WORKS IS ONLYFOR
 GENERALINFORMATION AND DOESN'T PROVIDEINFORMATION
 FOR ACTUAL PROPOSED ORNAMENTAL RAILING.
  
 5- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) POLYFOAM USED FOR ROOF TILE. (REPEAT COMMENT).
 SEE ROOF TILE PRODUCT APPROVAL FOR LISTED POLYFOAM.
  
 B) FLAT ROOF: NEED TO SPECIFY WHICH APPROVED
 ASSEMBLY AND SPECIFIC FASTENING OPTION IS GOING TO BE
 USED. ALSO, NEED TO PROVIDE THE RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7.SEE GENERAL
 LIMITATIONS ON LAST PAGE OF NOA 07-0111.03 SUBMITTED.
 (REPEAT COMMENT).
  
 C) ARCHED DOORS AS SHOWN ON GARAGE EXTERIOR
 ELEVATIONS. (REPEAT COMMENT).
  
 D) DOUBLE HUNG WINDOWS.MARVIN WINDOWS AND DOORS
 FLORIDA PRODUCT APPROVAL FL4765-R0 IS MISSING THE
 DRAWINGS SHOWING THE WINDOWS.PROVIDE COMPLETE
 DRAWINGS.
  
 E) MULLIONS. CLEARLY MARK SPECIFIC MULLION SIZE AND
 ANCHORING TO BE USED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 ***NOTE:THERE ARE PRODUCT APPROVALSFOR DOORS AND
 WINDOWS FROM PGT AND FROM MARVIN WINDOWS AND DOORS.
 PROVIDE ONLY THE PRODUCTAPPROVALFOR SPECIFIC
 PRODUCT THAT IS GOING TO BE INSTALLED.PGT OR MARVIN.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. SOME PRODUCT APPROVALS ARE
 MISSING THE ARCHITECT'S REVIEW STAMP.
  
 7- PROVIDE COMPLETE SPECIFICATIONS FOR RAISED WOOD
 FLOOR IN GARAGE AREAAND RAISED WOOD FLOOR IN NEW
 ADDITION AREA TO SHOW COMPLIANCE WITH SECTIONS R319
 (PROTECTION AGAINST DECAY)AND SEC. R408.1 THRU
 R408.3 OF 2004 FLORIDA RESIDENTIAL CODE (UNDER-FLOOR
 SPACE VENTILATION AND ACCESS).(REPEAT COMMENT). THERE
 ARE NO SPECS PROVIDED TO SHOW COMPLIANCE WITH SEC.
 R319. AND, LOCATION OF VENTILATION OPENINGSNEED TO BE
 BETWEEN 3' OF EACH CORNER AS REQUIRED BY SEC. R408.1.
 REVISEPLANS AS REQUIRED.
  
 8- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 B) COMPLETE INFORMATION ON TOP OF FORM. (REPEAT
 COMMENT).
  
 9-SOIL TEST REPORT SHOWS SOIL BEARING CAPACITY OF
 2000 PSF AND RECOMMENDS MINIMUM FOOTING WIDTH OF 24".
 STRUCTURAL PLANS REQUIRE 2500PSF SOIL BEARING CAPACITY
 AND FOOTING WIDTH IS LESS THAN THE ONE RECOMMENDED ON
 THE SOIL TEST REPORT.STRUCTURAL ENGINEER TO
 COORDINATEWITH GEO-TECHNICAL ENGINEER AND REVISE
 EITHER ONE THE SOIL TEST REPORT OR STRUCTURAL DRAWINGS
 AS REQUIRED.
  
 10- SHEET A5.0:REVISE NAIL TYPETO BE USED FOR ROOF
 SHEATHING ON DETAIL #18.SEC. R803.2.3.1 REQUIRES MIN.
 8D RING SHANK NAILS. REVISE AS REQUIRED.
  
 11- SHEET A6: REVISE INSULATION SPECIFICATIONS ON ALL
 WALL ASSEMBLIES SHOWN ON THE WALL SCHEDULE. COORDINATE
 WITH THE ENERGY CALCULATIONS AND REVISE AS REQUIRED.
 (REPEAT COMMENT).
  
 12- SHEET S-4:REVISE ALL INFORMATION ON DETAIL C
 REGARDING THE ROOF SHEATHING FASTENER TYPE AND SPACING.
 SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL AND
 SPACING REQUIRED INCLUDING ON ROOF ZONE #3.
  
