Plan Review Details - Permit 07110013
Plan Review Stops For Permit 07110013
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-06-01 Cont ID  
Sent By jwitmer Date 2009-06-01 Time 08:40 Rev Time 0.66
Received By jwitmer Date 2009-06-01 Time 08:00 Sent To  
Notes
2009-06-01 08:33:31REVISION# 3, DATED 5-12-09
 SHEETS A-0, A-2.1 & A-6.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-10 Cont ID  
Sent By jwitmer Date 2008-04-10 Time 16:21 Rev Time 1.33
Received By jwitmer Date 2008-04-10 Time 16:21 Sent To PC
Notes
2008-04-10 16:22:48RED LINE PROJECT INFO TO READ TYPE IIA PROTECTED,
 SPRINKERED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By jwitmer Date 2008-02-15 Time 08:40 Rev Time 2.22
Received By jwitmer Date 2008-02-15 Time 08:39 Sent To  
Notes
2008-02-15 08:44:03BUILDING PLAN REVIEW
 PERMIT: 07110013
 ADD: 221 CLEMATIS ST
 CONT: PLAZA CONSTRUCTION INC
 TEL: (561)271-5297
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL. PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL. 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SHEET A-0 PROJECT INFORMATION: PLEASE PROVIDE THE
 CORRECT CONSTRUCTION TYPE OF IIA REQUIRING 1 HR
 PROTECTION, SEE TABLE 601. THIS IS A 4 STORY BUILDING
 NOT A THREE STORY BUILDING.
  
 3)THIS IS A 4 STORY BUILDING THAT ENVOKES THE STATE
 STATUTES FOR THRESHOLD BUILDINGS, 4 STORIES AND MORE IN
 HEIGTH. THE FOLLOWING THREE ITEMS SHALL BE REQUIRED
 BEFORE PERMIT ISSUANCE.
 3A)THRESHOLD INSPECTION PLANFL S. S. 553.71(7)
 " THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURALINSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR:WPB AMENDMENT 105.13.6.
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. CONTACT HAROLD
 PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 3C) THRESHOLD BLDG,REQUIRED STATEMENT:W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) TABLE 601 PROVIDE INFORMATION FOR THE 1 HR FIRE
 PROOFING FOR THE FLOOR FRAMING MEMBERS.
  
 5) SHEET A-2.1 THE THIRD FLOOR CORRIDOR IS INDICATED AS
 A 1-HR RATED CORRIDOR, BUT SECTIONS OF SAID WALL STILL
 DO NOT INDICATE A FIRE RATING. TABLE 1016.1 INDICATES
 THAT NO FIRE RATING IS REQUIRED BUT IF THE DESIGN TEAM
 WANTS TO BUILD TO A MORE RESTRICTIVE WE ARE JUST NOTING
 THAT THE CORRIDOR IS NOT TOTALLY 1 HR FIRE RATED.
  
 6) SHEET A-2.1 HAS TWO DETAILS BUT THEY ARE MARKED AS
 A-2.2 PLEASE CORRECT.
 6A) DETAIL 02/A-2.2 INDICATES SHAFT WALL CONSTRUCTION
 THAT DOES TIE INTO THE CORRIDOR PLEASE SPECIFY THE WALL
 RATING 707.4.
  
 7) SHEET A2.3 DETAIL# 06 INDICATES 1 HR RATINGS FOR
 STEEL COLUMNS OUT OF THE 1997 STANDARD BUILDING CODE
 PLEASE UPDATE TO THE 2004 FBC.
  
 8)PLANS INDICATE NEW PREENGINEERED A/C STAND ON THE
 ROOF, WILL REQUIRE (2) COPIES OF PRODUCT APPROVALS, THE
 CUT SHEET SUBMITTED WILL NEED TO MEET THE FOLLOWING:
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By shill Date 2007-11-13 Time 10:02 Rev Time 0.00
Received By shill Date 2007-11-13 Time 10:02 Sent To  
Notes
2007-11-13 10:02:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 REVISED ON 11/27 AFTER SITE VISIT AND FURTHER
 INVESTIGATION:
  
 1.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 2.A-0, OCCUPANT LOAD, PLEASE ROUND UP AS THE OCCUPANT
 LOAD CANNOT BE LESS THAN FBC TABLE 1004.1.2.
  
