Plan Review Details - Permit 07110058
Plan Review Stops For Permit 07110058
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By rmcdouga Date 2008-01-11 Time 15:17 Rev Time 0.00
Received By rmcdouga Date 2008-01-11 Time 15:17 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-20 Cont ID  
Sent By rmcdouga Date 2007-12-20 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2007-12-20 Time 17:10 Sent To  
Notes
2007-12-20 18:21:532004 FBC W/2007 REVISIONS
 CHANGE OF OCCUPANCY FROM R3 TO MIXED OCCUPANCY
 R3/BUSINESS
  
 DENIED BY BUILDING
  
 1)THE VALUE OF THE WORK ON THE APPLICATION MAY BE TOO
 LOW. ADDITIONAL WORK MAY BE REQUIRED TO ACHIEVE CODE
 COMPLIANCE FOR THE CHANGE OF OCCUPANCY. THE PLANS DO
 NOT CLEARLY INDICATE THE SCOPE OF WORK THAT WILL BE
 DONE. PROVIDE AN ITEMIZED LIST OF WHAT IS TO BE DONE
 UNDER THIS PERMIT ON THE PLANS. SEE FBC 106.1.1THE
 VALUE OF THE WORK WILL BE DETERMINED BY THE SCOPE OF
 THE PROPOSED WORK.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) COMPLIED
  
 4) THE PLANS DO NOT ADEQUATELY INDICATE THE EXISTING
 CONDITIONS, ACCORDING TO THE PRE-INSPECTION REPORT THAT
 WAS SUBMITTED BY DOUG ROBERTSON. 1) THE ENTRY DOOR IS A
 SINGLE DOOR. (2) BREAK ROOM DOESN'T HAVE SINK OR RANGE.
 (3) STAIRS ARE 32" WIDE. (4)ON THE SECOND FLOOR THERE
 IS NO WALL BETWEEN THE STUDY AND THE BEDROOM. PLEASE
 SUBMIT PLANS THAT ACCURATELY INDICATE THE THE
 CONDITIONS. FBC 106.1.1* CITY AMENDMENTS. PROVIDE
 DRAWINGS THAT SHOWS EXACTLY WHAT IS EXISTING AND
 DRAWINGS SHOWING WHAT NEW WORK WILL BE DONE.
  
 5) THE BUILDING PLAN REVIEW WAS DONE BASED ON THE PLANS
 THAT WERE SUBMITTED.
  
 6) SPECIFY THE LIVE LOAD CAPACITY OF THE FIRST FLOOR.
 OFFICES REQUIRE A MINIMUM UNIFORMLY DISTRIBUTED LIVE
 LOAD OF 50 PSF. SEE FBC TABLE 1607.1.
  
 7) COMPLIED
  
 8) COMPLIED
  
 9) SHOW COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS FOR
 DOORS FBC 11-4.1.3(7), 11-4.3.9 AND 11-4.13. SPECIFY
 THE SIZES OF THE DOORS ON THE PLANS AND THAT THE DOOR
 HARDWARE AND THRESHOLDS COMPLY WITH ACCESSIBILTY
 REQUIREMENTS.
  
 10) FBC EXISTING BUILDING 812.5 REQUIRES THE NEW
 OCCUPANCY TO COMPLY WITH FBC CHAPTER 11 FOR
 ACCESSIBILITY. ALSO SEE 11-4.1.6 SHOW COMPLIANCE WITH
 FBC 1007 FOR ACCESSIBLE MEANS OF EGRESS. (SEE COMMENT
 #11).
  
 11) SHOW COMPLIANCE WITH 11-4.1.3(8)AND (9) FOR
 ACCESSIBLE ENTRANCES. THESE SECTIONS REQUIRE THE NUMBER
 OF ACCESSIBLE ENTRANCES IN A NUMBER EQUIVALENT TO THE
 NUMBER OF REQUIRED EXITS. FBC 1013.2 PROHIBITS EGRESS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES. THEREFORE, YOU WILL NEED TO
 ELIMINATE THE STOVE FROM THE BREAK ROOM OR PROVIDE
 ANOTHER ACCESSIBLE ENTRANCE.
  
