Plan Review Details - Permit 07100733
Plan Review Stops For Permit 07100733
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-11-19 Cont ID  
Sent By lursu Date 2007-11-19 Time 15:01 Rev Time 0.00
Received By lursu Date 2007-11-01 Time 11:42 Sent To  
Notes
2007-11-19 15:05:26PERMIT ASSIGNED TO THE LOWEST PCN = 74434322140030100,
 BASED ON THE RECORDED UNITY OF TITLE FOR ALL THE
 FOLLOWING PARCELS:
 74434322140030100,74434322140030110,74434322140030120,
 74434322140030130,74434322140030161,74434322140030180.
  
 QUESTIONS/COMMENTS PLEASE CONTACT :
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-08 Cont ID  
Sent By jwitmer Date 2008-05-08 Time 12:49 Rev Time 3.33
Received By jwitmer Date 2008-05-08 Time 12:49 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-06 Cont ID  
Sent By jwitmer Date 2008-05-06 Time 07:18 Rev Time 2.22
Received By jwitmer Date 2008-05-06 Time 07:18 Sent To PC
Notes
2008-05-06 07:21:34STRRUCTURAL REVISIONS
 REV# 2 DATED MARCH 18/2008
 REV# B DATED APRIL 15/2008
 REV# 3 DATED APRIL22/2008
  
 NOTE: ENERGY FORMS AND CALCULATIONS SUBMITTED :
 NOT TO REVIEWED UNDER STRUCRAL PERMIT, MUST BE
 SUBMITTED UNDER THE TOTAL BUILDING PERMIT # 08010249

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-17 Cont ID  
Sent By jwitmer Date 2008-01-17 Time 14:13 Rev Time 2.22
Received By jwitmer Date 2008-01-17 Time 14:09 Sent To  
Notes
2008-01-18 10:25:04 
 III CITY PLAZA
 HYATT PLACE
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 07100733
 ADDRESS: 295 LAKEVIEW AVE
 CONT: KAST CONSTRUCTION
 TELL # (561) 718-6141
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.106.1.1 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISOS:
  
  
 105.13. SPECIAL STRUCTURAL ONLY PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE STRUCTURE
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By jwitmer Date 2008-01-04 Time 15:33 Rev Time 2.22
Received By jwitmer Date 2008-01-04 Time 15:33 Sent To  
Notes
2008-01-04 15:46:54HYATT PLACE
  
 BUILDING PLAN REVIEW
 PERMIT: 07100733 / STRUCTURAL PERMIT ONLY
 ADD: 295 LAKEVIEW DRIVE
 CONT: KAST CONSTRUCTION
 TEL: (561)# 718-6141
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL,PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1E) CONFIRMED/ COMPLIED.
  
 2) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3) COMPLIED
  
 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
  
 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 I
  
 6) BUILDING PROVISO:105.13. SPECIAL STRUCTURAL ONLY
 PERMIT WHEN APPLICATION FOR A PERMIT TO ERECT OR
 ENLARGE A BUILDING HAS BEEN FILED, & PENDING ISSUANCE
 OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 OR STRUCTURAL ONLY PERMIT, UPON WRITTEN REQUEST OF THE
 OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL
 PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE REMAINDER OF THE WORK
 WILL BE GRANTED AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE
 TECHNICAL CODE.
  
 NEW COMMENTS:
 7) REVISION # 4 INDICATES ON THE ARCHITECTURAL SHEET
 A-101A COLUMN LINE A: 11.9 INDICATING A SINGLE COLUMN
 VERSES STRURTURAL SHEET S-101.A NOT PICKING UP THE
 REVISION INDICATING COLUMNS C-73 & C-93, PLEASE
 CORRELATE.
  