 13- TRUSS PACKAGE:
 A) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE
 TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 B) TRUSS DRAWINGS NEED TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY SEC. 61G15-23.002 FLORIDA
 STATUTE. AND CHAPTER 472 FLORIDA STATUTE.
  
 C) TRUSS COVER SHEET IS MISSING THE INFORMATION
 REGARDING THE ENGINEER OF RECORD. PROVIDE THIS
 INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By jgomez Date 2007-11-19 Time 15:27 Rev Time 0.00
Received By jgomez Date 2007-11-19 Time 15:26 Sent To P
Notes
2007-11-19 15:30:14RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3-A) NEW ADDITION NEEDS TO COMPLY WITH SEC. R302.1
 AND R302.2 OF 2004 FLORIDA RESIDENTIAL CODE REGARDING
 WALL FIRE RATING, ROOF PROJECTIONS AND NO OPENINGS
 ALLOWED ON EAST WALL.
  
 B) SAME COMMENT APPLIES TO GARAGE RENOVATION AND
 ALTERATION ON WEST WALL.
  
 4- PROVIDE SPECIFICATIONS FOR GARAGE SWING DOOR LEADING
 TO THE WORKROOM AREA FOR COMPLIANCE WITH SEC. R309.1 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 5- PROVIDE DETAILS/SPECS FOR SPIRAL STAIRS SHOWING
 COMPLIANCE WITHSEC. R311.5.8.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 NOTE: ATTACHMENT METHOD MUST MEET THE DESIGNER'S
 CALCULATED UPLIFT MOMENT. SEE PRODUCT APPROVAL.
  
 7- PROVIDE COMPLETE DETAILS/SPECS FOR ORNAMENTAL
 GUARDRAIL TO VERIFY COMPLIANCE WITH TABLE R301.5 AND
 SEC. R312.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ROOF TILE.
  
 B) ROOF TILE ADHESIVE IFSPECIFIED BY THE DESIGNER
 OF RECORD ON ITEM 6 ABOVE. SEE TILE PRODUCT APPROVAL
 FOR SPECIFICADHESIVE TO BE USED.
  
 C) FLAT ROOF. AND, CLEARLY SPECIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED.IF MORE THAN ONE
 FASTENING OPTION IS LISTED IN THE SELECTED APPROVED
 ASSEMBLY, THEN SPECIFY SELECTED FASTENING OPTION. ALSO,
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT THE
 PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7
 ON PRODUCT APPROVAL.IF CALCULATIONS NEED TO BE DONE
 AND SEALED BY ARCHITECT OR ENGINEER, THEN PROVIDE SUCH
 CALCULATIONS.
  
 D) ARCHED DOORSAS SHOWN ON EXTERIOR ELEVATIONS.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10- PROVIDE COMPLETE SPECIFICATIONS FOR RAISED WOOD
 FLOOR IN GARAGE AREA AND RAISED WOOD FLOOR IN NEW
 ADDITION AREA TO SHOW COMPLIANCE WITH SECTIONS R319
 (PROTECTION AGAINST DECAY),AND SEC. R408.1 THRU
 R408.3 OF 2004 FLORIDA RESIDENTIAL CODE (UNDER-FLOOR
 SPACE VENTILATION AND ACCESS).
  
 11- ENERGY CALCULATIONS:
 A) PROVIDE SEPARATE ENERGY CALCULATIONS FOR GARAGE
 AND FOR NEW ADDITION AS REQUIRED BY SEC. 13-101.2.5.1
 FBC 2004.
 NOTE: MAKE SURE CORRESPONDING A/C AREA IS USED FOR EACH
 BUILDING.
  
 B) NEED TO USE REVISED FORM 600A-200R.
  
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 D) MAKE SURE CORRECT OVERHANG HEIGHT AND LENGTH IS
 USED. SEE ARCHITECTURAL PLANS AND REVISE AS REQUIRED.
  
 E) MAKE SURE CORRECT R-VALUES AE SHOWN FOR EXTERIOR
 WALLS. SEE SEC. 13-602.1.ABC.1 OF FBC 2004.
  
 12- PROVIDE SOIL TEST REPORT.TWO COPIES. SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
 NOTE: PLEASE MAKE SURE SOIL TEST REPORT HAS ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AND ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IS PROVIDED AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE TO AVOID DELAYS.
  
