Plan Review Details - Permit 07100733
| Plan Review Stops For Permit 07100733 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-11-19 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-11-01 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2007-11-19 15:05:26 | PERMIT ASSIGNED TO THE LOWEST PCN = 74434322140030100, | | | BASED ON THE RECORDED UNITY OF TITLE FOR ALL THE | | | FOLLOWING PARCELS: | | | 74434322140030100,74434322140030110,74434322140030120, | | | 74434322140030130,74434322140030161,74434322140030180. | | | | | | QUESTIONS/COMMENTS PLEASE CONTACT : | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-08 |
Time |
12:49 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-05-08 |
Time |
12:49 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-06 |
Time |
07:18 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-05-06 |
Time |
07:18 |
Sent To |
PC |
|
| Notes |
| 2008-05-06 07:21:34 | STRRUCTURAL REVISIONS | | | REV# 2 DATED MARCH 18/2008 | | | REV# B DATED APRIL 15/2008 | | | REV# 3 DATED APRIL22/2008 | | | | | | NOTE: ENERGY FORMS AND CALCULATIONS SUBMITTED : | | | NOT TO REVIEWED UNDER STRUCRAL PERMIT, MUST BE | | | SUBMITTED UNDER THE TOTAL BUILDING PERMIT # 08010249 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-17 |
Time |
14:13 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-01-17 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2008-01-18 10:25:04 | | | | III CITY PLAZA | | | HYATT PLACE | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 07100733 | | | ADDRESS: 295 LAKEVIEW AVE | | | CONT: KAST CONSTRUCTION | | | TELL # (561) 718-6141 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.106.1.1 ADMINISTRATIVE CODE/ 06. | | | | | | BUILDING PROVISOS: | | | | | | | | | 105.13. SPECIAL STRUCTURAL ONLY PERMIT | | | WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A | | | BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH | | | PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER | | | DISCRETION, ISSUE A SPECIAL PERMIT FOR THE STRUCTURE | | | ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR. | | | THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT | | | HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT | | | FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT | | | CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE | | | PROVISIONS OF THE TECHNICAL CODE. | | | | | | 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL | | | BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT | | | THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT | | | TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY | | | OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL | | | OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 109.3.10.1 HURRICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW | | | CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO | | | REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION | | | SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE | | | DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR | | | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS | | | WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED | | | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN | | | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO | | | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE | | | PURSUANT TO SECTION 113 OF THIS CHAPTER. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-04 |
Time |
15:33 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-01-04 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2008-01-04 15:46:54 | HYATT PLACE | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07100733 / STRUCTURAL PERMIT ONLY | | | ADD: 295 LAKEVIEW DRIVE | | | CONT: KAST CONSTRUCTION | | | TEL: (561)# 718-6141 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) INFORMATIONAL,PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE2007 REVISIONS. | | | | | | 1E) CONFIRMED/ COMPLIED. | | | | | | 2) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION | | | SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A | | | SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE | | | SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | 3) COMPLIED | | | | | | 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. | | | | | | 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. | | | I | | | | | | 6) BUILDING PROVISO:105.13. SPECIAL STRUCTURAL ONLY | | | PERMIT WHEN APPLICATION FOR A PERMIT TO ERECT OR | | | ENLARGE A BUILDING HAS BEEN FILED, & PENDING ISSUANCE | | | OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER | | | DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION | | | OR STRUCTURAL ONLY PERMIT, UPON WRITTEN REQUEST OF THE | | | OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL | | | PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT | | | ASSURANCE THAT A PERMIT FOR THE REMAINDER OF THE WORK | | | WILL BE GRANTED AND THAT CORRECTIONS WILL NOT BE | | | REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE | | | TECHNICAL CODE. | | | | | | NEW COMMENTS: | | | 7) REVISION # 4 INDICATES ON THE ARCHITECTURAL SHEET | | | A-101A COLUMN LINE A: 11.9 INDICATING A SINGLE COLUMN | | | VERSES STRURTURAL SHEET S-101.A NOT PICKING UP THE | | | REVISION INDICATING COLUMNS C-73 & C-93, PLEASE | | | CORRELATE. | | | | | | 8) PROVISO: NOTE THIS WILL NOT EFFECT THE STRUCTURAL | | | PERMIT BUT WILL EFFECT THE BUILDING PERMIT. ON THE EAST | | | SIDE OF THE BUILDING PLAN A-100 & A-101B BOTH INDICATE | | | THE GENERATOR ROOM VENTING (INTAKE) ON THE EAST SIDE OF | | | THE BUILDING . THE PROPERTY LINE IS APPROXIMATELY 1'0" | | | AWAY. TABLE 704.8 ALLOWABLE OPENINGS DOES NOT ALLOW ANY | | | OPENINGS WITHIN 3'-0" OF THE PROPERTY LINE. PLEASE ALSO | | | NOTE THERE IS NO EXHAUST FOR THE GENERATOR INDICATED, | | | THESE ITEMS WILL NEED TO BE ADDRESSED UNDERTHE BUILDING | | | PERMIT. | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-16 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2007-11-16 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2007-11-16 10:48:59 | HYATT PLACE | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07100733 | | | ADD: 295 LAKEVIEW DRIVE | | | CONT: KAST CONSTRUCTION | | | TEL: (561)# 718-6141 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) INFORMATIONAL,PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE2007 REVISIONS. | | | | | | 1E) PLEASE SUBMIT A COPY OF THE PAID IMPACT FEE | | | RECEIPT, (WHITE & BLUE DOCUMENT) THE DOCUMENT SUBMITTED | | | INDICATES A BALANCE OF$286,308.00. | | | | | | 2) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION | | | SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A | | | SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE | | | SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER | | | INFORMATION BEFORE | | | THE PERMIT MAY BE ISSUED. | | | | | | 3) 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLEASE | | | SUBMIT THE ARCHITECTURAL FLOOR PLANS AND FOR THE ROOF | | | DECK AND OR ELEVATOR PENTHOUSE OR MECHANICAL ROOMS. | | | NOTE UNDER THE STRUCTURAL ONLY PERMIT , THE PLANS | | | SUBMITTED CAN NOT BE CHECKED FOR TABLE 601 EXTERIOR | | | BEARING WALLS, TABLE 602 EXTERIOR NON-BEARING WALLS AND | | | TABLE 704.8 ALLOWABLE EXTERIOR WALL OPENINGS. | | | | | | 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL | | | BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT | | | THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT | | | TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY | | | OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL | | | OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW | | | CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO | | | REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION | | | SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE | | | DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR | | | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS | | | WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED | | | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN | | | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO | | | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE | | | PURSUANT TO SECTION 113 OF THIS CHAPTER. | | | | | | 6) BUILDING PROVISO:105.13. SPECIAL FOUNDATION OR | | | STRUCTURAL ONLY PERMIT WHEN APPLICATION FOR A PERMIT TO | | | ERECT OR ENLARGE A BUILDING HAS BEEN FILED, & PENDING | | | ISSUANCE OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT | | | HIS/ HER DISCRETION, ISSUE A SPECIAL PERMIT FOR THE | | | FOUNDATION OR STRUCTURAL ONLY PERMIT, UPON WRITTEN | | | REQUEST OF THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH | | | A SPECIAL PERMIT IS PROCEEDING AT HIS OR HER OWN RISK | | | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE REMAINDER | | | OF THE WORK WILL BE GRANTED AND THAT CORRECTIONS WILL | | | NOT BE REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE | | | TECHNICAL CODE. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-20 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-20 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2007-12-20 14:18:30 | GROUNDING ELECTRODE SYSTEM FOR STRUCTURE AND | | | FOUNDATION. | | | | | | ELECTRICAL PERMIT WILL BE REQUIRED ONCE THE STRUCTURAL | | | ONLY PERMIT IS ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-21 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-21 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2007-11-21 13:32:40 | ** DENIED REVIEW ** | | | | | | ** THE BELOW COMMENTS WERE PREVIOUSLY GIVEN IN MEETINGS | | | AND PHONE CONVERSATIONS. | | | | | | 1) NOTE:PLEASE SEE COVER SHEET WHICH REFLECTS BOTH | | | THE 2002 NATIONAL ELECTRICAL CODE AND 2005 NATIONAL | | | ELECTRICAL CODE. | | | AS OF DECEMBER 8TH, 2006 THE STATE HAS ADOPTED THE | | | 2005. | | | PLEASE SEE THAT OTHER RELEVANT CODES SHALL BE ON | | | PLANS. | | | 2002 NFPA-72 | | | 2002 NFPA-110 | | | 2003 NFPA-20(IF IN DESIGN FOR BUILDING. | | | | | | 2) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL GROUNDING | | | ELECTRODE SYSTEM AND SIZING FOR MINIMUM ATTACHMENT | | | LOCATIONS PER 250.50 | | | | | | 3) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS MEETINGS | | | THE LOCATION OF THE GENERATOR WITH AIR INTAKE AND | | | EXHAUST ON ZERO LOT LINE NEEDS TO BE LOOKED AT FOR CODE | | | COMPLIANCE. | | | AS SHOWN THE LOCATION FOR BOTH OF THESE ITEMS MAY | | | CHANGE STRUCTURAL COMPONENTS. | | | | | | 4) NOTE: PLEASE SEE NEC 680.26 FOR EQUAL-POTENTIAL | | | BONDING OF POOL/SPA AREAS AND ALL STEEL AND OTHER METAL | | | WITHIN 5 FT OF POOL. | | | PLEASE KNOW AS SOME OF THESE STRUCTURAL ELEMENTS APPEAR | | | TO BE DONE AT THIS TIME, PLEASE INCLUDE DETAILS FOR | | | THIS. | | | | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-01-16 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-01-16 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2008-01-16 14:20:57 | I STAMPED & SIGN 3 SETS,MR. JASON GUNTHER DID NOT | | | REVISE SHEET 5 OF 10, THE 4TH SET, THIS SHEET 5 OF 10 | | | HAS DEC 12, UNREVISED SHEET.THEREFORE SET 4,WAS NOT | | | STAMPED & SIGNED. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-01-08 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-01-08 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2008-01-08 14:52:18 | ***FAILED**** | | | | | | SHEET EX-1 SITE LOGISTICS PLAN IS NOT SEALED &SIGNED BY | | | MR. GUNTHER, P.E. PLEASE MAKE SURE ALL SHEETS ARE | | | SEALED & SIGNED BY P.E. WHEN YOU RESUBMIT THE SET NEXT | | | TIME. | | | | | | I THINK YOU REVISED THIS SHEET FOR POLLUTION PREVENTION | | | FOR VIBRO-FLOATATION PERMIT. PLEASE USE THATREVISED | | | SHEET IN THIS SET. WE TALKED ABOUT IN VIBRO-FLOATATION | | | PERMIT THAT SILT FENCE SHOULD BE INSTALLED ALL AROUND | | | THE SITE INCLUDING SOUTH & WEST. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-11-27 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-11-27 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2007-11-27 08:48:06 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | | | | 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING | | | SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS | | | DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT | | | OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST | | | PARTICLES. | | | | | | ORDINANCE NO. 4060-07: | | | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | | FOLLOWING: | | | | | | 1. EROSION CONTROL, AND | | | 2. LAND STABILIZATION | | | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | | | 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | | SERVICES, PHONE# 494-1040 | | | | | | 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | | | 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA | | | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST | | | FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE | | | ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. | | | | | | 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | | PROVIDE A COPY OF THESE CALCULATIONS. | | | | | | 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | | THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL | | | ENVRONMENTAL REPORT. | | | | | | 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | | FLOODED AND HAVE ENOUGH DRAINS. | | | | | | 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | | WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE | | | APPROVED FROM 100045TH STREET ENGINEERING SERVICES. | | | | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-17 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-17 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2008-01-17 13:09:37 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS G-002 AND AC-101 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-11 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-11 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2008-01-11 19:01:40 | *****UNSAT***** | | | | | | 01.SOME PLAN SHEET LIST LAKEVIEW AS A DRIVE, SHOULD | | | BE LISTED AS AN AVENUE.SEE SHEETS -A-100B THRU | | | A-100E, A-102A THRU E-302, SHEET #4 THRU S-301 | | | | | | 02.ON SHEET G-000 UNDER BUILDING INFORMATION AND | | | CODES, PLEASE EXPLAIN REFERENCE TO NFPA 2002.NFPA | | | 101 - LIFE SAFETY CODE - 2003 EDITION, AND THE FLORIDA | | | FIRE PREVENTION CODE - 2004 EDITION,SHALL BE | | | REFERENCED | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-04 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-04 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-12-04 16:11:07 | *****DENIED***** | | | | | | 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET.ALSO, SOME PLAN | | | SHEET LIST LAKEVIEW AS A DRIVE, SHOULD BE LISTED AS AN | | | AVENUE. | | | | | | 02.ON SHEET G-000 UNDER BUILDING INFORMATION AND | | | CODES, PLEASE EXPLAIN REFERENCE TO NFPA 2002. | | | | | | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 04.