| 2007-11-16 10:49:34 | FAILED FOR FOLLOWING REASONS: |
| | |
| | 1. DUMPSTER LOCATION MUST BE ACCESSIBLE FOR PICKUP |
| | TRUCK. |
| | 2. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED |
| | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA |
| | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST |
| | FLOOR ELEVATION. |
| | 3. PLEASEMAKE SURE THESE AREAS SHOWN ON DRAINAGE |
| | DRAWINGS MUST MATCH WITH AND USED IN STORM WATER |
| | QUALITY CALCULATIONS. PLEASE PROVIDE A COPY OF THESE |
| | CALCULATIONS. |
| | 4. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE |
| | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM |
| | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE |
| | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING |
| | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR |
| | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET |
| | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL |
| | THESE. |
| | 5. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND |
| | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET |
| | FLOODED AND HAVE ENOUGH DRAINS. |
| | 6. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM |
| | WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE |
| | APPROVED FROM 100045TH STREET ENGINEERING SERVICES. |
| | 7. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION |
| | PLAN SHOWING SILT FENCE AROUND THE SITE & CATCH BASINS |
| | DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT |
| | OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST |
| | PARTICLES. |
| | 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH |
| | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. |
| | 9. YOUR PLANS NOT ORIGINALLY SIGNED & SEALED.PLANS |
| | MUST BE SEAL & SIGNED BY FLORIDA P.E. |
| | |
| | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| | PERMITTING PROCESS |
| | |
| | RASIK CHOKSHI805-6723 |