 8) PROVISO: NOTE THIS WILL NOT EFFECT THE STRUCTURAL
 PERMIT BUT WILL EFFECT THE BUILDING PERMIT. ON THE EAST
 SIDE OF THE BUILDING PLAN A-100 & A-101B BOTH INDICATE
 THE GENERATOR ROOM VENTING (INTAKE) ON THE EAST SIDE OF
 THE BUILDING . THE PROPERTY LINE IS APPROXIMATELY 1'0"
 AWAY. TABLE 704.8 ALLOWABLE OPENINGS DOES NOT ALLOW ANY
 OPENINGS WITHIN 3'-0" OF THE PROPERTY LINE. PLEASE ALSO
 NOTE THERE IS NO EXHAUST FOR THE GENERATOR INDICATED,
 THESE ITEMS WILL NEED TO BE ADDRESSED UNDERTHE BUILDING
 PERMIT.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-16 Cont ID  
Sent By jwitmer Date 2007-11-16 Time 10:41 Rev Time 0.00
Received By jwitmer Date 2007-11-16 Time 10:40 Sent To  
Notes
2007-11-16 10:48:59HYATT PLACE
  
 BUILDING PLAN REVIEW
 PERMIT: 07100733
 ADD: 295 LAKEVIEW DRIVE
 CONT: KAST CONSTRUCTION
 TEL: (561)# 718-6141
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL,PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1E) PLEASE SUBMIT A COPY OF THE PAID IMPACT FEE
 RECEIPT, (WHITE & BLUE DOCUMENT) THE DOCUMENT SUBMITTED
 INDICATES A BALANCE OF$286,308.00.
  
 2) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 3) 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLEASE
 SUBMIT THE ARCHITECTURAL FLOOR PLANS AND FOR THE ROOF
 DECK AND OR ELEVATOR PENTHOUSE OR MECHANICAL ROOMS.
 NOTE UNDER THE STRUCTURAL ONLY PERMIT , THE PLANS
 SUBMITTED CAN NOT BE CHECKED FOR TABLE 601 EXTERIOR
 BEARING WALLS, TABLE 602 EXTERIOR NON-BEARING WALLS AND
 TABLE 704.8 ALLOWABLE EXTERIOR WALL OPENINGS.
  
 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) BUILDING PROVISO:105.13. SPECIAL FOUNDATION OR
 STRUCTURAL ONLY PERMIT WHEN APPLICATION FOR A PERMIT TO
 ERECT OR ENLARGE A BUILDING HAS BEEN FILED, & PENDING
 ISSUANCE OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT
 HIS/ HER DISCRETION, ISSUE A SPECIAL PERMIT FOR THE
 FOUNDATION OR STRUCTURAL ONLY PERMIT, UPON WRITTEN
 REQUEST OF THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH
 A SPECIAL PERMIT IS PROCEEDING AT HIS OR HER OWN RISK
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE REMAINDER
 OF THE WORK WILL BE GRANTED AND THAT CORRECTIONS WILL
 NOT BE REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE
 TECHNICAL CODE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 14:17 Sent To  
Notes
2007-12-20 14:18:30GROUNDING ELECTRODE SYSTEM FOR STRUCTURE AND
 FOUNDATION.
  
 ELECTRICAL PERMIT WILL BE REQUIRED ONCE THE STRUCTURAL
 ONLY PERMIT IS ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2007-11-21 Time 13:16 Sent To  
Notes
2007-11-21 13:32:40** DENIED REVIEW **
  
 ** THE BELOW COMMENTS WERE PREVIOUSLY GIVEN IN MEETINGS
 AND PHONE CONVERSATIONS.
  
 1) NOTE:PLEASE SEE COVER SHEET WHICH REFLECTS BOTH
 THE 2002 NATIONAL ELECTRICAL CODE AND 2005 NATIONAL
 ELECTRICAL CODE.
 AS OF DECEMBER 8TH, 2006 THE STATE HAS ADOPTED THE
 2005.
 PLEASE SEE THAT OTHER RELEVANT CODES SHALL BE ON
 PLANS.
 2002 NFPA-72
 2002 NFPA-110
 2003 NFPA-20(IF IN DESIGN FOR BUILDING.
  
 2) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL GROUNDING
 ELECTRODE SYSTEM AND SIZING FOR MINIMUM ATTACHMENT
 LOCATIONS PER 250.50
  
 3) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS MEETINGS
 THE LOCATION OF THE GENERATOR WITH AIR INTAKE AND
 EXHAUST ON ZERO LOT LINE NEEDS TO BE LOOKED AT FOR CODE
 COMPLIANCE.
 AS SHOWN THE LOCATION FOR BOTH OF THESE ITEMS MAY
 CHANGE STRUCTURAL COMPONENTS.
  
