Plan Review Details - Permit 07100843
Plan Review Stops For Permit 07100843
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-15 Cont ID  
Sent By mjacobs Date 2008-02-15 Time 08:55 Rev Time 0.00
Received By mjacobs Date 2008-02-15 Time 08:10 Sent To PC
Notes
2008-02-15 08:55:38PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By mjacobs Date 2008-02-13 Time 09:51 Rev Time 0.00
Received By mjacobs Date 2008-02-12 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-28 Cont ID  
Sent By mjacobs Date 2008-01-28 Time 08:18 Rev Time 0.00
Received By mjacobs Date 2008-01-25 Time 16:15 Sent To PC
Notes
2008-01-28 08:17:49 
 BUILDING PLAN REVIEW
 PERMIT: 07100843
 ADD: 10130 NORTHLAKE BLVD
 CONT: DOUGLAS M PISARSKI INC.
 TEL: (561)662-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST - 1/28/08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) OK
  
 **NOTE: SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS
 WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN
 70 INCHES ABOVE THE DRAIN INLET FBC 1210.3. THE
 RESPONSE SHEET INDICATES 4 FEET.**
 2)THE NEW SHOWER SHALL BE IN COMPLIANCE WITH FBC
 1210.3. THE WALLS SHALL BE FINISH WITH A SMOOTH
 NONABSORBENT SURFACE. PAINT ALONE ON DRYWALL OR DUROCK
 IS NOT CONSIDERED NONABSORBENT. WALL WITHIN 2 FEET OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD
 NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE
 FINISH FLOOR. FBC1210.2. NOTE: EPOXY PAINT ON DRYWALL
 IS NOT CONSIDERED A HARD SURFACE.
 3)OK
 4) OK
 **THE LEVEL OF ALTERATION SHALL BE INDICATED ON THE
 PLANS.**
 5)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
 6)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-07 Cont ID  
Sent By mjacobs Date 2007-11-07 Time 18:53 Rev Time 0.00
Received By mjacobs Date 2007-11-07 Time 15:19 Sent To  
Notes
2007-11-07 18:53:04BUILDING PLAN REVIEW
 PERMIT: 07100843
 ADD: 10130 NORTHLAKE BLVD
 CONT: DOUGLAS M PISARSKI INC.
 TEL: (561)662-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST11/7/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)THE NEW SHOWER SHALL BE IN COMPLIANCE WITH FBC
 1210.3. THE WALLS SHALL BE FINISH WITH A SMOOTH
 NONABSORBENT SURFACE. PAINT ALONE ON DRYWALL OR DUROCK
 IS NOT CONSIDERED NONABSORBENT. WALL WITHIN 2 FEET OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD
 NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE
 FINISH FLOOR. FBC1210.2. NOTE: EPOXY PAINT ON DRYWALL
 IS NOT CONSIDERED A HARD SURFACE.
  
 3)NOTE: THE SPACE OF THE BRACING SHOWS TWO DIFFERENT
 MEASUREMENTS ON SHEET A-2. INDICATE CLEARLY WHICH
 MEASUREMENT SHALL BE USED. SHEET A-1 SHALL HAVE THE
 SAME DIMENSION AS SHEET A-2 FOR THE SPACING OF THE
 BRACING.
  
 4) NOTE: PROVIDE THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION INFORMATION FOR THE X-RAY MACHINE ON THE
 NEW ?LEAD LINED WALL?
  
 5)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6)PROVIDE A WALL SECTION DETAIL SHOWING HOW THE
 KENNEL CAGES WILL BE ATTACH TO THE WALL TO PREVENT THEM
 FROM OVERTURNING. A STRUCTURAL DETAIL IS ALSO REQUIRED
 FOR THE RELOCATION OF THE ELECTRIC WATER HEATER TO THE
 CEILING AS STATED ON SHEET A-1. WHAT TYPE OF MATERIALS
 IS USED TO CONSTRUCT THE DOG WASH AREA? PROVIDE A
 ELEVATION DETAIL SHOWING ALL MATERIALS AND DIMENSIONS
 INCLUDING THE STEPS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-07 Cont ID  
Sent By btrobaug Date 2008-02-07 Time 14:54 Rev Time 0.00
Received By mjacobs Date 2008-02-07 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 16:41 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 12:31 Rev Time 0.00
Received By btrobaug Date 2007-11-13 Time 09:00 Sent To FIRE
Notes
2007-11-13 11:10:55 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-3 AND A-4, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2005
 NEC UNLESS OTHERWISE NOTED.
  
 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED. THER ARE REFERENCES TO OUTDATED CODES
 THROUGHOUT THE PLANS.
  