 3.A2.1, A2.2, SHOWS STAIRS WHICH HAVE BEEN CLOSED OFF
 AT A LOWER LEVEL.THIS CREATES A DEAD END CORRIDOR,
 SEE FBC1016.2.YOU CANNOT HAVE A STAIRWAY WHICH
 APPEARS TO BE AN EXIT WHICH IS BLOCKED OFF.PLEASE
 ADDRESS AS DISCUSSED.
  
 4.A2.2, LEGEND DOES NOT MATCH THE GRAPHIC FOR THE
 WALL.PLEASE CHECK ALL.
  
 5.DOOR D305, A2.2, WHAT IS NEXT TO THE DOOR?THIS
 APPEARS TO BE AN EXISTING STRUCTURAL COLUMN.SEE FBC
 FIGURE 11-25, MANEUVERING CLEARANCE REQUIRED, AND SHOW
 ON THE PLAN.
  
 6.THE PLAN STATES THAT 2ND AND 3RD FLOORS ARE
 BUSINESS OCCUPANCY.PLESAE SEE PERMIT 06090366; A
 PERMIT FOR SECOND FLOOR ALTERATION HAS ALREADY BEEN
 ISSUED AND THE 2ND FLOOR IS ASSEMBLY OCCUPANCY.PLEASE
 SUBMIT CHANGES FOR THE SECOND FLOOR AS A REVISION TO
 THE ISSUED PERMIT, 06090366.
  
 THE SCOPE OF WORK UNDER THIS PERMIT, 07110013, SHOULD
 INCLUDE ONLY THE THIRD FLOOR.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-19 Cont ID  
Sent By dpalmer Date 2008-03-19 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2008-03-19 Time 09:17 Sent To  
Notes
2008-03-19 09:19:18LIGHTING CALCULATIONS ARE OK, PLANS ACTUALLY REFLECT
 CLOSER TO SHOWN FIXTURE DESIGN ALLOWANCES. THE METHOD B
 SUBMITTED FOR LIGHTIGN PERFORMANCE LEVELS ARE ACTUALLY
 SHOWN ROUNDED UP.
  
 ** WILL NEED TO REVISE PENDANT FIXTURE INFORMATION ONCE
 KNOWN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-23 Cont ID  
Sent By dpalmer Date 2008-01-23 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2008-01-23 Time 10:22 Sent To  
Notes
2008-01-23 10:23:04 
  
 ** DENIED2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE METHOD *B* FLA COM CALCULATIONS
 AND INPUT DATA REPORT DOES NOT MATCH WITH PLANS. FOR
 EXAMPLE: PLEASE SEE THE IDR ONLY INDICATES ONE FIXTURE
 WHICH IS NOT POSSIBLE WHEN THE PLANS CONTAIN NUMEROUS
 FIXTURES.
 EACH FIXTURE, WATTAGE AND METHOD OF CONTROL NEEDS TO
 COORDINATE WITH PLANS.
 13-415.2, 13-415.1.B
  
 ** ELECTRICAL PLANS ARE OK AND HAVE BEEN STAMPED. NEED
 TO ADDRESS #1 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By dpalmer Date 2007-11-28 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2007-11-28 Time 11:49 Sent To  
Notes
2007-11-28 14:52:07** DENIED**
  
  
 1) NOTE: PLEASE SEE CODES SHALL BE STATED ON PLANS FOR
 RELEVANT DESIGNS.
 PLEASE INCLUDE THE FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** ALSO REQUIRED ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE COORDINATE ALL SCOPE OF WORK ON
 APPLICATION AND PLANS WITH THAT OF PERMITTED WORK
 ALREADY ISSUED FOR BUILDING.
 PLEASE KNOW FOR EXAMPLE, STAIRS ON 2ND FLOOR ARE NO
 LONGER GOING TO DEAD ON FIRST FLOOR, WALL IS BEING
 REMOVED, ELECTRICAL LIGHTING AS SHOWN IS CHANGING ETC
 ETC.
 PLEASE KNOW THIS WORK IS FOR TENANT COMMON AREAS.
 PLEASE ALSO KNOW THIS LOCATION IS PART OF A LARGER
 BUILDING AND IS NO LONGER ONE BUILDING BY DEFINITION AS
 OLD PREVIOUS FIRE WALLS ARE NO LONGER IN EXISTENCE.
  