 13- SHEET A3.2: WALL SECTIONS CALLS FOR NEW 3/4" STUCCO
 ON PLAYWOOD ON METAL STUD FRAMED WALLS, WHILE
 STRUCTURAL DRAWINGS CALL FOR WOOD FRAMING. REVISE AS
 REQUIRED.
 NOTE: THIS COMMENT APPLIES TO WALL SECTIONS ON SHEETS
 A3.3,A3.4AND A3.5ALSO.
 REVISE AS REQUIRED.
  
 14- SHEET A3.4:PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF 1" BRICK PAVERS SET ON FLOATING WOOD
 DECK IN BALCONY.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 IN REFERENCE TO WIND LOADS SEC. R301 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 15- SHEET A5.0: PROVIDECOMPLETE SPECIFICATION FOR ALL
 FASTENERS TO BE USED ON SECTION/DETAIL 18 FOR CANOPY
 INSTALLATION.
  
 16- SHEET A6.0:REVISE INSULATION SPECIFICATIONS ON
 ALL WALL ASSEMBLIES SHOWN ON THE WALL SCHEDULE.
 COORDINATE WITH ENERGY CALCULATIONS AND REVISE AS
 REQUIRED.
  
 17- SHEET S-4:
 A) REVISE LOCATION OF ZONE 3 SHOWN ON DETAILB. SEE
 FIGURE 6-11C OF ASCE 7-02AND REVISE AS REQUIRED.
  
 B) DETAIL C : INFORMATION FOR ZONE 1,2 & 3 DOESN'T
 MATCH INFORMATION SHOWN BY 2X4 BLOCKING. ALSO, SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR MINIMUM
 TYPE OF NAIL AND NAIL SPACING TO BE USED, INCLUDING
 NAIL SPACING IN ZONE 3 AREAS. REVISE ALL INFORMATION ON
 THIS DETAIL AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-18 Cont ID  
Sent By btrobaug Date 2008-04-18 Time 09:58 Rev Time 0.00
Received By btrobaug Date 2008-01-31 Time 07:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By btrobaug Date 2007-11-14 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2007-11-14 Time 12:13 Sent To M
Notes
2007-11-14 16:20:37 
  
 APPLICATION #07110196
 ELECTRICAL PLAN REVIEW
 711 CLAREMORE DRIVE
 11/14/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} REFERENCING THE RISER DIAGRAM FOR THE HOUSE SUBPANEL
 ON SHEET E3, THE FEEDER TO THAT PANEL MUST HAVE AN
 EQUIPMENT GROUND (#8 MINIMUM) PER 250.122.
  
 2} THE HOUSE SUBPANEL CANNOT BE LOCATED IN THE BATHROOM
 AS INDICATED ON SHEET E1, 1ST FLOOR ELECTRICAL PLAN.
 SEE ARTICLE 240.24(E).
  
 3} SHEET E2, THE RISER FOR THE CABANA INDICATES THAT
 SERVICE IS EXISTING, THE CABANA PANELBOARD INDICATES
 ?NEW?. CLARIFY IF NEW OR EXISTING, INDICATE THE
 GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66, MINIMUM
 #6.
  
 4} THE 1? CONDUIT CONTAINING 3#1/0 CONDUCTORS FOR THE
 CABANA PANEL FEED IS IN VIOLATION OF THE CONDUIT FILL
 REQUIREMENTS. SEE ANNEX ?C? OR CALCULATE FROM TABLE
 #8.
  
 5} THE CABANA PANEL LOCATION APPEARS NOT TO HAVE THE 3?
 CLEARANCE REQUIRED PER 110.26. PLEASE VERIFY.
  
 6} THE LOAD CALCULATIONS ARE NOT PER 220.82 OR 220.83
 AS THEY SHOULD BE FOR AN EXISTING RESIDENCE. THERE ARE
 LOADS ON THE PANEL SCHEDULES NOT PART OF THE
 CALCULATIONS IG; WARMER, WATER HEATER, RANGE IN PANEL
 ?H?.ALSO THERE ARE LOADS FROM THE CABANA SERVICE
 LISTED IN THE HOUSE SERVICE CALCULATIONS. THESE
 SERVICES MUST BE CALCULATED AND LISTED SEPARATELY AS
 THEY ARE FROM SEPARATE SERVICES NOT SEPARATE PANELS ON
 THE SAME SERVICE.
  
