Plan Review Details - Permit 07100792
Plan Review Stops For Permit 07100792
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-14 Cont ID  
Sent By rmcdouga Date 2009-01-14 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2009-01-14 Time 11:27 Sent To  
Notes
2009-01-14 11:28:46REVISION TO RPLACE TWO WINDOWS AND SGD WITH PAIR OF
 FRENCH DOORS AT THE FAMILY ROOM IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-18 Cont ID  
Sent By kconrad Date 2008-11-18 Time 13:33 Rev Time 0.00
Received By kconrad Date 2008-11-18 Time 13:33 Sent To  
Notes
2008-11-18 13:34:35PREINSPECT PERFORMED BY CJ: REAR STORAGE ACCESSORY
 STRUCTURE FOR STUCCO APPLICATION APPROVED AS STATED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-12 Cont ID  
Sent By rmcdouga Date 2008-06-12 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2008-06-12 Time 09:47 Sent To  
Notes
2008-06-12 10:13:25BUILDING PROVISO
  
 1) SUBMIT (2) TWO SETS OF RAS 117 CALCULATIONS FOR THE
 GAF MODIFIED ROOFING THAT WILL BE INSTALLED ON THE FLAT
 ROOF BEFORE INSTALLING. SPECIFY THE APPROVED ASSEMBLY,
 FASTENING OPTION AND DESIGN PRESSURE FOR THE SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-26 Cont ID  
Sent By rmcdouga Date 2008-02-26 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2008-02-26 Time 07:03 Sent To  
Notes
2008-02-26 09:42:082004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 3) THE ENERGY CALCULATION FORM IS OUTDATED. THE CURRENT
 FORM IS 600C-04. THE FORM IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT. SEE FBC 11-600.
  
 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, FLOOR
 FRAMING PLAN AND SHOP DRAWINGS FOR THE HAMBRO FLOOR
 SYSTEM. FBC 106.1.2* CITY AMENDMENTS
  
 5) SHOP DRAWINGS WILL BE REQUIRED FOR THE GUARD RAILS
 AT THE BALCONY, SHOWING COMPLIANCE WITH R312. FBC
 106.1.2* CITY AMENDMENTS
  
 6) THE WINDLOAD SCHEDULE ON SHEET 2 DOES NOT SPECIFY
 THE PRESSURES FOR ROOF ZONE 3. PLEASE REVISE. SEE FBC
 TABLE R301.2(2).
  
 7) THE ROOF ZONE DIAGRAM ON SHEET 2 DOES NOT INDICATE
 ROOF ZONE 3 AT THE CORNERS. PLEASE CORRECT. SEE FIGURE
 R301.2 (8).
  
 8) REVISE THE ROOF SHEATHING NAILING SCHEDULE ON SHEET
 2 TO COMPLY WITH R803.2.3.1 SHEATHING FASTENINGS. WOOD
 STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO ROOF
 FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON CENTER
 AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1.0.113-INCH NOMINAL SHANK DIAMETER
 2.RING DIAMETER OF 0.012 OVER SHANK DIAMETER 3.
 16 TO 20 RINGS PER INCH
 4.0.280 INCH FULL ROUND HEAD DIAMETER
 5.2-INCH NAIL LENGTH
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1 .
  
 9) THE STATEMENT ON SHEET 2 THAT RING SHANK NAILS ARE
 NOT REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25 FEET
 IS INCORRECT. PLEASE REVISE. SEE R 803.2.1.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE ROOF ACCESS HATCH
 AND THE SKYLITE SHOWN ON THE ROOF FRAMING PLAN ON SHEET
 3. FAC RULE 9B-72
  
 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE GAF
 MODIFIED ROOF SYSTEM IS INCOMPLETE. THE SHEETS WITH THE
 APPROVED ASSEMBLY AND LIMITATIONS ARE MISSING. THE
 APPROVED ASSEMBLY, THE FASTENING OPTION, THE DESIGN
 PRESSURE AND RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING THAT WILL BE USED ARE REQUIRED TO BE
 SPECIFIED.
  
 12)PRODUCT APPROVAL FL4904 FOR THE MASONITE
 INTERNATIONAL EXTERIOR DOORS IS OK FOR THE SINGLE
 INSWING DOOR. HOWEVER, THE DESIGN PRESSURES ARE TOO LOW
 FOR THE NON-IMPACT RATED GLAZED DOUBLE DOORS. WHEN
 MULTIPLE PRODUCT APPROVALS FOR THE SAME ITEMS ARE
 SUBMITTED IT IS HELPFUL IF THE SPECIFIC ITEM TO WHICH
 IT APPLIES IS NOTED THE PRODUCT APPROVAL. FAC RULE
 9B-72
  
 13) THE DRAWINGS ATTACHED TO THE COVERSHEET FOR THE PGT
 SINGLE HUNG WINDOWS ARE THE WRONG ONES AND ARE EXPIRED.
 SEE FL 2939-R10. FAC RULE 9B-72
  
 14) DUE TO THE REVISIONS TO THE PLANS, THE PRODUCT
 APPROVALS FOR THE ROOF TILE NO LONGER APPLY. PLEASE
 REMOVE THEM FROM THE SUBMITTALS.
  