 3) NOTE: PLEASE SEE THE METHOD *A* WHOLE BUILDING
 CALCULATIONS CAN NOT BE USED AS THE WHOLE BUILDING IS
 NOT BEING BROUGHT INTO COMPLIANCE.
 PLEASE KNOW FOR ELECTRICAL LIGHTING PERFORMANCE
 CALCULATIONS ARE NEEDED PER 13-415.2
 PLEASE ALSO PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.1.ABC.1.1, .1.2
  
 4) NOTE: PLEASE SEE NO LIGHTING CONTROLS ARE SHOWN PER
 13-415.1.ABC.1.1, .1.2.
 PLEASE BE SURE TO SEE FBC CHAPTER 10 FOR USE OF ANY
 OCCUPANCY SENSORS ON EGRESS AREA LIGHTING AND SEE
 NFPA-101 7.8.1.2.2, FBC 1006.1.2
  
 5) NOTE: PLEASE PROVIDE MORE INFORMATION ON HOUSE PANEL
 WHICH IS NOTED AS BEING REPLACED.
 RISER HAS NOTE WHICH MENTIONS TO SEE NOTE #1, HOWEVER
 COULD NOT LOCATE ANY NOTE #1 ON THAT SAME SHEET FOR
 INFORMATION ON PANEL CHANGE OUT.
  
 6) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ADA
 COMPLIANCE FOR HORN AND STROBE DEVICES PER FBC
 11-4.28.1,.2 AND .3(4)
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-05-29 Cont ID  
Sent By mawillia Date 2009-05-29 Time 13:49 Rev Time 0.00
Received By mawillia Date 2009-05-29 Time 13:32 Sent To  
Notes
2009-05-29 13:46:28*****REVISION #3, DATED 05/12/-09, APPROVED*****
  
  
 REVISED PLAN SHEETS (OF THE 4 SUBMITTED) A-2.1 AND
 A-6.1 WERE STAMPED, INTIIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 12:52 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 12:35 Sent To  
Notes
2008-04-07 12:51:58*****APPROVED*****
  
  
 PLAN SHEETS A-2.1, A-6.1, E-1, AND FP-1 WERE STAMPED,
 INTIIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By mawillia Date 2008-02-19 Time 12:58 Rev Time 0.00
Received By mawillia Date 2008-02-19 Time 12:29 Sent To  
Notes
2008-02-19 12:56:46*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER, THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By mawillia Date 2007-11-19 Time 16:16 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 13:55 Sent To  
Notes
2007-11-19 16:36:51*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.PROJECT LOCATION UNCLEAR;THE ATTACHED
 ENERGY/GAUGE SHEETS INDICATE THE 3RD FLOOR, WHEREAS THE
 PLAN SHEETS INDICATE RENOVATION FOR THE 2ND AND 3RD
 FLOORS.
  
 3.BASED UPON A FIELD SURVEY CONDUCTED BY THIS WRITER,
 IT WOULD APPEAR THAT THE TYPE OF OCCUPANCY FOR THE
 PROJECT IS ASSEMBLY.PLEASE CLARIFY.
  
 4.PLEASE INCLUDE A LIFE SAFETY PLAN SHEET(S) WHICH
 SHALL SHOW THE TRAVEL DISTANCE TO REACH THE EXITS.
  
 5.ON SHEET A-2.1 AND A-2.2, PLEASE EXPLAIN RATIONALE
 FOR THE CLOSING OF THE EXISTING STAIR AT THE LOWER
 LEVEL.
  
 6.SEPARATE PLANS AND PERMIT SHALL BE REQUIRED FOR THE
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 13:16 Sent To  
Notes
2009-05-21 13:18:47TO C8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 15:56 Sent To  
Notes
2008-03-18 16:45:16TO "COMM" BD#16
2008-03-17 15:56:45WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 14:55 Sent To  
Notes
2008-02-01 16:35:432/1/08-MOVED TO "COMM" BD#44
2008-01-15 15:01:22TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-11-05 Time   Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 11:51 Sent To  
Notes
2007-11-15 14:58:34TO "COMM" BD#30
2007-11-05 11:52:14WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-06-17 Cont ID  
Sent By rregueir Date 2009-06-17 Time 10:39 Rev Time 0.00
Received By rregueir Date 2009-06-17 Time 10:38 Sent To PC
Notes
2009-06-17 10:39:11PAGE M1 REVISION 3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-29 Cont ID  
Sent By rregueir Date 2008-03-29 Time 18:27 Rev Time 0.00
Received By rregueir Date 2008-03-29 Time 18:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-13 Cont ID  
Sent By rregueir Date 2008-02-13 Time 10:21 Rev Time 0.00
Received By rregueir Date 2008-02-13 Time 07:53 Sent To  
Notes
2008-02-13 10:20:581. PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, REVIEW STOP WILL BE IN "FAIL" STATUS
 PENDING BUILDING PLAN REVIEW OF PRODUCT APPROVAL FOR
 THE PRE-ENGINEERED A/C STAND. THE PAPERWORK SUBMITTED
 DOES NOT APPEAR TO BE AN ACTUAL PRODUCT APPROVAL BUT
 SOME PAPERWORK FROM THE MANUFACTURER. ALSO, THE
 SUBMITTAL IS OF POOR QUALITY AND IS ILLEGIBLE.
  
