| Plan Review Stops For Permit 07100743 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-01-07 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-01-07 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2008-01-07 14:35:09 | PAGE C-1 INCLUDED WITH THE PLANS REPRESENT THE INTERIOR | | | ROAD AND THE LOCATION JOB IS INDEED EAST OF N JOG RD AT | | | 5920 N JOG RD. | | | | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | | |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-12-31 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-12-31 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2007-12-31 11:27:51 | BASED ON THE LOCATION MAP THE PERMIT SHOULD READ 6501 N | | | JOG RD ,PLEASE MAKE CORRECTIONS ON THE SITE PLANS AND | | | APPLICATION . | | | | | | QUESTIONS/COMMENTS: | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-28 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-28 |
Time |
17:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-09 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-09 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2007-11-09 16:30:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS471.025.SOME SHEETS WERE NOT SIGNED OR | | | SEALED, OTHERS NOT SEALED BUT SIGNED AND DATED.PLEASE | | | SUBMIT ALL SHEETS SIGNED, SEALED AND DATED. | | | | | | 2.S1, INCLUDE 2007 AMENDMENTS IN GOVERNING CODE | | | EFFECTIVE 7/1/2007. | | | | | | 3.PROVIDE TWO ORIGINAL SIGNED, SEALED, DATED SETS OF | | | THE SOILS REPORTS REFERRED TO ON S2. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-12-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-22 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-22 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2007-12-22 13:50:31 | ALL CONNECTIONS ON 5KV SHALL BE 90C RATED PER 110.14, | | | VEROFIED BY THE ENGINEER ON E-MAIL DATED 12/20/07 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-26 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-26 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2007-11-26 16:38:21 | ** DENIED** | | | | | | | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006/2007 REVISIONS | | | TO THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006/07 REVISIONS | | | 2005 NFPA-70 | | | | | | 2) NOTE:PLEASE SEE ADDRESS OF LOCATION AS APPLIED IS | | | 7501 JOG RD., YET OUR SYSTEM AS APPLIED ADDRESS IS | | | 6501. THE PLANS AND DOCUMENTS HAVE BEEN ROUTED TO | | | ADDRESSING FOR REVIEW AND COORDINATION. PLEASE KNOW | | | ONCE THE ADDRESS HAS BEEN DETERMINED; PLEASE ADJUST | | | TITLE BLOCKS OF PLANS FOR LOCATION. | | | FAC 61G15-23.002, FBC ADMIN SECTION 106.1.2, 110.2 | | | PLEASE BE SURE TO ADJUST ALL PLANS, AND SUPPORTING | | | DOCUMENTATION. | | | | | | 3) NOTE: PLEASE SEE THE CONDUCTORS TO NEW 1K | | | TRANSFORMER ARE ONLY RATED FOR 175AMPS YET OVER CURRENT | | | PROTECTION IS 200AMPS. | | | PLEASE SEE 240.4, 310.16, AND 240.6 AND ADJUST. (3/0 | | | MIN. REQUIRED). | | | 110.14. | | | | | | 4) NOTE: PLEASE SEE PLANS ON E-2 MENTIONS 4/0 FOR | | | GROUND LOOP HOWEVER SOME SECTIONS ON E-4 ARE 2/0 AND | | | 4/0? | | | PLEASE CLARIFY. | | | 250.50, 250.64 | | | | | | PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING | | | REVIEWER. | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-08 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-08 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-27 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-27 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2007-11-27 12:45:53 | *****UNSAT***** | | | | | | 1.PLEASE EXPLAIN/CLARIFY THE FLARE CONTROL | | | PANEL/FLARE SKID AND HOW IT WOULD IMPACT FIRE AND LIFE | | | SAFETY CONCERNS. | | | | | | 2.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-01-16 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-01-16 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-01-16 11:06:19 | MAIN GAS LINE FROM LANDFILL TO COMPRESSOR. ALL | | | CONNECTIONS FROM COMPRESSOR, DRYER, CHILLER TO BE | | | PREFABED FLANGED SECTIONS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-07 |
Time |
18:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-07 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2007-12-07 19:01:43 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | 1. MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT | | | OUTLET PRESSURE IS THE PIPING DESIGNED FOR DOWNSTREAM | | | OF THE COMPRESSOR.--PLEASE INDICATE THE METHOD OF | | | PIPING THE DIFFERENT SKID EQUIPMENT, SUCH AS THE | | | COMPRESSOR, DRYER, FLARE ETC. IF THE METHOD IS WELD | | | PIPE, THEN THE WELDING PROCEDURE AND WELDING | | | CERTIFICATIONS WILL BE REQUIRED PRIOR TO ISSUING THE | | | PERMIT. A PICTURE IDENTIFICATION WILL BE REQUIRED ALONG | | | WITH THE CERTIFICATIONS. SECTION 106.1.2. | | | | | | 2. PLEASE PROVIDE MANUF. SPECIFICATION SHEETS FOR THE | | | COMPRESSOR, DRYER, ETC. SECTION 106.1.2. | | | | | | 3. THE ADDRESS ON THE APPLICATION DOES NOT REFLECT THE | | | ADDRESS IN OUR SYSTEM. ONCE THE CORRECT ADDRESS IS | | | DETERMINED, ALL PLAN TITLE BLOCKS AND SHALL SHOW THE | | | CORRECT ADDRESS PER SECTION 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-12-20 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-12-20 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2007-12-20 18:00:34 | SENT TO COMMERCIAL BOARD # 59 MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-10 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-25 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2007-11-13 09:28:01 | TO "COMM" BD#16 | | 2007-10-25 14:27:05 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-01-16 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-01-16 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2008-01-16 11:04:06 | CONDENSATE LINE FROM DRYER TO DRAIN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-12-27 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-12-27 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-10-30 |
Time |
19:16 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-10-30 |
Time |
19:16 |
Sent To |
|
|
| Notes |
| 2007-10-30 19:18:51 | FAILED | | | | | | 1) THE PERIMETER OF THE GAS COMPRESSION SKID SYSTEM | | | SHALL BE SCREENED BY HEDGE MATERIAL. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|