 15) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 ANCHOR TYPE, ANCHOR SPACING, EDGE DISTANCE, ETC. FBC
 301.2.1.2SEE SAMPLE INSTALLATION SCHEDULE ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-08 Cont ID  
Sent By rmcdouga Date 2007-11-08 Time 12:57 Rev Time 0.00
Received By rmcdouga Date 2007-11-08 Time 12:57 Sent To P
Notes
2007-11-08 16:58:082004 FBC W/2007 REVISIONS
 TWO STORY ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. NOTE: WORK ON THE PROJECT MUST
 START WITHIN 90 DAYS OF THE DATE THE NOC IS RECORDED.
  
 3)SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF
 THE ADDITION AND THE DISTANCE TO PROPERTY LINES. FBC
 106.3.5* CITY AMENDMENTS.
  
 4) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
 IF THE DISTANCE FROM THE ADDITION TO THE PROPERTY LINE
 IS LESS THAN 6 FEET, SPECIFY THE DISTANCE TO STRUCTURES
 ON ADJACENT PROPERTY.
  
 5)SUBMIT ENERGY CALCULATIONS FOR THE ADDITION. THE
 FORMS ARE REQUIRED TO BE SIGNED BY THE OWNER/AGENT. SEE
 FBC CHAPTER 13.
  
 6) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, FLOOR
 FRAMING PLAN AND SHOP DRAWINGS FOR THE HAMBRO FLOOR
 SYSTEM. FBC 106.1.2* CITY AMENDMENTS
  
 7) SHOP DRAWINGS WILL BE REQUIRED FOR THE GUARD RAILS
 AT THE BALCONY SHOWING COMPLIANCE WITH R312. FBC
 106.1.2* CITY AMENDMENTS
  
 8) SPECIFY THE WIND EXPOSURE CATEGORY ON THE PLANS.
 R301.2.1.4
  
 9) THE WINDLOAD SCHEDULE ON SHEET 2 LISTS THE SAME
 PRESSURES FOR ROOF ZONES 2 AND 3. PLEASE CORRECT. SEE
 TABLE R301.2(2).
  
 10)THE ROOF ZONE DIAGRAM ON SHEET 2 DOES NOT INDICATE
 ROOF ZONE 3 AT THE ROOF CORNERS. PLEASE CORRECT. SEE
 FIGURE R301.2(8)ASCE7-02 ALLOWS ROOF ZONE 3 TO BE
 TREATED AS ZONE 2 IF A PARAPET EQUAL TO OR GREATER THAN
 3 FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF.
 THIS IS NOT SHOWN ON THE PLANS.
  
 11) SPECIFY THE ROOF SHEATHING NAIL SPACING FOR ROOF
 ZONE 3 0N THE SCHEDULE ON SHEET 2.ROOF SHEATHING IS
 REQUIRED TO BE FASTENED IN ACCORDANCE WITH SECTION
 R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL
 CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED
 TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. SPACING OF RING-SHANK FASTENERS SHALL BE 4
 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1.
  
 12) SPECIFY THE ROOF PITCH OF THE NEW SLOPED ROOF AREA.
 FBC 106.1* CITY AMENDMENTS
  
 13) SPECIFY THE SIZE AND LOCATIONS OF THE ROOF SCUPPERS
 AND OVERFLOW SCUPPERS. R903.4 AND R903.4.1
  
 14) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 15) THE WALL SECTION DETAIL 'A' ON SHEET 3 AT THE ROOF
 PARAPET DOES NOT CORRESPOND WITH THE ROOF FRAMING PLAN
 OR THE ELEVATIONS. PLEASE CORRECT.
  
 16) PROVIDE STRUCTURAL DETAILS FOR THE SLOPED AND FLAT
 ROOF OVER THE NEW MASTER BEDROOM. FBC 106.1* CITY
 AMENDMENTS
  
 17) FIREBLOCKING IS REQUIRED WHERE THE SECOND FLOOR
 WALLS AND CEILING MEET. PLEASE INDICATE ON THE WALL
 DETAIL 'A'.R602.1.2 FIREBLOCKING REQUIRED.
 FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED
 DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO
 FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND
 BETWEEN A TOP STORY AND THE ROOF SPACE.
  