 7} REGARDING THE CABANA FLOOR PLAN SHEET E1, LOCATE THE
 WASHER AND DRYER LISTED ON THE PANEL SCHEDULE.
  
 8} THE BATHROOM IN THE CABANA IS REQUIRED TO HAVE A
 CIRCUIT FOR THE RECEPTACLE SEPARATE PER 210 52(D). IT
 IS ON WITH OTHER RECEPTACLES OUTSIDE OF THAT ROOM.
  
 9} THE LOFT BATHROOM MUST COMPLY WITH 210.52(D)
 RECEPTACLE REQUIREMENT.
  
 10} THE LAUNDRY OFF THE MASTER BEDROOM MUST COMPLY WITH
 210.11(C)(2), LAUNDRY BRANCH CIRCUIT. PANEL MUST BE
 LABELED INDICATING SAME PER 408.4.
  
 11} ALL BEDROOM OUTLETS MUST COMPLY WITH 210.12 ARC
 FAULT PROTECTED. INDICATE IN THE PANELS.
  
 12} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 LOCATIONS OF REQUIRED ALARMS ON THE PLANS AND NOTE THE
 REQUIREMENT FOR INTERCONNECTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-01-29 Cont ID  
Sent By ssherman Date 2008-01-29 Time 10:53 Rev Time 0.00
Received By ssherman Date 2008-01-29 Time 10:53 Sent To  
Notes
2008-01-29 10:54:04HISTORICAL APPROVAL PER FRIEDERIKE MITTNER
2007-11-08 10:22:30NO HISTORIC FEE & OK PER G JUDGE 11-8-07

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 15:28 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 15:28 Sent To M
Notes
2008-08-14 15:29:16TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 13:23 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 13:23 Sent To M
Notes
2008-06-13 13:23:29TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 13:45 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 13:45 Sent To E
Notes
2008-04-16 13:45:27TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 14:18 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 14:18 Sent To Z
Notes
2008-01-29 14:18:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-27 Cont ID  
Sent By jleech Date 2007-11-27 Time 15:05 Rev Time 0.00
Received By jleech Date 2007-11-08 Time 14:07 Sent To  
Notes
2007-11-08 14:07:38TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-15 Cont ID  
Sent By tgordon Date 2008-08-15 Time 10:19 Rev Time 1.30
Received By tgordon Date 2008-08-15 Time 10:19 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-06-16 Cont ID  
Sent By tgordon Date 2008-06-16 Time 10:15 Rev Time 0.45
Received By tgordon Date 2008-06-16 Time 10:15 Sent To B
Notes
2008-06-16 10:17:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) 2) AS NOTED IN LAST TWO REVIEWS 11/15/07 AND 4/18/08
 NOTE #2. PROVIDE FOR RETURN AIR FOR THE NEW LOFT, SEE
 2004 FBC/R M1602.2. ENGINEERS RESPONSE WAS, THE STAIR
 TO THE LOFT IS OPEN AT THE CEILING ETC. PLEASE SEE THAT
 THE STAIR TO THE LOFT IS CLOSED OFF AT THE BOTTOM FROM
 THE RETURN AIR GRILL IN THE MASTER BEDROOM BY A WALL
 AND A DOOR SO RETURN AIR CAN NOT RETURN TO THE AIR
 HANDLER. PLEASE CORRECT.
  
 2) MECHANICAL PLAN M1 NOW SHOWS 6"X6" METAL CURB
 (SLEEPERS) AND PLAN A5.0 DETAIL 19, SHOWS 8" METAL CURB
 (SLEEPERS). PER 2004 FBC TABLE 1509.7 CLEARANCE BELOW
 RAISED ROOF MOUNTED MECHANICAL UNITS. THE MINIMUM
 CLEARANCE ABOVE ROOF SURFACES IS 14" PLEASE CHECK THE
 TABLE AS THE UNIT YOU ARE INSTALLING MAY REQUIRE MORE
 CLEARANCE. SEE 2004 FBC/R M1301.1, FBC/M 306.5, AND
 FBC1509.7. PLEASE CORRECT.
  
