| Plan Review Stops For Permit 07100891 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-10-31 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-10-31 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2007-10-31 15:40:18 | 1. THE NEW BACKFLOW PREVENTION DEVICE MUST BE INSTALLED | | | IN ACCORDANCE WITH MANUFACTURERS REQUIREMENTS AND ALL | | | APPLICABLE REGULATIONS. | | | | | | 2. THE NEW BACKFLOW PREVENTION DEVICE CANNOT BE TURNED | | | ON UNTIL APPROVED BY REGULATORY ENTITIES. | | | | | | 3. THE NEW DEVICE SHALL NOT NEGATIVELY IMPACT THE | | | OPERATION OF THE EXISTING FIRE SPRINKLER SYSTEM. | | | | | | 4. ANY CONTROL VALVES FOR THE BACKFLOW PREVENTION | | | DEVICE MUST BE PROPERLY SUPERVISED AND LOCKED TO | | | PREVENT ANY UNAUTHORIZED CLOSURE. | | | | | | 5. THE NEW INSTALLATION IS SUBJECT TO INSPECTION AND | | | APPROVAL. | | | | | | 6. THE EXISTING FIRE WATCH IS TO REMAIN ON THE BUILDING | | | UNITL SUCH TIME AS THE NEW FIRE LINE BACKFLOW DEVICE | | | HAS BEEN INSPECTED, TESTED, AND APPROVED. | | | | | | THIS REVIEW WAS PERFORMED AS AN EMERGENCY SINCE THE | | | EXISTING BUILDING HAS BEEN OPERATING UNDER FIRE WATCH | | | CONDITIONS SINCE THE WATER WAS TURNED OFF. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
|