Plan Review Details - Permit 07100862
Plan Review Stops For Permit 07100862
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-14 Cont ID  
Sent By jgomez Date 2008-03-14 Time 07:43 Rev Time 0.00
Received By jgomez Date 2008-03-13 Time 16:38 Sent To PC
Notes
2008-03-14 07:57:52IMPACT FEES PAID. RECEIPT AND NOC COPY PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-11 Cont ID  
Sent By jgomez Date 2008-02-07 Time 11:03 Rev Time 0.00
Received By jgomez Date 2008-02-07 Time 10:46 Sent To PC
Notes
2008-02-07 11:43:05BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT PRIOR TO SLAB INSPECTION
 TO AVOID DELAYS.
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECS FOR
 EXTERIOR DOUBLE POCKET SLIDING GLASS DOORS. NEED TO
 INCLUDE JAMBDETAIL. ONLY HEADER DETAIL WAS PROVIDED.
 ALSO,SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE
 1/2" EXP. BOLTS SPECIFIED ON HEADER DETAIL.
 3-PROVIDE COMPLETE MANUFACTURER'S SPECS FOR BBQ THAT
 ALLOWS INSTALLATION ON PROPOSED AREA PRIOR TO
 INSTALLATION TO AVOID DELAYS OR CONFLICTS.
 4- PROVIDE PRODUCT APPROVAL FOR ROOF TILE ADHESIVE
 THAT IS LISTED ON THE TILE PRODUCT APPROVAL TO VERIFY
 UPLIFT RESISTANCE.
 5-PROVIDE COMPLETE TRUSS PACKAGE TO INSPECTORAT
 TIME OF INSPECTION. MAKE SURE TRUSS PACKAGE IS PROPERLY
 SIGNED AND SEALED BY THE ENGINEER AS REQUIRED BYSEC.
 61G15.23.002.COPY OF SIGNATURE IS NOT ALLOWED.
 ALSO, TRUSS PACKAGE TO BE APPROVED IN WRITING BY THE
 ARCHITECT OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By jgomez Date 2007-11-09 Time 10:32 Rev Time 0.00
Received By jgomez Date 2007-11-09 Time 10:32 Sent To P
Notes
2007-11-09 10:54:23RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW
 UNDER EXISTING BUILDING 2004 CODE, FLORIDA RESIDENTIAL
 CODE 2004 AND FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY AT 2300 N. JOG RD
 TO VERIFY IF IMPACT FEES ARE DUE.BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- NEW ADDITION EAST WALL NEEDS TO HAVE MIN. ONE HOUR
 FIRE RATINGINCLUDING THE ROOF OVERHANG AS REQUIRED BY
 SEC. R302.1 OF 2004 FLORIDA RESIDENTIAL CODE. PROVIDE
 SPECIFICATIONS AS REQUIRED.
  
 4- OPENINGS ARE NOT ALLOWED ON EAST WALL OF NEW
 ADDITION AS REQUIRED BY SEC. R302.2 OF 2004 FLORIDA
 RESIDENTIAL CODE. REVISE AS REQUIRED.
  
 5- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) DOUBLE POCKET SLIDING FRENCH DOORS AS SHOWN ON
 FLOOR PLANS. NOA 05-0526.05 SUBMITTED DOESN'T INCLUDE
 PROPOSED INSTALLATION SHOWN ON PLANS.
  
 B) EXTERIOR SWING DOOR IN LAUNDRY/STORAGE ROOM. NOA
 02-1211.18 SUBMITTED EXPIRED ON 08/15/2007.
  
 C) FLAT CONCRETE TILE AS SPECIFIED ON DRAWINGS. NOA
 02-0916.11 SUBMITTED IS NOT FOR FLAT TILE.
  
 D) ALL SIMPSON OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS,TRUSS ANCHOR SCHEDULE AND DETAILS.
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE WHERE THE CONNECTOR IS SHOWN ONLY.
  
 7- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- SPECIFY IN PLANS AREA TABULATION, INCLUDING THE
 COVERED PATIO AREA FOR PROPER BUILDING VALUATION (SEC.
 108.3 CITY AMENDMENTS TO FBC 2004)AND TO CHECK THE
 ENERGY CALCULATIONS.
  
 9- TRUSS DRAWINGS:
 A) PROVIDE COMPLETE PACKAGE. ONLY TRUSS LAYOUT WAS
 PROVIDED. NEED ALL INDIVIDUAL ENGINEERED TRUSSES TOO.
  
