Plan Review Details - Permit 07110158
Plan Review Stops For Permit 07110158
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By rmcdouga Date 2008-01-11 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2008-01-10 Time 12:21 Sent To  
Notes
2008-01-10 12:19:222004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1)SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) THE DESIGN PARAMETERS ON SHEET 4.1 SPECIFIES THE
 WIND EXPOSURE CATEGORY AS C AND THE COMPONENT AND
 CLADDING TABLE PRESSURES ON SHEET 7 ARE FOR EXPOSURE B.
 PLEASE CORRECT. SEE FBC R301.2.1.4 AND TABLE
 R301.2(2).
  
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) ON SHEET 6.1, NUMBER 22 ON THE CONNECTOR SCHEDULE IS
 SPECIFIED AS A SIMPSON LUS 10. IS THIS SUPPOSE TO BE A
 LUS 210? PLEASE CLARIFY. THERE IS NO SIMPSON LUS 10
 CONNECTOR. THE UPLIFT AND NUMBER OF NAILS CORRESPONDS
 WITH A SIMPSON LUS 210. HOWEVER, THE FL # FOR THE LUS
 CONNECTOR IS FL 3750.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) SPECIFY THE LINTELS ABOVE THE SECOND FLOOR WINDOWS.
 SEE FBC* 106.1.1 CITY AMENDMENTS.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS THAT
 HAVE BEEN SIGNED AND DATED BY THE OWNER/AGENT AS
 REQUIRED BY FBC CHAPTER 13.101.2.
  
 18) THE ENERGY CALC. FORM LISTS THE EXTERIOR CONCRETE
 WALL INSULATION AS R-5 AND THE GENERAL WALL SECTION ON
 6.1 SPECIFIES R-4.2 INSULATION. PLEASE CORRECT.
  
 19) COMPLIED.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE FAC RULE 9B-72. SUBMIT PRODUCT APPROVALS FOR
 THE INSWING AND OUTSWING EXTERIOR DOORS, WINDOWS,
 WINDOW MULLIONS AND ROOFING MATERIAL. THE NOA THAT WAS
 SUBMITTED FOR THE SINGLE HUNG WINDOWS IS EXPIRED,
 SUBMIT CURRENT NOA.
  
 21) FBC *106.3 CITY AMENDMENTS. PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 22)FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE
 INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.
  
 23) SHOW COMPLIANCE WITH R310.4. THE TEMPORARY
 INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE
 PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS
 DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF
 SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED,
 AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE
 WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE
 EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL. SPECIFY WHICH OPENING WILL COMPLY
 AND HOW IT WILL COMPLY.
  
 24) THE VALUE FOR THE SCOPE OF WORK SPECIFIED ON THE
 PLANS HAS BEEN ADJUSTED TO $123,358.00. ADDITIONAL
 PERMIT FEES ARE DUE.
  
 25) PLANS ARE REQUIRED TO HAVE HISTORIC REVIEW AND HAVE
 HISTORIC STAMP ON PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By rmcdouga Date 2007-11-21 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2007-11-21 Time 07:31 Sent To M
Notes
2007-11-21 11:17:422004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) " WHITE-OUT" ONPLANS IS NOT ACCEPTABLE. SEE FBC*
 106.1.3 CITY AMENDMENTS AND FS 471.
  
 3) THE PERMIT APPLICATION INDICATES THAT THIS PROJECT
 IS TO BE DONE IN PHASES. THE FIRST FLOOR ADDITION BEING
 PHASE ONE AND A SECOND STORY TO BE PHASE TWO. THE PLANS
 WILL NEED TO BE RE-DRAWN SHOWING ONLY THE FIRST FLOOR
 WITH THE ROOF ABOVE IT. THE ELEVATIONS AND OTHER
 DRAWINGS SHOULD SHOW THE ONE STORY STRUCTURE WITH NOTES
 INDICATING FUTURE SECOND STORY. SEE FBC* 106.1.1 CITY
 AMENDMENTS.
  
 4) THE DESIGN PARAMETERS ON SHEET 4.1 SPECIFIES THE
 WIND EXPOSURE CATEGORY AS C AND THE COMPONENT AND
 CLADDING TABLE PRESSURES ON SHEET 7 ARE FOR EXPOSURE B.
 PLEASE CORRECT. SEE FBC R301.2.1.4 AND TABLE
 R301.2(2).
  
 5) SPECIFY SAFETY GLAZING IN THE BATHROOM WINDOWS AS
 REQUIRED BY FBC R308.3.
  
 6) SPECIFY THE HEIGHT OF THE LOW PARAPET WALLS ON THE
 PLANS. FBC* 106.1.1 CITY AMENDMENTS
  
 7) ON SHEET 6.1, NUMBER 22 ON THE CONNECTOR SCHEDULE IS
 SPECIFIED AS A SIMPSON LUS 10. IS THIS SUPPOSE TO BE A
 LUS 210? PLEASE CLARIFY.
  