 18) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE ROOF TILES. FBC 106.1* CITY AMENDMENTS AND
 R905.1
  
 19) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 21) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 22) SUBMIT PRODUCT APPROVALS FOR THE TILE AND FLAT ROOF
 COVERINGS, STRUCTURAL WINDOW MULLIONS, IN-SWING GLAZED
 FRENCH DOORS, IN-SWING PANEL DOOR AND STORM PANELS. FAC
 RULE 9B-72
  
 23) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE,
 ANCHOR SPACING, EDGE DISTANCE, ETC. SEE ATTACHED
 SAMPLE. FBC R301.2.1.2
  
 24) THE INFORMATION SUBMITTED FOR THE CENTURY SPECIALTY
 WINDOWS IS NOT ACCEPTABLE. SEE FAC RULE 9B-72. THE
 DESIGN PRESSURES FOR THIS WINDOW ARE TOO LOW. SEE PLANS
 FOR REQUIRED COMPONENT AND CLADDING PRESSURES. FBC
 TABLE R301.2(2)
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-10 Cont ID  
Sent By btrobaug Date 2008-06-10 Time 10:54 Rev Time 0.00
Received By btrobaug Date 2008-06-10 Time 10:45 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By btrobaug Date 2008-02-22 Time 11:47 Rev Time 0.00
Received By btrobaug Date 2008-02-22 Time 10:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-30 Cont ID  
Sent By btrobaug Date 2007-10-30 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2007-10-30 Time 07:46 Sent To M
Notes
2007-10-30 08:54:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET 4-4 , UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} INDICATE THE SERVICE CONDUCTOR SIZE AND NUMBER FOR
 THE FEED TO THE DISCONNECT FROM THE METER.310.16,
 250.2. 2005 NEC.
  
 2} THE PANEL SCHEDULE/LOAD CALCULATION ONLY LISTS ONE
 SMALL APPLIANCE CIRCUIT. A MINIMUM OF TWO ARE REQUIRED
 PER 210.11(C)(1).
  
 3} THERE IS A MECHANICAL PERMIT APPLIED FOR BUT NO
 MECHANICAL PLANS SUBMITTED. INDICATE IF ANY OF THE
 MECHANICAL WIRING IS PART OF THIS PERMIT. THE
 DISCONNECTS AT THE CONDENSING UNIT DO NOT COMPLY WITH
 THE CLEARANCE REQUIREMENTS OF 110.26.AHU #1 AND #2 IN
 THE CLOTHES CLOSETS MAY BE IN VIOLATION OF 422.17 AND
 240.24(D) IF OVERCURRENT PROTECTION IS PRESENT IN THE
 CLOSET.
  
 4} THE TITLE BLOCK ON THIS SHEET IS INDISCERNIBLE.
 106.1.1 FBC AS AMENDED.
  
 5} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-13 Cont ID  
Sent By adarroug Date 2009-01-13 Time 08:44 Rev Time 0.00
Received By adarroug Date 2009-01-13 Time 08:44 Sent To B
Notes
2009-01-13 08:44:57TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 10:23 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 10:23 Sent To M
Notes
2008-12-30 10:23:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 09:57 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 09:57 Sent To B
Notes
2008-11-19 09:57:48TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 11:12 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 11:12 Sent To Z
Notes
2008-06-04 11:13:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-13 Cont ID  
Sent By adarroug Date 2008-02-13 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-02-13 Time 09:18 Sent To Z
Notes
2008-02-13 09:18:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-09 Cont ID  
Sent By mperson Date 2007-11-09 Time 16:40 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 16:11 Sent To  
Notes
2007-10-26 16:12:08TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 11:58 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 11:46 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-10 Cont ID  
Sent By tgordon Date 2008-06-10 Time 16:48 Rev Time 0.30
Received By tgordon Date 2008-06-10 Time 16:48 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 11:53 Rev Time 0.35
Received By tgordon Date 2008-02-25 Time 11:53 Sent To B
Notes
2008-02-25 12:00:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R,
 SEE 2004 FBC 13-600.3.C (12-8-06 REVISION).
  
 2) WHEN SUBMITTING REVISED ENERGY CALCULATIONS THEY
 NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) PROVIDE FOR RETURN AIR TO THE MASTER BEDROOM SUITE,
 SEE 2004 FBC/R M1604.2.
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-30 Cont ID  
Sent By tgordon Date 2007-10-30 Time 14:20 Rev Time 0.25
Received By tgordon Date 2007-10-30 Time 14:20 Sent To P
Notes
2007-10-30 14:24:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS, SEE WPB AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By mperson Date 2008-06-11 Time 08:13 Rev Time 0.00
Received By mperson Date 2008-06-11 Time 08:13 Sent To B
Notes
2008-06-11 08:24:26******PROVISO******
 A} PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN
 THE INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 B} REVISION WILL BE REQUIRED ON THE FLOOR PLAN FOR THE
 BAR SINK LOCATION BEING INDICATED ON PLUMBING RISER
 "B". PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C} CLEANOUTS AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER SHALL BE TWO-WAY CLEANOUTS. PER FBC-2004
 PLUMBING SECTION 708.3.5.
  
