Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-11-13 Cont ID  
Sent By mwennerg Date 2007-11-13 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2007-11-13 Time 15:01 Sent To  
Notes
2007-11-13 15:07:12***APPROVED***
  
 1) PLANS INDICATE THAT THE FDC IS LOCATED 305' FROM A
 FIRE HYDRANT (SHEET 4) WITH LETTER ATTACHED. NO LETTER
 WAS ATTACHED WITH THIS SUBMITTAL. PLEASE PROVIDE
 DOCUMENTATION OF PRIOR APPROVAL FROM THIS OFFICE
 ALLOWING AN ARRANGEMENT THAT EXCEEDS THE MINIMUM CODE
 REQUIREMENT. THIS OFFICE WILL TYPICALLY EXTEND THE
 DISTANCE TO NOT MORE THAN 150' FROM THE CLOSEST FIRE
 HYDRANT. LETTER WAS FAXED TO THIS OFFICE AFTER INITIAL
 REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-13 Cont ID  
Sent By mwennerg Date 2007-11-13 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2007-10-31 Time 10:08 Sent To  
Notes
2007-10-31 10:09:17TO "F" BOX