 B) TRUSS LAYOUT TO BE SIGNED, SEALED AND DATED AND
 PROVIDE ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE AND SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
 ***NOTE: IF CONFORMING TO SEC. 61G15-31.003 TO AVOID
 SIGNING AND SEALING EACH TRUSS SHEET,THEN MAKE SURE
 DESIGNER OF RECORD NAME INFORMATION IS PROVIDED AND
 EACH SHEET IS PROPERLY NUMBERED.
  
 C) TRUSS DESIGN LOADS NEED TO BE COORDINATED WITH
 DESIGNER OF RECORD AND MAKE SURE ATTIC LIVE LOAD IS
 INCLUDED AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 D) DESIGNER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 10- ENERGY CALCULATIONS:REVISEHOUSE NUMBER AND
 COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 11- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004. OWES $124.36 FOR
 UPDATED PERMIT VALUATION AND RADON FEES.
  
 12- ONE SET OF PLANS IS MISSING SHEET A-1.
  
 13- SHEET A-2:
 A) PROVIDE COMPLETE FRAMING DETAIL FOR EXTERIOR
 DOUBLE POCKET SLIDING GLASS DOORS AS SHOWN ON PLANS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 AND SEC. R301
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) SIZE OF DOOR OPENING SHOWN BY CABANA ROOM IS TOO
 LARGE COMPARED TO THE SIZE OF DOOR SPECIFIED. REVISE AS
 REQUIRED.
  
 C) UPDATE FLORIDA BUILDING CODE NOTE. CORRECT
 REVISIONS TO BE 2007 REVISIONS, NOT 2006.
  
 D) MAXIMUM DOORS AND WINDOWS DESIGN PRESSURES DON'T
 MATCH THOSE SHOWN ON SHEET S-2. REVISE AS REQUIRED.
  
 E) ROOM FINISH NOTE #2 DOESN'T APPLY TO THIS
 PROJECT. REVISE AS REQUIRED.
  
 14- TYPICAL WALL SECTION ON SHEET A-4:
 A) ROOF SHEATHING: REVISE NAIL TYPE REQUIRED AND
 NAIL SPACING FOR ROOF ZONE 3 AS REQUIRED BY SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. ALSO,
 CLEARLY DEFINE ROOF ZONES.
  
 B) SPECIFY ROOFCROSS VENTILATIONAS REQUIRED BY
 SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE:
 KEEP IN MIND THAT OPENINGS ON EAST WALL ARE NOT ALLOWED
 BY SEC. R302.2.
  
 C) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2
 AND SEC. R602.1.2.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 15- SHEET S-1:
 A) CLARIFY ASSUMED SOIL BEARING CAPACITY FOR THE
 DESIGN OF THIS STRUCTURE.FOUNDATION NOTE #3 CALLS FOR
 2500PSF BEARING CAPACITY, WHILE NOTE ON COLUMN SCHEDULE
 ABOVE CALLS FOR 2000PSF. REVISE/CLARIFY AS REQUIRED.
  
 B) REVISE VERTICAL REINFORCEMENT OF CONCRETE BLOCK
 WALLS AS REQUIRED BY SEC. R609.3.3 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 C) REVISE/CLARIFY TYPE OF POST BASE USED FOR THE 6X6
 WOOD POST. DETAIL D CALLS FOR SIMPSON CB66, WHILE
 DETAIL 2/S-2 CALLS FOR SIMPSON CBSQ66-SDS2.REVISE AS
 REQUIRED.
  
 16- SHEET S-2:
 A) ROOF TRUSS LOADS: CLEARLY SPECIFY IF ATTIC IS
 GOING TO HAVE STORAGE OR NOT.FLOOR PLAN ON SHEET A-2
 IS SHOWING ATTIC ACCESS WITH LADDER TO ACCESS THE AIR
 HANDLER UNIT.ALSO, TRUSS DESIGN CRITERIA NOTE #7
 CALLS FOR ADDITIONAL LOAD FOR STORAGE, BUT IS NOT CLEAR
 IF THE ATTIC WILL HAVE STORAGE OR NOT. REVISE TRUSS
 LOADS AS REQUIRED. COORDINATE LOADS WITH TRUSS ENGINEER
 ALSO.
  