 8) THE SPACING FOR THE VERTICAL REINFORCING BARS FOR
 THE FIRST FLOOR ON SHEET 3.1 IS NOT ADEQUATE. PLEASE
 REVIEW AND CORRECT. SEE FBC R 609.3.
  
 9) SPECIFY THE LOCATIONS AND SIZE OF VERTICAL
 REINFORCING BARS FOR THE SECOND FLOOR WALLS AND THE
 PARAPET WALLS. SEE FBC* 106.1.1 CITY AMENDMENTS AND FBC
 R 609.3.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 11) THE ROOF SHEATHING NAILING AT THE BOTTOM OF THE
 CONNECTOR SCHEDULE ON SHEET 6.1 IS INCORRECT AND DOES
 NOT CORRESPOND TO FASTENING SPECIFIED ELSEWHERE ON THIS
 SHEET. SEE FBC R803.2.3.1.
  
 12) PROVIDE A DETAIL OF THE STEEL COLUMN SHOWN AT THE
 CORNER OF THE WINDOW OPENINGS AT THE SECOND FLOOR
 MASTER BEDROOM. SEE FBC* 106.1.1 CITY AMENDMENTS.
  
 13) ON SHEET 8.1 AN ELEVATION OF 20'-4" IS SPECIFIED AS
 THE T.O. BEAM AND IT APPEARS TO BE THE BOTTOM OF THE
 BEAM. PLEASE CLARIFY.
  
 14) SPECIFY THE LINTELS ABOVE THE SECOND FLOOR WINDOWS.
 SEE FBC* 106.1.1 CITY AMENDMENTS.
  
 15) PLEASE REMOVE THE EXTERIOR BEARING WALL DETAIL 5 ON
 8.2 WHICH DOES NOT APPLY TO THIS PROJECT.
  
 16) SECTION 1 ON 6.1 REFERS TO DETAIL #12 ON SHEET 6.2.
 HOWEVER, THERE WAS NO SHEET 6.2 SUBMITTED.
  
 17) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS THAT
 HAVE BEEN SIGNED AND DATED BY THE PREPARER AND
 OWNER/AGENT AS REQUIRED BY FBC CHAPTER 13.101.2.
  
 18) THE ENERGY CALC. FORM LISTS THE EXTERIOR CONCRETE
 WALL INSULATION AS R-5 AND SECTION 1 ON 8.1 SPECIFIES
 R-4.2 INSULATION. PLEASE CORRECT.
  
 19) THE CONDITIONED SPACE ON THE ENERGY CALC. FORM
 LISTS 2363 SQFT AND THE PLANS SPECIFY 2358 SQFT. PLEASE
 CORRECT.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE FAC RULE 9B-72. SUBMIT PRODUCT APPROVALS FOR
 THE INSWING AND OUTSWING EXTERIOR DOORS, WINDOW
 MULLIONS AND ROOFING MATERIAL.
  
 21) FBC *106.3 CITY AMENDMENTS. PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 22)FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT AN INSTALLATION
 SCHEDULE INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.
  
 23) SHOW COMPLIANCE WITH R310.4. THE TEMPORARY
 INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE
 PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS
 DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF
 SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED,
 AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE
 WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE
 EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-07 Cont ID  
Sent By btrobaug Date 2008-01-07 Time 15:25 Rev Time 0.00
Received By btrobaug Date 2008-01-07 Time 07:59 Sent To M
Notes
2008-01-07 15:24:51 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THR COMMENT IS FROM THE PREVIOUS REVIEW
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 16:08 Rev Time 0.00
Received By btrobaug Date 2007-11-16 Time 15:25 Sent To M
Notes
2007-11-16 16:08:35 
  
 APPLICATION #07110158
 3212 ALTON ROAD
 ELECTRICAL PLAN REVIEW
 WEST PALM BEACH, FL
 11/16/07
 .
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THERE ARE TWO SHEETS NUMBERED 10.1., RENUMBER ONE TO
 MATCH THE SEQUENCE 106.1.3 FBC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER
 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. ALSO 210.12 DICTATES
 THEY BE ON AN ARC FAULT CIRCUIT. THE SMOKE DETECTOR
 CIRCUITS LISTED ON THE PLAN ARE 1) NOT ARC FAULT AND 2)
 ON MULTIPLE CIRCUITS, WHICH WOULD PROHIBIT THE REQUIRED
 INTERCONNECTION.
  
 4} THE DINING ROOM CIRCUITS ARE MISMARKED AS 5 IN THE
 PANEL AND 7 AT THE RECEPTACLES.
  