 2} THE ARCHITECTS SEAL MUST BE DATED PER 61G1-16.004(4)
 FAC. ONLY ONE SET OF PLANS ARE SEALED. TWO SETS OF ALL
 DOCUMENTS MUST BE SUBMITTED FOR REVIEW PER 106.1 FBC AS
 AMENDED.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE DISCONNECT LOCATION HAS BEEN OMITTED.
  
 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. NOTE SAME ON THE PLANS ELECTRICAL SHEETS.
  
 5} SHEET A-4 INDICATES THE METER BEING FED FROM A
 GUTTER.PROVIDE A SITE PLAN INDICATING THE LOCATION OF
 ALL SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE
 230 CAN BE REVIEWED. PROVIDE CONDUIT AND CONDUCTOR SIZE
 AND TYPE FOR THE SERVICE EQUIPMENT FROM THE GUTTER. IT
 CANNOT BE DETERMINED IF THERE IS A DISCONNECTING MEANS
 AHEAD OF THE METER SHOWN OR IF THIS IS A SEPERATE
 SERVICE. THE EQUIPMENT GROUNDING CONDUCTOR RAN TO THE
 DISCONNECT SHOULD BE REMOVED IF IT IS DETERMINED THAT
 THE DISCONNECT SHOWN IS THE FIRST MEANS. SEE
 250.24(A)(5), 2005 NEC.
  
 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 7} THE LOAD CALCULATION GIVEN IS FOR A RESIDENTIAL UNIT
 AS EVIDENCED WITH THE SMALL APPLIANCE CIRCUITS AND
 TAKING A 65% DEMAND ON THE HEAT, BOTH ARE SPECIFIC
 CALCULATIONS FOR DWELLINGS. SUBMIT CALCULATIONS PER
 215.2(A)(1), 125% OF CONTINUOUS LOADS,220.12, 220.14,
 220.16 AND 220 PART III.
  
 8}THE PANEL SCHEDULE CIRCUIT #2,4 INDICATES A DRYER,
 CIRCUIT #8 INDICATES A WASHER. SHEET A-3 SHOWS A
 WASHER/DRYER COMBO, WITH NO CIRCUIT NUMBERS. CORRELATE
 SAME.
  
 9} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. 106.1.2.
 FBC AS AMENDED.
  
 10} THE X-RAY EQUIPMENT MUST BE INCLUDED IN THE LOAD
 CALCULATION PER 220.14(A). SEE ARTICLE 660, 2005 NEC.
  
  
 11} PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT
 OLD SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 13:40 Rev Time 0.00
Received By mawillia Date 2008-02-13 Time 13:29 Sent To B1
Notes
2008-02-13 13:32:53*****RE-STAMPED*****
  
 PLAN SHEETS A-1, A-2, AND A-3 WHICH WERE PREVIOUSLY
 APPROVED ON 01/25/08 WERE RE-STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By mawillia Date 2008-01-25 Time 11:28 Rev Time 0.00
Received By mawillia Date 2008-01-25 Time 11:15 Sent To B1
Notes
2008-01-25 11:28:01*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1, A-2, AND A-3 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By mawillia Date 2007-11-13 Time 14:39 Rev Time 0.00
Received By mawillia Date 2007-11-13 Time 14:10 Sent To  
Notes
2007-11-13 14:37:09*****DENIED*****
  
 1.AMEND THE COVER PAGE AND THE PROJECT SITE LOCATION
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET TO
 REFLECT THE AUTHORITY HAVING JURISDICTION WHICH IS THE
 CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY.
  
 2.ONE OF THE TWO SUBMITTED PLAN SETS ARE NOT SIGNED
 AND SEALED.
  
 3.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 6.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 13:52 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 13:52 Sent To  
Notes
2008-02-06 13:55:29TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 09:47 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 09:47 Sent To  
Notes
2008-01-15 09:53:30TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-13 Cont ID  
Sent By mawillia Date 2007-11-13 Time 14:46 Rev Time 0.00
Received By mawillia Date 2007-10-30 Time 11:23 Sent To  
Notes
2007-11-05 10:47:04TO "BOB"#10
2007-10-30 11:24:25WAITING FOR "BOB"--OK TO ROUTE TO "BOB" PER RBROWN

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-11 Cont ID  
Sent By mperson Date 2008-02-11 Time 16:33 Rev Time 0.00
Received By mperson Date 2008-02-11 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By mperson Date 2008-01-18 Time 11:27 Rev Time 0.00
Received By mperson Date 2008-01-18 Time 11:27 Sent To  
Notes
2008-01-18 13:17:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS REVIEW COMMENTS**
  
 1. **OK** COMMENT ADDRESSED HOWEVER SEE NEW COMMENTS
 ON THE RESUBMITTED SANITARY RISER.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **OK** COMMENT ADDRESSED.
  
