Plan Review Details - Permit 07110124
Plan Review Stops For Permit 07110124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2008-01-30 Cont ID  
Sent By mjacobs Date 2008-01-30 Time 07:15 Rev Time 0.00
Received By mjacobs Date 2008-01-30 Time 07:05 Sent To PC
Notes
2008-01-30 07:06:01PROCESS PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By mjacobs Date 2008-01-29 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2008-01-29 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By mjacobs Date 2008-01-18 Time 10:28 Rev Time 0.00
Received By mjacobs Date 2008-01-18 Time 07:26 Sent To  
Notes
2008-01-18 10:27:59 
 BUILDING PLAN REVIEW
 PERMIT: 07110124
 ADD: 2400 PRESIDENTIAL WAY #303
 CONT: DELCO CONSTRUCTION & HOMES
 TEL: (561)436-4106
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 1/18/08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) OK
  
  
  
 NOTE: THIS INFORMATION SHALL BE INDICATED ON THE
 PLANS.
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS. INDICATE ON THE
 DRAWINGS WHICH CODE THE PLANS ARE DESIGN TO. THE PERSON
 RESPONSIBLE FOR THE DRAWINGS NEEDS TO DATE THE
 DRAWINGS. PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ELECTRICAL, MECHANICAL, PLUMBING AND STRUCTURAL
 CHANGES TO EXISTING FLOOR LAYOUT. PROVIDE THE LAYOUT OF
 THE ENTIRE UNIT TO SHOW SMOKE ALARM COMPLIANCE.
  
 NOTED: HOWEVER, NO CHANGES IN PEN, PENCIL OR WHITE-OUT
 IS ALLOWED ON THE PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. THIS APPEARS TO
 BE A LEVEL 2 ALTERATION.
  
 NOTE: OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By mjacobs Date 2007-11-19 Time 14:14 Rev Time 0.00
Received By mjacobs Date 2007-11-19 Time 10:54 Sent To  
Notes
2007-11-19 14:14:28 
  
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07110124
 ADD: 2400 PRESIDENTIAL WAY #303
 CONT: DELCO CONSTRUCTION & HOMES
 TEL: (561)436-4106
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST11/19/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS. INDICATE ON THE
 DRAWINGS WHICH CODE THE PLANS ARE DESIGN TO. THE PERSON
 RESPONSIBLE FOR THE DRAWINGS NEEDS TO DATE THE
 DRAWINGS. PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ELECTRICAL, MECHANICAL, PLUMBING AND STRUCTURAL
 CHANGES TO EXISTING FLOOR LAYOUT. PROVIDE THE LAYOUT OF
 THE ENTIRE UNIT TO SHOW SMOKE ALARM COMPLIANCE.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. THIS APPEARS TO
 BE A LEVEL 2 ALTERATION.
  
 NOTE: THE INITIAL ?SD? FOR SMOKE DECTOR NEEDS TO CHANGE
 TO ?SA? SMOKE ALARM. SEE FBC. 907.10.1.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 15:13 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 07:15 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 06:32 Sent To  
Notes
2007-11-20 07:14:41 
  
  
 APPLICATION #07110124
 ELECTRICAL PLAN REVIEW
 2400 PRESIDENTIAL WAY #303
 11/20/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON ALL
 SHEETS OF THE PLANS FOR RECORD RETENTION.106.1.3.FBC AS
 AMENDED.
  
 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. NOTE SAME ON PLANS.
  
 4} DECLARE THE USE OF THE BUILDING PER CHAPTER 3, FBC.
 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By mwennerg Date 2008-01-25 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2008-01-25 Time 10:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By mwennerg Date 2007-11-29 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2007-11-29 Time 15:05 Sent To  
Notes
2007-11-29 15:17:41***DENIED***
  
 1) PLANS REFERENCE SMOKE DETECTORS THAT WOULD INDICATE
 THAT EQUIPMENT IS CONNECTED TO A FIRE ALARM SYSTEM. IF
 EQUIPMENT SHOULD REFLECT SMOKE ALARMS FOR OCCUPANT
 NOTIFICATION ONLY, PLEASE MAKE CORRECTION.
  
 2) PLEASE SEE ELECTRICAL COMMENT #2 REGARDING
 REQUIREMENTS FOR DRAWINGS.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 13:01 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 13:00 Sent To  
Notes
2008-01-14 13:06:17TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By jleech Date 2007-12-10 Time 08:18 Rev Time 0.00
Received By jleech Date 2007-11-09 Time 16:55 Sent To  
Notes
2007-11-09 16:56:21WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By jleech Date 2007-12-10 Time 08:18 Rev Time 0.00
Received By jleech Date 2007-12-10 Time 08:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By mperson Date 2008-01-29 Time 08:21 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 08:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-22 Cont ID  
Sent By jleech Date 2008-01-22 Time 08:09 Rev Time 0.00
Received By jleech Date 2008-01-22 Time 07:56 Sent To  
Notes
2008-01-22 08:13:05DENIED;
 1. NO CHANGES ON PLANS PERMITED TO BE IN PEN OR PENCIL.
 PLEASE REDUE PLANS.
 2. PLUMBING INFORMATION GIVEN IS OK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By jleech Date 2007-12-10 Time 08:10 Rev Time 0.00
Received By jleech Date 2007-12-10 Time 08:04 Sent To  
Notes
2007-12-10 08:16:20DENIED;
 SHOW ON PLANS THE EXTENT OF PLUMBING WORK TO BE DONE.
 I.E. NEW KITCHEN SINK, MOVE W/M DRAIN, ETC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 13:09 Rev Time 0.00
Received By choops Date 2007-11-16 Time 13:09 Sent To  
Notes
2007-11-16 13:11:14*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.