 B) REVISE ENGINEERING CRITERIA.REFER TO 2007 FBC
 REVISIONS, NOT 2006.
  
 C) SPECIFY CONNECTORS AT THE END OF TRUSS GIRDER
 ABOVE DOUBLE 36"X80" POCKET SLIDING DOORS.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND SEC. R301 OF
 2004 FLORIDA RESIDENTIAL CODES FOR CALCULATED UPLIFT
 LOADS.
  
 D) BEAM BB-1 SHOWN ON THE ROOF FRAMING PLAN IS NOT
 LISTED IN THE BEAM SCHEDULE. REVISE AS REQUIRED.
  
 E) GENERAL ROOF NOTE #2: CLEARLY SPECIFY WHICH TYPE
 OF 10D NAIL ARE REQUIRED. SEE ROOF TILE PRODUCT
 APPROVAL AND VERIFY THAT PROPOSED NAILS WILL MEET THE
 CALCULATED UPLIFT MOMENT.
 ***NOTE: IF USING POLYFOAM TO ATTACH TILE, THEN PROVIDE
 PRODUCT APPROVAL FOR SUCH POLYFOAM AS LISTED IN THE
 PRODUCT APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 10:25 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 08:01 Sent To P
Notes
2008-01-24 10:25:34 
  
  
 PROVISO
  
 THE 100 AMP DISCONNECT FOR THE SEPERATE STRUCTURE,
 SHOWN ON THE RISER DIAGRAM, MUST BE LOCATED ON THAT
 STRUCTURE. 225.32

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 10:33 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 09:50 Sent To M
Notes
2007-11-05 10:33:48 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.INDICATE THE PANEL LOCATION
  
 2} THE MAIN LUG ONLY PANEL SHOWN ON THE RISER DIAGRAM
 DOES NOT COMPLY WITH 225.31FOR THE REQUIRED
 DISCONNECTING MEANS. ALSO SEE 225.32 FOR LOCATION.
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66.
 INDICATE SAME ON THE RISER DIAGRAM.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). NO RECEPTACLE IS SHOWN ON
 THE PLAN.
  
 5} ONLY ONE SMALL APPLIANCE CIRCUIT IS IN THE LOAD
 CALCS. PER 210.11(C)(1) TWO ARE REQUIRED. ALTHOUGH NO
 WORK IS BEING DONE IN THE MAIN HOUSE, TWO ARE REQUIRED
 IN THE GUEST HOUSE.
  
 6} THE SMOKE ALARMSHOWN IN THE GUEST BEDROOM IS
 INCORRECTLY PLACED, BOTH ARE INSIDE THE ROOM, ONE IS
 REQUIRED TO BE IMMEDIATLY OUTSIDE.R313.1.2 RES FBC.
  
 7} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14 A/C UNITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 09:19 Sent To M
Notes
2008-03-11 09:19:49TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 11:04 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 11:04 Sent To Z
Notes
2008-01-14 11:05:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 13:01 Rev Time 0.00
Received By jleech Date 2007-10-31 Time 12:35 Sent To  
Notes
2007-10-31 12:36:56TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 11:00 Rev Time 0.30
Received By tgordon Date 2008-03-11 Time 11:00 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By tgordon Date 2008-01-17 Time 16:13 Rev Time 0.40
Received By tgordon Date 2008-01-17 Time 16:13 Sent To E
Notes
2008-01-17 16:45:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ARCHITECT'S RESPONSE SENT BACK WITH REVISED PLANS
 REGARDING GAS TANKLESS WATER HEATER. (MOVED TO OUTSIDE,
 COMBUSTION AIR CAL'S. AND OUTSIDE AIR NOT NEEDED).
 PLEASE LOOK AT THE PLANS SUBMITTED FOR THE GAS TANKLESS
 WATER HEATER OUTSIDE THE BUILDING, IF YOU ARE UNABLE TO
 FIND IT PLEASE LOOK IN THE LAUNDRY/STORAGE ROOM ON PAGE
 A-2 AND MEP-2. THIS ROOM IS A CONFINED SPACE WITH A
 CLOTHES DRYER IN IT, SEE 2004 FBC/R G2407.5.1.
  
 2) AS REQUESTED IN LAST REVIEW 11-5-07. PROVIDE
 COMBUSTION AIR CALCULATIONS AND COMBUSTION AIR OR
 MAKEUP AIR (AS REQUIRED) FOR GAS TANKLESS WATER HEATER,
 SEE 2004 FBC/R G2407.1.
  