 5. **RESPONSE NOTED, HOWEVER SEE NOTE: FOR COMMENT
 #5.**
 SHEET A-1 EXISTING A-1 EXISTING OR PROPOSED FLOOR PLAN
 DOES NOT INDICATE A DRINKING FOUNTAIN. PER FBC PLUMBING
 TABLE *03.1(2) BUSSINESS, A DRINKING FOUNTAIN IS
 REQUIRED AND SHALL BE ACCESSIBLE PER THE FOLLOWING,
 ALSO PLEASE INDICATE IF THE BATHROOMS ARE ACCESSIBLE.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **NOTE: THE RESUBMITTED PLANS ARE INDICATING THE
 REQUIRED DRINKING FOUNTAIN, HOWEVER THE REQUIRED
 ELEVATION DETAIL WITH THE ABOVE REQUIREMENTS FOR THE
 DRINKING FOUNTAIN WERE NOT ON THE RESUBMITTED PLANS.
 PLEASE COMPLY ON THE RESUBMITTAL.
  
 6. **RESPONSE NOTED, HOWEVER SEE NOTE: FOR COMMENT
 #6.**
 THERE WERE NO ENERGY CALCULATIONS SUBMITTED FOR THE
 NEW PROPOSED 50 GAL. WATER HEATER PER CHAPTER 13 ENERGY
 EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A
 STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE
 STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE
 PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY
 BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS
 FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL
 DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING,
 VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING
 SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO
 ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES,
 TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND
 PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF
 OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND
 FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP,
 AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING
 SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH
 THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
  
 **NOTE: THE ENERGY CALCULATIONS FOR THE WATER HEATER
 WERE NOT IN THE RESUBMITAL.
  
 7. **RESPONSE NOTED**
 PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE A
 PERMIT CAN BE ISSUED.
  
 **THE FOLLOWING ARE NEW COMMENTS TO THE SANITARY
 ISOMETRIC RISER DIAGRAM DUE TO DESIGN CHANGES FROM THE
 PREVIOUS PLAN REVIEW**
  
 8. SHEET A-4 SANITARY RISER DIAGRAM: PLEASE SIZE ALL
 WASTE, VENTS, AND TRAPS. PER CHAPTER 1 CITY AMENDMENTS,
 SECTION *106.3.5.1.3 PLUMBING, FBC PLUMBING SECTIONS
 *701.1 SCOPE AND 901.1 SCOPE.
  
 9. SHEET A-4 SANITARY RISER DIAGRAM: A WATER-SEAL TRAP
 IS REQUIRED FOR THE TUB. PER FBC PLUMBING SECTION
 *1002.1 FIXTURE TRAP.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By mperson Date 2007-11-09 Time 11:57 Rev Time 0.00
Received By mperson Date 2007-11-09 Time 11:57 Sent To  
Notes
2007-11-09 15:02:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM: THE
 PROPOSED SANITARY PLUMBING BEING SHOWN AS TYING INTO
 THE EXISTING TOILET STUB IS ILLEGAL PER FBC-2004,
 PLUMBING, SECTION *909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 2. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM: THE
 WASTE PIPING TO THE WASHING MACHINE IS UNDERSIZED AND
 WILL NEED TO BE INCREASED TO 3 INCH PER (A) *406.3
 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) *708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
  
 (D) *708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 3. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 4. SHEET A-1 PROPOSED FLOOR PLAN: THE PROPOSED FLOOR
 PLAN IS INDICATING A NEW 50 GAL. ELEC. WATER HEATER
 BEING RELOCATED ABOVE THE CEILING. PROVIDE A DETAIL ON
 HOW THE 500 LBS WATER HEATER IS BEING SUPPORTED ABOVE
 THE CEILING.
  
 5. SHEET A-1 EXISTING OR PROPOSED FLOOR PLAN DOES NOT
 INDICATE A DRINKING FOUNTAIN. PER FBC-2004 W/05 & 06
 REV. PLUMBING TABLE *403.1(2) BUSINESS, A DRINKING
 FOUNTAIN IS REQUIRED AND SHALL BE ACCESSIBLE PER THE
 FOLLOWING ALSO PLEASE INDICATE IF THE EXISTING
 BATHROOMS ARE ACCESSIBLE.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 6. THERE WERE NO ENERGY CALCULATIONS SUBMITTED FOR THE
 NEW PROPOSED 50 GAL. WATER HEATER PER CHAPTER 13 ENERGY
 EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A
 STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE
 STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE
 PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY
 BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS
 FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL
 DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING,
 VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING
 SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO
 ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES,
 TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND
 PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF
 OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND
 FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP,
 AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING
 SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH
 THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
  
 7. PER FC 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy