| 2007-11-15 09:02:18 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.THE APPLICATION STATES THAT THIS WILL BE INSTALLED |
| | IN AUGUST 2003 BY OTHERS.WHAT DOES THIS MEAN?A |
| | PERMIT IS REQUIRED PRIOR TO COMMENCING WORK. |
| | |
| | 2.THE SITE PLAN IS TO BE PREPARED BY A DESIGN |
| | PROFESSIONAL AS IT IS REQUIRED TO SHOW CODE COMPLIANCE, |
| | FBC*106.THIS MAY BE PREPARED BY THE ARCHITECT OR BY |
| | THE SURVEYOR.TWO SIGNED, SEALED, DATED ORIGINALS |
| | (WITH ORIGINAL SIGNATURES) WILL BE REQUIRED.(12/17/7 |
| | - SITE PLAN NOT REQUIRED TO BE DONE BY DESIGN |
| | PROFESSIONAL BUT IF IT IS PREPARED BY AN ARCHITECT, |
| | ENGINEER, OR SURVEYOR AND IS REQUIRED TO SHOW CODE |
| | COMPLIANCE, MUST BE A SIGNED, SEALED, DATED ORIGINAL.) |
| | |
| | 3.CVR, DESIGN PARAMETERS, STATES THAT THIS WILL |
| | COMPLY WITH 110MPH.THIS IS IN CONFLICT WITH CODE |
| | REQUIREMENTS AND OTHER PLACES ON THE PLAN, SEE FBC1609. |
| | THE CITY OF WEST PALM BEACH IS ENTIRELY IN THE 140MPH |
| | REGION. |
| | |
| | 4.EXPOSURE B IS DECLARED.THE PLANS STATE THAT |
| | COASTAL IS EXPOSURE C.SEE FBC1609.4(3), AS THE |
| | DEFINITION OF EXPOSURE C HAS CHANGED EFFECTIVE DECEMBER |
| | 8, 2006.ENGINEER IS TO EVALUATE SITE CONDITIONS AND |
| | PROVIDE JUSTIFICATION FOR EXPOSURE B.THIS MAY BE DONE |
| | BY REVISING THE SITE PLAN TO SHOW TERRAIN CONDITIONS |
| | AROUND THE PROPOSED IMPROVEMENT. |
| | |
| | 5.DESIGN PARAMETERS, SHEET CVR, REFERS TO "APPLICABLE |
| | INTERNAL PRESSURE" BUT DOES NOT PROVIDE AN ENCLOSURE |
| | CLASSIFICATION OR COEFFICIENT, FBC1603.1.4. |
| | |
| | 6.THE CERTIFICATE OF AUTHORIZATION FOR THE |
| | ARCHITECTURE FIRM IS TO BE PRINTED ON EACH SHEET, |
| | FAC61G16-23.002, 003. |
| | |
| | 7.THIS AMENITY IS REQUIRED TO BE ACCESSIBLE, SEE |
| | FBC11-4.1.SHOW THE ACCESSIBLE ROUTE TO AND INTO THE |
| | GAZEBO, FBC11-4.1.6, FBC11-4.1.2.THE ACCESSIBLE ROUTE |
| | TO THE GAZEBO CAN BE SHOWN BY SPECIFYING MINIMUM WIDTH |
| | AND MAXIMUM SLOPE OF THE SIDEWALK LEADING TO THE |
| | GAZEBO.THE ROUTE INTO THE GAZEBO DOES NOT APPEAR TO |
| | BE COMPLIANT AS THERE IS A STEP UP INTO THE GAZEBO. SEE |
| | FBC11-4.3.8. |
| | |
| | 8.THE NOA FOR THE SHINGLE ROOF REFERRED TO ON THE |
| | PLAN IS EXPIRED.PROVIDE CURRENT PRODUCT APPROVAL, |
| | FAC9B72. |
| | |
| | 9.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE EVALUATION REPORT (NOA), FAC9B72. |
| | WWW.FLORIDABUILDING.ORG.PLEASE PROVIDE BOTH |
| | DOCUMENTS, TWO SETS. |
| | |
| | 10. THE SHEATHING NAILING PATTERN ON A1 REFERS TO ZONE |
| | 3 FOR GABLES.PLEASE SEE FBC FIGURE 1609.6.2.2; HIP |
| | ROOFS ALSO HAVE A ZONE 3 AND THE 4" EDGE NAILING IS |
| | APPLICABLE, FBC TABLE 2304.9.1(31). |
| | |
| | 11.A1, OTHER PLACES, REFERS TO FBC2001, PLEASE |
| | REVISE. |
| | |
| | 12.REVISE GOVERNING CODE TO INCLUDE 2007 AMENDMENTS |
| | (EFFECTIVE JULY 1, 2007). |
| | |
| | 13.DECLARE OCCUPANCY CLASSIFICATION FBC CHAPTER 3. |
| | |
| | 14.FLOOR LOADS HAVE BEEN DECLARED BUT INTIL OCCUPANCY |
| | HAS BEEN DECLARED, COMPLIANCE WITH FBC TABLE 1607.1 |
| | CANNOT BE DETERMINED. |
| | |
| | 15.ROOFING SYSTEM APPROVAL NOTES, A1, REFERS TO SOUTH |
| | FLORIDA BUILDING CODE 2004.THIS IS NOT GOVERNING CODE |
| | (AND DOES NOT EXIST). |
| | |
| | 16.ROOFING SYSTEM APPROVAL NOTES, A1, REFERS TO MIAMI |
| | DADE PRODUCER 115.DO YOU MEAN RAS115?CHECK ALL |
| | NOTES AND REFERENCES. |
| | |
| | 17.A19 IS HANDWRITTEN ON EACH SHEET.IT IS NOT CLEAR |
| | WHAT THIS IS; ARE THERE SHEETS MISSING FROM THE PLAN? |
| | |
| | 18.PROVIDE PRODUCT APPROVAL FOR THE HELICAL SOIL |
| | ANCHORS, FAC9B72.NOTE THAT PRODUCT APPROVALS ARE TO |
| | BE APPROVED BY DESIGNER OF RECORD (SHOP DRAWING REVIEW |
| | STAMP, LETTER, OR SPECIFIC PRODUCT INCORPORATED INTO |
| | THE PLAN), FBC*106.3.3. |
| | |
| | 19.A2 SHOWS CEDAR SHAKE SHINGLE; OTHER SHOW 5TAB |
| | ASPHALT.PLEASE REVISE CONFLICT. |
| | |
| | 20.FLOOR FRAMING SURFACE IS TO COMPLY WITH FBC11-4.5. |
| | SHOW MAXIMUM GAPS AT BOARD JOINTS. |
| | |
| | 21.PRODUCT APPROVALS REQUIRED FOR THE LOUVERS, |
| | FAC9B72. |
| | |
| | 22.NO (ACCESS) OPENING IN THE GAZEBO RAILING SHOWN. |
| | SHOW LOCATION AND WIDTH, FBC10. |
| | |
| | 23.THE RAILING FOR THE GAZEBO IS TO COMPLY WITH |
| | FBC1012.1.PROVIDE DESIGN CRITERIA SHOWING COMPLIANCE |
| | WITH FBC1012 AND FBC1607.7. |