Plan Review Details - Permit 07100724
Plan Review Stops For Permit 07100724
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-04-17 Cont ID  
Sent By lursu Date 2008-04-17 Time 08:50 Rev Time 0.00
Received By lursu Date 2008-04-17 Time 08:50 Sent To  
Notes
2008-04-17 08:51:09THE SITE ADDRESS WAS CHANGED TO A NEW ADDRESS AS 5611
 GEORGIA AVE ,WEST PALM BEACH, FL 33405.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By lursu Date 2008-04-03 Time 13:20 Rev Time 0.00
Received By lursu Date 2008-04-03 Time 13:19 Sent To  
Notes
2008-04-03 13:22:36PLEASE CONTACT THIS DEPARTMENT IF A CHANGE OF ADDRESS
 IS NEEDED. IF THE ADDRESS CHANGE IS APPROVED THEN THE
 REVISED PLANS MUST HAVE THE NEW ADDRESS DEPICTED AND
 PERMIT WILL BE ISSUED WITH THE NEW ADDRESS .
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-30 Cont ID  
Sent By shill Date 2009-01-30 Time 13:45 Rev Time 0.00
Received By shill Date 2009-01-30 Time 13:45 Sent To  
Notes
2009-01-30 13:46:04REVISED SHEET 3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-01-22 Cont ID  
Sent By shill Date 2009-01-22 Time 07:55 Rev Time 0.00
Received By shill Date 2009-01-22 Time 07:55 Sent To  
Notes
2009-01-22 08:04:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE ENERGY CALCS ARE FOR A FINISHED BUILDING, METHOD
 A, AND SHOW 556 SF OF CONDITINED SPACE. PLEASE REVISE
 ENERGY CALCS, FBC13-101.1.6.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-15 Cont ID  
Sent By shill Date 2009-01-15 Time 08:05 Rev Time 0.00
Received By shill Date 2009-01-15 Time 08:05 Sent To  
Notes
2009-01-15 08:05:48REVISION; NEW ROOF NOA (GAF MODIFIED FOR STEEL)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-19 Cont ID  
Sent By shill Date 2008-05-19 Time 08:56 Rev Time 0.00
Received By shill Date 2008-05-19 Time 08:56 Sent To  
Notes
2008-05-19 09:01:02SEPARATE ROOF PERMIT REQUIRED
 NOA 06-0601.07 REVIEWED, NO ASSEMBLY SELECTED, 1 1/2"
 RIGID INSULATION BOARD SHOWN ON SHEET 4 OF PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 09:15 Rev Time 0.00
Received By shill Date 2008-04-28 Time 17:34 Sent To  
Notes
2008-04-29 09:28:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE REVISE GOVERNING CODE TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.PLANS REFER TO 2006 REVISIONS.
  
 2.SEE ENERGY CALCS.ZONE 1 IS UNCONDITIONED SPACE,
 BUT IS USED THROUGHOUT THE ENERGY CALCS FOR COMPONENTS.
 ONLY TWO WALLS ARE SHOWN; PLEASE CLARIFY.SQUARE FOOT
 AREA DOES NOT CORRELATE WITH PLANS.THE TOTALS FOR THE
 THREE AREAS DO NOT MATCH THE TOTAL.CHECK ALL ITEMS.
  
  
 3.PLEASE INCLUDE THE NEW JOB ADDRESS ON THE TITLE
 BLOCK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-11 Cont ID  
Sent By shill Date 2008-03-11 Time 11:03 Rev Time 0.00
Received By shill Date 2008-03-11 Time 11:03 Sent To  
Notes
2008-03-11 11:04:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)INFORMATIONAL ONLY; SEPARATE PERMITS WILL BE
 REQUIRED.(THIS INCLUDES THE LIGHT POLE,
  
 2.)ADDRESSED.PLEASE KEEP THE ORIGINAL SOILS REPORTS
 IN THE PERMIT PACKAGE WHEN RESUBMITTING.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 SEE OTHER COMMENTS; NEW PRODUCT APPROVALS WILL BE
 REQUIRED.PLEASE HAVE DOR REVIEW PRIOR TO
 RESUBMITTAL.
  