 5} DUE TO THE METER LOCATION, AND THE PANEL LISTED AS
 MLO, A DISCONNECT IS REQUIRED PER 230.70, 225.32.
 INDICATE LOCATION ON PLAN AND ADD TO THE RISER DIAGRAM,
 PER 230.72(A)(1)
 .
 6} THE AIC RATING IS LISTED AS 22000 ON THE RISER AND
 10000 IN THE PANEL. CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-11-07 Cont ID  
Sent By ssherman Date 2007-11-07 Time 13:19 Rev Time 0.00
Received By ssherman Date 2007-11-07 Time 13:18 Sent To  
Notes
2007-11-07 13:19:16HISTORICAL APPROVAL NO FEE PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-02 Cont ID  
Sent By spalmer Date 2008-01-02 Time 11:46 Rev Time 0.00
Received By spalmer Date 2008-01-02 Time 11:46 Sent To Z
Notes
2008-01-02 11:46:57TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 14:50 Rev Time 0.00
Received By jleech Date 2007-11-07 Time 16:19 Sent To  
Notes
2007-11-07 16:19:43TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By tgordon Date 2008-01-08 Time 09:13 Rev Time 1.00
Received By tgordon Date 2008-01-08 Time 09:13 Sent To P
Notes
2008-01-08 09:23:13*** PROVISO ***
 1) AIR HANDLER #2 NEEDS TO COMPLY WITH 2004 FBC/R
 M1305.1.2 APPLIANCES IN ROOMS.
 APPLIANCES INSTALLED IN A COMPARTMENT, ALCOVE, BASEMENT
 OR SIMILAR SPACE SHALL BE ACCESSED BY AN OPENING OR
 DOOR AND AN UNOBSTRUCTED PASSAGEWAY MEASURING NOT LESS
 THAN 24 INCHES WIDE AND LARGE ENOUGH TO ALLOW REMOVAL
 OF THE LARGEST APPLIANCE IN THE SPACE, PROVIDED THAT A
 LEVEL SERVICE SPACE OF NOT LESS THAN 30 INCHES DEEP AND
 THE HEIGHT OF THE APPLIANCE, BUT NOT LESS THAN 30
 INCHES, IS PRESENT AT THE FRONT OR SERVICE SIDE OF THE
 APPLIANCE WITH THE DOOR OPEN.
  
 2) RETURN AIR NEEDS TO BE PROVIDED FOR TO THE SITTING
 ROOM AND BEDROOMS, SO THAT IT MAY RETURN TO THE AIR
 HANDLER IN COMPLIANCE WITH 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 11:42 Rev Time 0.45
Received By tgordon Date 2007-11-26 Time 11:42 Sent To P
Notes
2007-11-26 12:17:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SUBMIT THE COMPLETE ENERGY CALCULATIONS, NOT
 JUST TWO PAGES, SEE 4004 FBC 13-600.3.A.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER AND THE OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) NEED TO SUBMIT TWO (2) COPIES OF THE ENERGY
 CALCULATIONS AND THE COOLING LOAD CALCULATIONS, SEE
 2004 WPB AMEND. 106.1.
  
 4) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO THE
 MECHANICAL PLAN SHOWING ALL PERTINENT INFORMATION, SEE
 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) THE MECHANICAL PLAN SHOWS ACCESS TO AIR HANDLER #2
 AT THE WATER CLOSET, PER 2004 FBC/R M1305.1 THIRTY
 INCHES OF WORKING SPACE SHALL BE PROVIDED IN FRONT OF
 THE CONTROL SIDE TO SERVICE AN APPLIANCE. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By jleech Date 2008-01-08 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2008-01-10 Time 12:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 14:45 Rev Time 0.00
Received By jleech Date 2007-12-03 Time 14:37 Sent To  
Notes
2007-12-03 14:50:12DENIED;
 NO FLOOR PLAN FOR SECOND FLOOR PLUMBING.
 W/M CLEANOUT TO BE 4' AFF NOT 4".
 W/C TO BE IN BATHROOM GROUP NOT IN BUILDING DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By choops Date 2008-01-04 Time 15:39 Rev Time 0.00
Received By choops Date 2008-01-04 Time 15:39 Sent To E
Notes
2008-01-04 15:53:07***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY.
  
 NEW COMMENT:
  
 1)PLANS SHALL BE STAMPED AND APPROVED BY HISTORIC
 PRESERVATION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 09:34 Rev Time 0.00
Received By choops Date 2007-11-14 Time 09:34 Sent To E
Notes
2007-11-14 09:39:19***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM ANY NEW OR
 RELOCATED A/C MECHANICAL EQUIPMENT.NOTE:PURSUANT TO
 SECTION 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS:MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.
  
 3)PLANS SHALL CONTAIN NO WHITE-OUT.
  
 4)CLARIFY SCOPE OF WORK.2-STORY ADDITION AT REAR?
 SHOW FLOOR PLAN OF SECOND FLOOR IF BEING ADDED.WHAT
 IS EXISTING WHAT IS PROPOSED?
  
 5)PROVIDE AN ELEVATION PLAN SHOWING THE HEIGHTS OF
 THE PROPOSED ADDITIONS FROM GRADE TO THE MIDPOINT OF
 THE ROOF'S PITCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720