 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By tgordon Date 2007-11-05 Time 16:07 Rev Time 0.40
Received By tgordon Date 2007-11-05 Time 16:07 Sent To P
Notes
2007-11-05 16:40:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROVED COMBUSTION AIR CALCULATIONS FOR GAS TANK-LESS
 WATER HEATER ON MECHANICAL PLAN, SEE FBC/R G2407.1, AND
 PROVIDE COMBUSTION AIR IF REQUIRED.
  
 2) PROVIDE MAKEUP AIR FOR GAS TANK-LESS WATER HEATER,
 SEE FBC/R G2407.4.
  
 3) SHOW ON MECHANICAL PLAN WERE THE CLOTHES DRYER VENT
 WILL DISCHARGE TO. CLOTHES DRYER VENT MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE FBC/R R303.4.2.
  
 4) SEE MECHANICAL PLAN, THE SUPPLY AIR GRILL AND DUCT
 IN LAUNDRY / STORAGE ROOM IS NOT LEGIBLE, SEE WPB AMEND
 106.1.3. PLEASE CORRECT.
  
 5) SIZE ALL RETURN AIR DUCTS AND GRILLS ON MECHANICAL
 PLAN, SEE WPB AMEND. 106.3.5.4.
  
 6) MECH. PLAN SHOWS A RETURN AIR GRILL IN THE BATH
 ROOM, RETURN AIR MAY NOT BE TAKEN FROM A BATHROOM, SEE
 FBC/R M1602.2 (5). PLEASE CORRECT.
  
 7) SHOW A BATHROOM EXHAUST FAN IN GUEST BATH ON
 MECHANICAL PLAN, SEE FBC/R R303.3 EXCEPT.
  
 8) PLANS SHOW TWO A/C CONDENSER PADS, PLEASE CORRECT OR
 EXPLAIN.
  
 9) SHOW ON MECH. PLAN H.V.A.C. SPECIFICATIONS THE
 HEATER KW, SEE WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-12 Cont ID  
Sent By jleech Date 2008-03-12 Time 09:58 Rev Time 0.00
Received By jleech Date 2008-03-12 Time 09:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-05 Cont ID  
Sent By jleech Date 2008-02-05 Time 08:18 Rev Time 0.00
Received By jleech Date 2008-02-05 Time 08:15 Sent To B
Notes
2008-02-05 08:27:49DENIED;
 RISER DIAGRAM HAS BEEN CORRECTED.
 NEW COMMENTS;
 1. PROVIDE MANUFACTURE INFORMATION ON TANKLESS WATER
 HEATER.
 2. PROVIDE COMBUSTTION AIR CALCULATIONS.
 3. SHOW EXHAUST VENT LOCATION ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 12:56 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 12:55 Sent To  
Notes
2007-11-17 13:01:13SANITARY RISER DIAGRAM NOT TO CODE;
 A) SHOWER IS NOT VENTED. FBC PLUMBING
 SEC.909.1
 B)AUTOMATIC CLOTH WASHER BRANCH DRAIN TO BE
 3" SECTION 406.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-16 Cont ID  
Sent By choops Date 2008-01-16 Time 13:08 Rev Time 0.00
Received By choops Date 2008-01-16 Time 13:08 Sent To E
Notes
2008-01-16 13:24:11***APPROVED - RESUB #1***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-01 Cont ID  
Sent By choops Date 2007-11-01 Time 14:45 Rev Time 0.00
Received By choops Date 2007-11-01 Time 14:45 Sent To E
Notes
2007-11-01 14:52:47***FAILED***
  
  
 1)INDICATE THE SETBACK DIMENSIONS FROM THE PROPOSED
 CABANA TO ALL PROPERTY LINES.
  
 2)INDICATE THE SEPARATION DISTANCE FROM EXISTING
 HOUSE TO THE PROPOSED STRUCTURE.
  
 3)INDICATE THE SETBACK DISTANCE FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES (NOTE: MAY NOT PROJECT
 MORE THAN 4' INTO A REQUIRED SETBACK).
  
 4)SHEET A-4 EAST ELEVATION SHOWS A COVERING ON THE
 PROPOSED TRELLIS.CLARIFY.DOES TRELLIS HAVE A
 COVERED ROOF?IF NOT, REVISE AND REMOVE SHOWN
 COVERING.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720