 4) NOTE: PLEASE SEE NEC 680.26 FOR EQUAL-POTENTIAL
 BONDING OF POOL/SPA AREAS AND ALL STEEL AND OTHER METAL
 WITHIN 5 FT OF POOL.
 PLEASE KNOW AS SOME OF THESE STRUCTURAL ELEMENTS APPEAR
 TO BE DONE AT THIS TIME, PLEASE INCLUDE DETAILS FOR
 THIS.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-01-16 Cont ID  
Sent By rchokshi Date 2008-01-16 Time 13:59 Rev Time 0.00
Received By rchokshi Date 2008-01-16 Time 13:59 Sent To  
Notes
2008-01-16 14:20:57I STAMPED & SIGN 3 SETS,MR. JASON GUNTHER DID NOT
 REVISE SHEET 5 OF 10, THE 4TH SET, THIS SHEET 5 OF 10
 HAS DEC 12, UNREVISED SHEET.THEREFORE SET 4,WAS NOT
 STAMPED & SIGNED.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-01-08 Cont ID  
Sent By rchokshi Date 2008-01-08 Time 14:52 Rev Time 0.00
Received By rchokshi Date 2008-01-08 Time 14:39 Sent To  
Notes
2008-01-08 14:52:18***FAILED****
  
 SHEET EX-1 SITE LOGISTICS PLAN IS NOT SEALED &SIGNED BY
 MR. GUNTHER, P.E. PLEASE MAKE SURE ALL SHEETS ARE
 SEALED & SIGNED BY P.E. WHEN YOU RESUBMIT THE SET NEXT
 TIME.
  
 I THINK YOU REVISED THIS SHEET FOR POLLUTION PREVENTION
 FOR VIBRO-FLOATATION PERMIT. PLEASE USE THATREVISED
 SHEET IN THIS SET. WE TALKED ABOUT IN VIBRO-FLOATATION
 PERMIT THAT SILT FENCE SHOULD BE INSTALLED ALL AROUND
 THE SITE INCLUDING SOUTH & WEST.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-11-27 Cont ID  
Sent By rchokshi Date 2007-11-27 Time 08:48 Rev Time 0.00
Received By rchokshi Date 2007-11-27 Time 08:43 Sent To  
Notes
2007-11-27 08:48:06FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 ORDINANCE NO. 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 13:17 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 12:56 Sent To  
Notes
2008-01-17 13:09:37*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS G-002 AND AC-101 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By mawillia Date 2008-01-11 Time 19:02 Rev Time 0.00
Received By mawillia Date 2008-01-11 Time 18:12 Sent To  
Notes
2008-01-11 19:01:40*****UNSAT*****
  
 01.SOME PLAN SHEET LIST LAKEVIEW AS A DRIVE, SHOULD
 BE LISTED AS AN AVENUE.SEE SHEETS -A-100B THRU
 A-100E, A-102A THRU E-302, SHEET #4 THRU S-301
  
 02.ON SHEET G-000 UNDER BUILDING INFORMATION AND
 CODES, PLEASE EXPLAIN REFERENCE TO NFPA 2002.NFPA
 101 - LIFE SAFETY CODE - 2003 EDITION, AND THE FLORIDA
 FIRE PREVENTION CODE - 2004 EDITION,SHALL BE
 REFERENCED
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-12-04 Time 16:11 Rev Time 0.00
Received By mawillia Date 2007-12-04 Time 14:45 Sent To  
Notes
2007-12-04 16:11:07*****DENIED*****
  
 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.ALSO, SOME PLAN
 SHEET LIST LAKEVIEW AS A DRIVE, SHOULD BE LISTED AS AN
 AVENUE.
  
 02.ON SHEET G-000 UNDER BUILDING INFORMATION AND
 CODES, PLEASE EXPLAIN REFERENCE TO NFPA 2002.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR THE VICINITY THEREOF (INCLUDING ROADWAYS, ALLEYS,
 FIRE LANES).
  
 05.IN ALL BUILDINGS OVER ONE STORY IN HEIGHT, AT
 LEAST ONE STAIRWAY SHALL BE PROVIDE IN AN USABLE
 CONDITION AT ALL TIMES.
  
 06.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.THE STANDPIPES SHALL BE PROVIDED WITH
 CONSPICUOUSLY MARKED AND READILY ACCESSIBLE FIRE
 DEPARTMENT CONNECTIONS ON THE OUTSIDE OF THE BUILDING
 AT THE STREET LEVEL AND HAVE AT LEAST ONE STANDARD HOSE
 OULET AT EACH FLOOR.
  