 12) SHOW COMPLIANCE WITH FBC 11-4.3 FOR ACCESSIBLE
 ROUTE. PROVIDE SITE PLAN WITH DIMENSIONS OF WALKS, CURB
 RAMPS, RAMPS, LANDINGS, ETC. SPECIFIED. PROVIDE
 ELEVATIONS WITH DIMENSIONS INDICATING THE HEIGHTS ABOVE
 GRADE. SPECIFY THE WIDTH OF THE WALKWAY TO THE
 ACCESSIBLE ENTRANCE, SPECIFY THE SLOPE OF THE WALK,
 ETC. IF THERE IS A RAMP PROVIDE A DETAIL OF IT.
 INDICATE THE FINISH FLOOR HEIGHT OF THE STRUCTURE ABOVE
 GRADE AT THE ENTRANCES.
  
 13) COMPLIED
  
 14) COMPLIED
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 OF THESE COMMENTS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By rmcdouga Date 2007-11-13 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2007-11-09 Time 17:26 Sent To E
Notes
2007-11-13 15:50:302004 FBC W/2007 REVISIONS
 CHANGE OF OCCUPANCY FROM R3 TO MIXED OCCUPANCY
 R3/BUSINESS
  
 DENIED BY BUILDING
  
 1)THE VALUE OF THE WORK ON THE APPLICATION MAY BE TOO
 LOW. ADDITIONAL WORK MAY BE REQUIRED TO ACHIEVE CODE
 COMPLIANCE FOR THE CHANGE OF OCCUPANCY.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ENGINEER WHOSE NAME APPEARS IN THE IN THE TITLE
 BLOCK. FS 471 AND FAC 61G15-23.002
  
 4) THE PLANS DO NOT ADEQUATELY INDICATE THE EXISTING
 CONDITIONS, ACCORDING TO THE PRE-INSPECTION REPORT THAT
 WAS SUBMITTED BY DOUG ROBERTSON. 1) THE ENTRY DOOR IS A
 SINGLE DOOR. (2) BREAK ROOM DOESN'T HAVE SINK OR RANGE.
 (3) STAIRS ARE 32" WIDE. (4)ON THE SECOND FLOOR THERE
 IS NO WALL BETWEEN THE STUDY AND THE BEDROOM. PLEASE
 SUBMIT PLANS THAT ACCURATELY INDICATE THE THE
 CONDITIONS. FBC 106.1.1* CITY AMENDMENTS.
  
 5) THE BUILDING PLAN REVIEW WAS DONE BASED ON THE PLANS
 THAT WERE SUBMITTED.
  
 6) SPECIFY THE APPLICABLE CODES AND EDITIONS UNDER
 WHICH THE WORK WILL BE PREFORMED. SPECIFY THE
 CONSTRUCTION TYPE, OCCUPANCY TYPE AND IF THE STRUCTURE
 IS SPRINKLERED OR NOT ON THE PLANS. FBC 106.3.5.1.1*
 CITY AMENDMENTS
  
 7) SHOW COMPLIANCE WITH FBC EXISTING BUILDING 812.4
 WHICH REQUIRES THE FIRE AND LIFE SAFETY PROVISIONS OF
 THE CODE TO BE MET. SUBMIT A LIFE SAFETY PLAN. SPECIFY
 THE EXIT SIGNS (FBC 1006.3), TRAVEL DISTANCES(FBC
 1013.3)AND MEANS OF EGRESS ILLUMINATION (FBC 1006).
 ALSO SEE FBC EXISTING BUILDING 705.
  