 3)AS NOTED IN LAST TWO REVIEWS 11/15/07 AND 4/18/08
 NOTE #4. PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED A/C CONDENSER STANDS (IF USED), SEE FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL
 (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-04-18 Cont ID  
Sent By tgordon Date 2008-04-18 Time 10:33 Rev Time 0.30
Received By tgordon Date 2008-04-18 Time 10:33 Sent To P
Notes
2008-04-18 10:49:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 11/15/07 NOTE #1. PLEASE
 SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS) SEE 2004 FBC 13-607.1.ABC.1. ONE SET OF
 THE ENERGY CALCULATIONS FOR THE CABANA HAS A ONE SHEET
 SUMMARY SHEET '?' SEE THE EXCEPTION TO 13-607.1.ABC.1.
  
 2) AS NOTED IN LAST REVIEW 11/15/07 NOTE #2. PROVIDE
 FOR RETURN AIR FOR THE NEW LOFT, SEE 2004 FBC/R
 M1602.2.
  
 3)AS NOTED IN LAST REVIEW 11/15/07 NOTE #3. PLAN M4
 CONDENSER UNIT ROOF DETAIL, SHOWS A 6'X6' P.T. SLEEPER.
 PER 2004 FBC/M 301.13 THE USE OF WOOD SLEEPERS SHALL
 NOT BE PERMITTED. PLEASE CORRECT.
  
 4)AS NOTED IN LAST REVIEW 11/15/07 NOTE #4. PLEASE
 SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED
 A/C CONDENSER STANDS (IF USED), SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 5) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL
 (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT).
  
 **** UNDER 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A
 SUMMARY SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED
 BY THE ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-15 Cont ID  
Sent By btrobaug Date 2008-01-31 Time 09:00 Rev Time 0.40
Received By tgordon Date 2007-11-15 Time 14:15 Sent To P
Notes
2007-11-15 14:50:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS) SEE 2004 FBC 13-607.1.ABC.1.
  
 2) PROVIDE FOR RETURN AIR FOR THE NEW LOFT, SEE 2004
 FBC/R M1602.2.
  
 3) PLAN M4 CONDENSER UNIT ROOF DETAIL, SHOWS A 6'X6'
 P.T. SLEEPER. PER 2004 FBC/M 301.13 THE USE OF WOOD
 SLEEPERS SHALL NOT BE PERMITTED. PLEASE CORRECT.
  
 4) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED A/C CONDENSER STANDS (IF USED), SEE FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL
 (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-21 Cont ID  
Sent By jleech Date 2008-04-21 Time 08:52 Rev Time 0.00
Received By jleech Date 2008-04-21 Time 07:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-27 Cont ID  
Sent By jleech Date 2007-11-27 Time 14:55 Rev Time 0.00
Received By jleech Date 2007-11-27 Time 14:55 Sent To  
Notes
2007-11-27 15:05:25DENIED;
 1. CABANA SANITARY RISER DIAGRAM; THE SINK SHALL
 DISCHARGE DOWN STREAM OF THE BATHROOM GROUP. SEE FBC
 PLUMBING SECTION 909.1.
 2. 1ST FLOOR SANITARY RISER DIAGRAM; THE AUTOMATIC
 CLOTHES WASHER SHALL DISCHARGE INTO A 3"BRANCH DRAIN.
 SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-30 Cont ID  
Sent By choops Date 2008-01-30 Time 16:21 Rev Time 0.00
Received By choops Date 2008-01-30 Time 16:21 Sent To E
Notes
2008-01-30 16:28:21***APPROVED - RESUB #1***
  
 PROVISO:1) HEIGHT OF PROPOSED ADDITION SHALL NOT
 EXCEED 30', MEASURED FROM GRADE TO THE MIDPOINT OF THE
 ROOF'S PITCH. 2) AS THE EXISTING ACCESSORY GARAGE
 STRUCTURE IS DIMENSIONALLY NONCONFORMING WITH RESPECT
 TO ITS SETBACKS FROM THE WEST SIDE AND REAR PROPERTY
 LINES, THOSE NONCONFORMITIES SHALL NOT BE INCREASED NOR
 SHALL ANY NEW NONCONFORMITIES BE CREATED.3) ROOF
 OVERHANGS SHALL NOT PROJECT INTO ANY REQUIRED SETBACK
 MORE THAN 3'.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-08 Cont ID  
Sent By choops Date 2007-11-08 Time 16:01 Rev Time 0.00
Received By choops Date 2007-11-08 Time 16:01 Sent To E
Notes
2007-11-08 16:02:58***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF AN UPDATED SURVEY
 (WITHIN THE LAST YEAR)
  
 2)INDICATE HEIGHT OF PROPOSED ADDITION ON ELEVATIONS
 FROM GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720