 D} CLEANOUT REQUIRED AT THE BASE OF THE 3 INCH STACK
 FOR PLUMBING RISER "B". PER FBC-2004 PLUMBING SECTION
 708.3.4.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By mperson Date 2008-02-25 Time 10:22 Rev Time 0.00
Received By mperson Date 2008-02-25 Time 10:22 Sent To M
Notes
2008-02-25 11:19:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 1. SHEET 3 PLUMBING RISER "A": THE WASHING MACHINE
 WASTE STACK NEEDS TO BE 3". PER FBC PLUMBING SECTION,
 *406.3 WASTE CONNECTION.
  
 2. SHEET 3 PLUMBING RISER "A": THE 1ST FLOOR NEW BATH
 WATER CLOSET AND THE 2ND FLOOR MASTER BATH NEW TUB ARE
 NOT VENTED. PER FBC PLUMBING SECTION *901.2.1 VENTING
 REQUIRED.
  
 3.SHEET 3 PLUMBING RISER "A": ONLY FIXTURES WITHIN TWO
 BATHROOM GROUPS LOCATED ON THE SAME FLOOR ARE PERMITTED
 TO BE VENTED BY THE VERTICAL WET VENT. THE DOUBLE BOWL
 KITCHEN SINK IS NOT ALLOWED TO DRAIN INTO THIS. PER FBC
 PLUMBING SECTION 909.1.1 VERTICAL WET VENT.
 THE KITCHEN SINK CAN USE AN AIR ADMITTANCE VALVE. PER
 FBC PLUMBING SECTION *917.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By mperson Date 2007-11-09 Time 16:29 Rev Time 0.00
Received By mperson Date 2007-11-09 Time 16:29 Sent To PC
Notes
2007-11-09 16:34:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS REFLECTING THE PROPOSED FLOOR PLUMBING.
  
 **NOTE: SHEET 3 RISER DIAGRAMS ARE NOT ISOMETRIC AND
 THEY DON'T REFLECT THE FLOOR PLAN.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By choops Date 2008-06-09 Time 11:03 Rev Time 0.00
Received By choops Date 2008-06-09 Time 11:03 Sent To E
Notes
2008-06-09 11:03:50***APPROVED - RESUB #2 (RESTAMPED PLANS)***
  
 PROVISOS:
  
 1)ADDITIONS MUST MAINTAIN A MINIMUM SEPARATION
 DISTANCE OF 6' FROM THE EXISTING ACCESSORY STRUCTURES.
  
 2)BALCONIES OR OTHER STRUCTURAL INTRUSIONS SHALL NOT
 PROJECT MORE THAN 3' INTO A REQUIRED SETBACK.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-14 Cont ID  
Sent By choops Date 2008-02-14 Time 09:36 Rev Time 0.00
Received By choops Date 2008-02-14 Time 09:36 Sent To E
Notes
2008-02-14 09:38:30***APPROVED - RESUB #1***
  
 PROVISOS:
  
 1)ADDITIONS MUST MAINTAIN A MINIMUM SEPARATION
 DISTANCE OF 6' FROM THE EXISTING ACCESSORY STRUCTURES.
  
 2)BALCONIES OR OTHER STRUCTURAL INTRUSIONS SHALL NOT
 PROJECT MORE THAN 3' INTO A REQUIRED SETBACK.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By choops Date 2007-10-29 Time 11:48 Rev Time 0.00
Received By choops Date 2007-10-29 Time 11:48 Sent To E
Notes
2007-10-29 11:57:02***FAILED***
  
  
 1)PURSUANT TO SECTION 94-74(A)(3) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
  
 A.FRONT: 25 FEET;
 B.CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C.REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER
 IS LESS;
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING THE
 LOCATION OF THE PROPOSED ADDITION WITH DIMENSIONS AND
 SETBACK DIMENSIONS TO ALL PROPERTY LINES.
  
 2)PURSUANT TO SECTION 94-305(B)(2) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:OVERHANGS SHALL NOT PROJECT MORE THAN 3'
 INTO ANY REQUIRED SETBACK.INDICATE ALL OVERHANG
 DIMENSIONS FROM WALL TO OUTERMOST POINT OF ROOF.
  
 3)PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.INDICATE SETBACK
 DIMENSIONS FROM THE PROPERT LINES TO ANY PROPOSED/MOVED
 A/C EQUIPMENT.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720