 8) SPECIFY THE OCCUPANT LOAD ON THE PLANS. FBC1004.1
 AND 1004.9. SPECIFY THE NUMBER OF REQUIRED EXITS. SEE
 FBC 1018.2.
  
 9) FBC EXISTING BUILDING CODE 812.4.1.3 REQUIRES THE
 EGRESS CAPACITY TO MEET OR EXCEED THE OCCUPANT LOAD OF
 THE FBC. SHOW COMPLIANCE WITH FBC 1008.1.1 FOR DOOR
 SIZES. ALSO SEE ACCESSIBILITY REQUIREMENTS FOR DOORS
 FBC 11-4.1.3(7), 11-4.3.9 AND 11-4.13.
  
 10) FBC EXISTING BUILDING 812.5 REQUIRES THE NEW
 OCCUPANCY TO COMPLY WITH FBC CHAPTER 11 FOR
 ACCESSIBILITY. ALSO SEE 11-4.1.6 SHOW COMPLIANCE WITH
 FBC 1007 FOR ACCESSIBLE MEANS OF EGRESS.
  
 11) SHOW COMPLIANCE WITH 11-4.1.3(8)AND (9) FOR
 ACCESSIBLE ENTRANCES.
  
 12) SHOW COMPLIANCE WITH FBC 11-4.3 FOR ACCESSIBLE
 ROUTE. PROVIDE SITE PLAN WITH DIMENSIONS OF WALKS, CURB
 RAMPS, RAMPS, LANDINGS, ETC. SPECIFIED. PROVIDE
 ELEVATIONS WITH DIMENSIONS INDICATING THE HEIGHTS ABOVE
 GRADE.
  
 13) THE DOOR TO THE ACCESSIBLE BATHROOM DOES NOT COMPLY
 WITH FBC 11-4.13.6 MANEUVERING CLEARANCES AT DOORS
 WHICH REQUIRES A MINIMUM OF 18" ON THE PULL SIDE OF THE
 DOOR.
  
 14) TABLE 403.1 OF THE FBC PLUMBING REQUIRES A DRINKING
 FOUNTAIN. SHOW COMPLIANCE WITH FBC 11-4.1.3 (10) FOR
 ACCESSIBLE DRINKING FOUNTAINS.
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 OF THESE COMMENTS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-21 Cont ID  
Sent By btrobaug Date 2007-12-21 Time 12:03 Rev Time 0.00
Received By btrobaug Date 2007-12-21 Time 09:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 17:41 Rev Time 0.00
Received By btrobaug Date 2007-11-13 Time 16:26 Sent To FIRE
Notes
2007-11-13 17:41:34 
  
 APPLICATION # 07110058
 ELECTRICAL PLAN REVIEW
 311 11TH STREET
 11/13/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND LIGHTING.
  
 3} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES. PLEASE SEE NEW VERBIAGE FOR 2005 NEC:
 "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS." PHRASES LIKE ?GENERAL LIGHTING? ARE TOO VAGUE
 TO LOCATE THE DISCONNECTING MEANS FOR A CIRCUIT OR
 PIECE OF EQUIPMENT AS IS THE INTENT OF THIS ARTICLE.
  
 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED
 PER 700.12 NEC (F)(4). INDICATE SAME ON PLANS. SEE
 COMMENT #2.
  
 6} THE KITCHEN RECEPTACLES MUST COMPLY WITH
 210.8(B)(2), GFI PROTECTED. INDICATE ON THE PLANS.
  