 07.ILLUSTRATE FIRE HYDRANT LOCATIONS ON SITE PLAN.
  
 08.WHERE/IF UNDERGROUND WATER MAINS AND FIRE HYDRANTS
 ARE TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED,
 AND IS SERVICE PRIOR TO CONSTRUCTION WORK.
  
 09.THERE SHALL BE NO DELAY IN THE INSTALLATION OF
 FIRE PROTECTION EQUIPMENT.
  
 10.THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE
 PLACED IN SERVICE AS SOON AS PRACTICABLE.
  
 11.THE PROJECT SITE ADDRESS SHALL BE TEMPORARILY
 POSTED PRIOR TO, AND DURING CONSTRUCTION, OR UNTIL SUCH
 TIME THAT THE PERMANANT NUMERICAL ADDRESS IS DISPLAYED
 ON THE EXTERIOR ELEVATION WHICH FRONTS LAKEVIEW
 AVENUE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 10:17 Sent To B
Notes
2008-04-29 10:18:02TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 12:41 Sent To  
Notes
2008-01-16 12:41:23TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 16:26 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 16:26 Sent To ENG
Notes
2007-12-27 16:27:28TO RASIK CHOKSHI'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-17 Cont ID  
Sent By adarroug Date 2007-12-17 Time 15:24 Rev Time 0.00
Received By adarroug Date 2007-12-17 Time 15:24 Sent To  
Notes
2007-12-17 15:26:52TO "COMM" BD#16/PLANS ON RACK/1 ROLL AND BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-12-04 Time 14:45 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 11:17 Sent To  
Notes
2007-11-20 16:04:19TO "COMM" BD#63
2007-10-25 11:18:38WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-16 Cont ID  
Sent By mflis Date 2008-01-16 Time 15:48 Rev Time 0.00
Received By mflis Date 2008-01-16 Time 15:48 Sent To  
Notes
2008-01-16 15:49:02ZONING REVIEW: PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-21 Cont ID  
Sent By mflis Date 2007-12-21 Time 10:33 Rev Time 0.00
Received By mflis Date 2007-12-21 Time 10:26 Sent To  
Notes
2007-12-21 10:36:35ZONING REVIEW: FAILED
  
 **STRUCTURE ONLY PERMIT**
  
 - PLEASE NOT THAT ARCHITECTURAL, ENGINEERING, AND
 STRUCTURAL DRAWINGS ARE NOT COORDINATED.
 - ENTRY COLUMN CORRECTLY INDICATED IN ARCHITECTURAL
 SITE PLAN IS INCORRECT ON STRUCTURAL DRAWINGS S101-A,
 S102-A ETC; PLEASE MAKE SURE STRUCTURAL DRAWINGS
 ACCURATELY REFLECT ARCH SITE PLAN.
 - COMMENT ALSO APPLIES TO ENGINEERING DRAWINGS WHICH DO
 NOT APPEAR TO HAVE BEEN UPDATED TO REFLECT MOST RECENT
 SITE PLAN.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By mflis Date 2007-12-05 Time 15:12 Rev Time 0.00
Received By mflis Date 2007-12-05 Time 15:12 Sent To  
Notes
2007-12-05 15:15:06ZONING REVIEW: FAILED
  
 1) ENTRY AND ASSOCIATED STRUCTURE SHALL BE MODIFIED TO
 MATCH APPROVED SITE PLAN. THIS INCLUDES RELOCATION OF
 COLUMN.
 2) SIDEWALK DIMENSIONS SHOULD BE PROVIDED ON ALL SITE
 AND GROUND FLOOR PLANS.
 3) PLEASE REMOVE "TRASH PICK UP AREA" NOTE ON FLOOR
 PLAN WHERE ARE IS LOCATED ON SIDEWALK ALONG OLIVE
 AVENUE.
 4) DRIVEWAY ALONG LAKEVIEW SHALL BE MODIFIED TO MATCH
 APPROVED SITE PLAN. THIS INCLUDES NARROWING THE DRIVE
 FOR ONE LANE OF TRAFFIC.
  
 MATT FLIS - 822-1445