 2. ENERGY CALCULATIONS HAVE NOT BEEN REVIEWED FOR
 COMPLIANCE WITH MECHANICAL REQUIREMENTS OF FBC CHAPTER
 13. METHOD B CALCULATIONS ARE NOT AN OPTION AS THIS IS
 NOT A RENOVATION AS DEFINED IN FBC 13-202. SEE FBC
 13-400.0.C.4 THEREFORE, ONLY MINIMUM EFFICIENCY
 CRITERIA FOR NEWLY INSTALLED EQUIPMENT NEED BE
 DEMONSTRATED. THIS INFORMATION IS ON THE PLANS AND IS
 DEEMED COMPLIANT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-01 Cont ID  
Sent By rregueir Date 2007-12-01 Time 15:37 Rev Time 0.00
Received By rregueir Date 2007-12-01 Time 14:23 Sent To  
Notes
2007-12-01 15:37:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. LEVEL OF ALTERATION SHALL BE DECLARED BY THE
 DESIGNER IN ACCORDANCE WITH FBC, EB 301.5. THIS APPEARS
 TO BE A LEVEL 2 ALTERATION AND SHALL BE REVIEWED AS
 SUCH.
  
 2. ENERGY CALCULATIONS: METHOD A COMPLIANCE IS NOT
 APPLICABLE FOR THIS PROJECT. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED IN ACCORDANCE WITH FBC
 13-400.0.C.4. DEMONSTRATE COMPLIANCE BY SHOWING ALL
 NEWLY INSTALLED BUILDING ENVELOPE COMPONENTS,
 MECHANICAL AND ELECTRICAL SYSTEMS MEET THE PRESCRIPTIVE
 MINIMUM EFFICIENCIES REQUIRED BY FBC SECTION 13-4.
 NOTE: SYSTEM SIZING SUMMARY ATTACHED TO METHOD A FORM
 IS OK AND MAY BE USED TO SHOW COMPLIANCE WITH FBC
 13-407.1.ABC.1.
  
 3. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SHOW COMPLIANCE WITH FBC, M TABLE 403.3 OR
 ASHRAE 62.1-2004 UNLESS MEANS FOR NATURAL VENTILATION
 ARE PRESENT AS ALLOWED UNDER FBC, M SEC.402. THIS
 APPLIES TO ALL HABITABLE AREAS OF THIS FLOOR.
  
 4. OUTSIDE AIR CALCULATIONS: NOTE CALLS FOR ASHRAE
 STANDARD 62 AND FMC 403.3. ONE METHOD OF VENTILATION OR
 THE OTHER SHALL BE DECLARED AND A COMBINATION OF THE
 TWO SHALL NOT BE USED IN ACCORDANCE WITH FBC, M 403.4.
  
 5. COND. UNIT SUPPORT DETAIL: IS THIS TO BE A SITE
 BUILT STAND OR A PRE-ENGINEERED SYSTEM? IF A
 PRE-ENGINEERED STAND IS TO BE USED, PRODUCT APPROVAL IS
 REQUIRED AS THESE STANDS HAVE BEEN DEFINED AS
 STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72. PROVIDE A
 PRODUCT APPROVAL FOR THE SPECIFIC STAND TO BE USED. FOR
 MORE INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 6. IF NEW CONDENSING UNIT IS INSTALLED WITHIN 10 FEET
 OF AN OPEN ROOF EDGE, PROVIDE GUARDS FOR SERVICE ACCESS
 IN ACCORDANCE WITH FBC, M 304.10.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2009-05-29 Cont ID  
Sent By aaponte Date 2009-05-29 Time 10:49 Rev Time 0.00
Received By aaponte Date 2009-05-29 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-06 Cont ID  
Sent By aaponte Date 2007-12-06 Time 10:36 Rev Time 0.00
Received By aaponte Date 2007-12-06 Time 10:36 Sent To  
Notes
***NONE***