 7} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 8} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By mawillia Date 2008-01-11 Time 16:19 Rev Time 0.00
Received By mawillia Date 2008-01-11 Time 15:30 Sent To B
Notes
2008-01-11 15:39:42*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A2 AND A3 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 14:14 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 13:38 Sent To  
Notes
2007-12-20 14:14:13*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF TEN) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS
 SUGGESTS HOW ITEM MAY BE ADDRESSED
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO CODE ANALYSIS, SHEET A3
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).ADD
 TO GENERAL NOTES, SHEET A1
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.ADD TO GENERAL NOTES,
 SHEET A1
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.ADD COMMENT TO AN
 APPROPIATE PLAN SHEET
  
 07.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
 PLEASE SPECIFY
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.COULD NOT LOCATE FIRE EXTINGUISHERS ON SHEET
 A2AS PER YOUR RESPONSE LETTER
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-15 Cont ID  
Sent By mawillia Date 2007-11-15 Time 12:38 Rev Time 0.00
Received By mawillia Date 2007-11-15 Time 11:49 Sent To  
Notes
2007-11-15 12:38:34*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.
  
 06.PROVIDE THE OCCUPANT LOAD (NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED)
 BASED UPON THE CHARACTERISTICS OF THE USE OF THE SPACE
 OR AS DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF
 THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 07.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 08.IT IS ILLUSTRATED ON THE SECOND FLOOR (SEE SHEET
 A3) OF SEVERAL SMOKE DETECTORS (SD);CLARIFY AS TO
 WHETHER THESE DEVICES ARE INDEED SMOKE DETECTORS OR
 SMOKE ALARMS.PLEASE BE ADVISED THAT SMOKE DETECTORS
 (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM SYSTEM,
 WHEREAS SMOKE ALARMS (SA) SOUND ONLY WITHIN AN
 INDIVIDUAL DWELLING UNIT OR SUITE OF ROOMS AND SHALL
 NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
  
 09.WHEN SMOKE ALARMS ARE INSTALLED IN NEW
 CONSTRUCTION, THEY SHALL BE ARRANGED SO THAT THE
 OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE ALARM
 WITHIN THE DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR
 AREA TO SOUND.
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 11:14 Sent To P
Notes
2008-02-20 11:14:29TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-07 Cont ID  
Sent By shill Date 2008-01-07 Time 15:59 Rev Time 0.00
Received By shill Date 2008-01-07 Time 15:59 Sent To  
Notes
2008-01-07 16:01:58TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 14:31 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 14:31 Sent To  
Notes
2007-12-13 14:31:33TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-15 Cont ID  
Sent By rbrown Date 2007-11-15 Time 11:50 Rev Time  
Received By mawillia Date 2007-11-07 Time 09:23 Sent To Z
Notes
2007-11-09 13:19:1311/9/07 SENT TO R MCDOUGAL FOR BUILDING REVIEW.WILL
 ALSO NEED BILL TROBAUGH TO DO ELECTRICAL REVIEW.RB
2007-11-07 09:23:57SENT TO CHRIS FOR ZONING REVIEW

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 08:54 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 08:36 Sent To  
Notes
2008-02-25 08:58:23PROVISO;
 PROVIDE MANUFACTURE'S PAPER WORK SHOWING DRINKING
 FOUNTAIN CONFORMS TO ASME A002.19.1M, ASME A112.19.2,
 ASME 112.19.9M. PAPER WORK MUST BE ON JOB FOR FINAL
 PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By jleech Date 2008-01-11 Time 13:41 Rev Time 0.00
Received By jleech Date 2008-01-11 Time 13:41 Sent To  
Notes
2008-01-11 13:59:51PROVISO;
 1. PROVIDE MANUFACTURE'S PAPER WORK SHOWING THE
 DRINKING FOUNTAIN CONFORMS TO, ASME A002.19.1M, ASME
 A112.19.2, ASME A112.19.9M.
 2. THE KITCHEN SINK MUST BE INSTALLED TO MEET TABLE
 403.1 MINIMUM PLUMBING FIXTURES. THIS SINK SHALL MEET
 ALL HANDICAP REQUIREMENTS AS LISTED IN THE FBC-BUILDING
 CHAPTER 11. SECTION 11-4.24.2 HEIGHT 34" ABOVE FINISH
 FLOOR. SECTION 11-4.24.3, KNEE CLEARANCE OF 27" HIGH,
 30 " WIDE AND 19" DEEP. 11-4.24.4 SINK TO BE A MAX. OF
 6 1/2" DEEP. SECTION 11-4.24.5, CLEAR FLOOR SPACE IS
 30" X 48". SECTION 11-4.24.6, EXPOSED PIPES TO BE
 RAPPED. SECTION 11-4.24.7 FAUCET TO BE LEVER-OPERATED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By mperson Date 2008-01-11 Time 10:30 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 10:29 Sent To  
Notes
2008-01-11 10:51:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. **COMMENT NOT ADDRESSED**
 SHOW ON PLANS HOW DRINKING FOUNTAIN WILL DRAIN TO
 SANITARY SYSTEM. **PROVIDE A SANITARY ISOMETRIC RISER
 DIAGRAM INDICATING PIPE AND TRAP SIZES.
  