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY | | | OR THE VICINITY THEREOF (INCLUDING ROADWAYS, ALLEYS, | | | FIRE LANES). | | | | | | 05.IN ALL BUILDINGS OVER ONE STORY IN HEIGHT, AT | | | LEAST ONE STAIRWAY SHALL BE PROVIDE IN AN USABLE | | | CONDITION AT ALL TIMES. | | | | | | 06.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE | | | BUILDING REACHES THREE STORIES OR THIRTY FEET IN | | | HEIGHT.THE STANDPIPES SHALL BE PROVIDED WITH | | | CONSPICUOUSLY MARKED AND READILY ACCESSIBLE FIRE | | | DEPARTMENT CONNECTIONS ON THE OUTSIDE OF THE BUILDING | | | AT THE STREET LEVEL AND HAVE AT LEAST ONE STANDARD HOSE | | | OULET AT EACH FLOOR. | | | | | | 07.ILLUSTRATE FIRE HYDRANT LOCATIONS ON SITE PLAN. | | | | | | 08.WHERE/IF UNDERGROUND WATER MAINS AND FIRE HYDRANTS | | | ARE TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, | | | AND IS SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | 09.THERE SHALL BE NO DELAY IN THE INSTALLATION OF | | | FIRE PROTECTION EQUIPMENT. | | | | | | 10.THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE | | | PLACED IN SERVICE AS SOON AS PRACTICABLE. | | | | | | 11.THE PROJECT SITE ADDRESS SHALL BE TEMPORARILY | | | POSTED PRIOR TO, AND DURING CONSTRUCTION, OR UNTIL SUCH | | | TIME THAT THE PERMANANT NUMERICAL ADDRESS IS DISPLAYED | | | ON THE EXTERIOR ELEVATION WHICH FRONTS LAKEVIEW | | | AVENUE. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-29 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-29 |
Time |
10:17 |
Sent To |
B |
|
| Notes |
| 2008-04-29 10:18:02 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-16 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-16 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2008-01-16 12:41:23 | TO "COMM" BD#38 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-12-27 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-12-27 |
Time |
16:26 |
Sent To |
ENG |
|
| Notes |
| 2007-12-27 16:27:28 | TO RASIK CHOKSHI'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-17 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-17 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2007-12-17 15:26:52 | TO "COMM" BD#16/PLANS ON RACK/1 ROLL AND BINDERS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-04 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-25 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2007-11-20 16:04:19 | TO "COMM" BD#63 | | 2007-10-25 11:18:38 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-01-16 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-01-16 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2008-01-16 15:49:02 | ZONING REVIEW: PASSED | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-12-21 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-12-21 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-12-21 10:36:35 | ZONING REVIEW: FAILED | | | | | | **STRUCTURE ONLY PERMIT** | | | | | | - PLEASE NOT THAT ARCHITECTURAL, ENGINEERING, AND | | | STRUCTURAL DRAWINGS ARE NOT COORDINATED. | | | - ENTRY COLUMN CORRECTLY INDICATED IN ARCHITECTURAL | | | SITE PLAN IS INCORRECT ON STRUCTURAL DRAWINGS S101-A, | | | S102-A ETC; PLEASE MAKE SURE STRUCTURAL DRAWINGS | | | ACCURATELY REFLECT ARCH SITE PLAN. | | | - COMMENT ALSO APPLIES TO ENGINEERING DRAWINGS WHICH DO | | | NOT APPEAR TO HAVE BEEN UPDATED TO REFLECT MOST RECENT | | | SITE PLAN. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-05 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-12-05 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-12-05 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2007-12-05 15:15:06 | ZONING REVIEW: FAILED | | | | | | 1) ENTRY AND ASSOCIATED STRUCTURE SHALL BE MODIFIED TO | | | MATCH APPROVED SITE PLAN. THIS INCLUDES RELOCATION OF | | | COLUMN. | | | 2) SIDEWALK DIMENSIONS SHOULD BE PROVIDED ON ALL SITE | | | AND GROUND FLOOR PLANS. | | | 3) PLEASE REMOVE "TRASH PICK UP AREA" NOTE ON FLOOR | | | PLAN WHERE ARE IS LOCATED ON SIDEWALK ALONG OLIVE | | | AVENUE. | | | 4) DRIVEWAY ALONG LAKEVIEW SHALL BE MODIFIED TO MATCH | | | APPROVED SITE PLAN. THIS INCLUDES NARROWING THE DRIVE | | | FOR ONE LANE OF TRAFFIC. | | | | | | MATT FLIS - 822-1445 |
|
|
|