 2. **COMMENT NOT ADDRESSED**
 THE BREAKROOM SINK IS REQUIRED TO MEET HANDICAP
 REQUIREMENTS. PER THE FOLLOWING FBC BUILDING CHAPTER
 11.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION AND CLEAR FLOOR SPACE INDICATED
 ON FLOOR PLAN)
  
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 3. CLEAR FLOOR SPACE REQUIRED ON FLOOR PLAN FOR
 DINKING FOUNTAIN. PER *11-4.15.5 CLEARANCES (1).
  
 4. SHEET A2: HAND WRITTEN CHANGES TO SIGN AND SEALED
 PLANS UNACCEPTABLE. PER *106.1.3 QUALITY OF BUILDING
 PLANS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By jleech Date 2007-12-26 Time 07:38 Rev Time 0.00
Received By jleech Date 2007-12-26 Time 07:17 Sent To  
Notes
2007-12-26 07:47:23DENIED;
 1. SHOW ON PLANS HOW DRINKING FOUNTAIN WILL DRAIN TO
 THE SANITARY SYSTEM. ELECTRICAL OUTLET REQUIRED FOR
 DRINKING FOUNTAIN.
  
 2. THE BREAK SINK IS REQUIRED TO MEET HANDICAP
 REQUIREMENTS. SEE FBC BUILDING CHAPTER 11, SECTIONS
 11-4.24.1 THRU 11-4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-26 Cont ID  
Sent By aaponte Date 2007-12-26 Time 09:13 Rev Time 0.00
Received By aaponte Date 2007-12-26 Time 09:13 Sent To  
Notes
2007-12-26 09:20:18PROVISO:
 1. PARKING SPACE ADJACENT TO THE EXISTING GARAGE WILL
 NOT BE COUNTED AS REQUIRED PARKING. BACK UP SPACE DOES
 NOT COMPLY WITH THE MINIMUM 24 FEET.
 TO COMPLY WITH 3 PARKING SPACES REQUIRED, TWO ARE
 PROVIDED ON BACK OF STRUCTURE AND ONE IS PROVIDED
 ON-STREET.
 2. ALL REQUIRED PARKING SPACES SHALL BE STRIPPED
 FOLLOWING CITY'S STANDARDS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By mawillia Date 2007-11-15 Time 11:50 Rev Time 0.00
Received By aaponte Date 2007-11-09 Time 10:10 Sent To E
Notes
2007-11-09 10:17:561. PLEASE PROVIDE A SURVEY OF THE PROPERTY. INCLUDE THE
 LOCATION OF EXISTING PLANT MATERIAL/TREES ON THE
 PROPERTY.
 2. PARKING SPACE DIMENSIONS ARE 8'6" WIDE BY 18"LONG.
 HANDICAP IS 12'WIDE BY 18' LONG , WITH A 5' WIDE
 ACCESS SPACE ON THE SIDE. ACCESS SPACE IS NOT NECESSARY
 AT THE FRONT OF THE HANDICAP PARKING AS DEPICTED ON
 SITE PLAN.