  
 4.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 THE RESPONSE LETTER STATES THAT THIS IS ON SHEET 1,
 MISC. DATA.THIS IS NOT ON SHEET 1.SEE FBC106.3.5.1,
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. DECLARE
 BUILDING TYPE FBC6, SPRINKLER INFORMATION (SPRINKLERED
 OR UNSPRINKLERED), OCCUPANCY CLASSIFICATION FBC CHAPTER
 3, AREA PER OCCUPANCY.
  
 ALSO PLEASE NOTE THAT SHEET 1 IS DATED JAN 23, 2007, SO
 IS THE SAME SHEET AS SUBMITTED FIRST REVIEW.
  
 ZONING SITE DATA ON SHEET 1 STATES INDUSTRIAL, A NOTE
 ON THE BUILDING FLOOR PLAN STATES INDUSTRIAL BUILDING
 AND ALSO WAREHOUSE AND SHOWROOM.NOTE THAT INDUSTRIAL
 WOULD BE FACTORY FBC3065, WAREHOUSE IS STORAGE
 OCCUPANCY.PLEASE DECLARE OCCUPANCY CLASSIFICATION AND
 ALSO SUBCLASSIFICATION IF APPLICABLE AS PER FBC CHAPTER
 3.NOTE THAT THE ENERGY CALCS ARE TO CORRELATE WITH
 THE PLANS.THE ENERGY CALCS STATE THAT TYPE IS RETAIL,
 WHICH WOULD BE MERCANTILE.
  
 5.)IDENTIFY WHETHER THIS IS A SEPARATED USE,
 NONSEPARATED USE, ACCESSORY, INCIDENTAL?SEE FBC302.
  
 RESPONSE LETTER STATES THAT THIS IS SEPARATED USE
 CLASSIFICATION, BUT NO OCCUPANCY SEPARATIONS SHOWN. SEE
 FBC302.3.2 REGARDING SEPARATED USES.IF THIS IS A
 SEPARATED USE, BOTH HORIZONTAL AND VERTICAL SEPARATION
 WOULD BE REQUIRED BETWEEN SHOWROOM (MERCANTILE) AND THE
 OTHER AREA (F OR S).
  
 ALL FIRE RATINGS ARE TO BE SHOWN ON THE PLAN.
  
 6.)SPECIFY MAXIMUM SLOPE AND MINIMUM WIDTH FOR THE
 SIDEWALK (ACCESSIBLE ROUTE) SHOWN ON SHEET 1,
 FBC11-4.1.2.
  
 PLEASE PUT INFORMATION ON THE RESPONSE LETTER ONTO THE
 PLAN.THE RESPONSE LETTER IS DISCARDED AND IS NOT TO
 BE USED TO SHOW CODE COMPLIANCE.ALL CODE REQUIREMENTS
 ARE TO BE SPECIFIC AND ARE TO BE ON THE PLAN,
 FBC*106.1.1.
  
 7.)SHEET 1, SEE ATTACHED PARKING DETAIL.THE 2FT
 DIMENSION IS TO BE TO THE BACK OF THE WHEEL STOP, NOT
 THE FRONT.PLEASE REVISE.
  
 8.)THIS APPEARS TO BE FOUR UNITS.SHOW REQUIRED
 TENANT SEPARATIONS FBC708.1(5).PROVIDE A DETAIL WITH
 EITHER TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC 7.
  
 ALL INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS TO
 BE ON THE PLAN.PLEASE INCORPORATE THE INFORMATION ON
 THE RESPONSE LETTER INTO THE PLAN.PROVIDE THE UL
 ASSEMBLY DETAIL ON THE PLAN.THE FLOOR PLAN IS TO SHOW
 ALL REQUIRED FIRE RESISTANCE RATED WALLS SO THAT OTHER
 TRADES WILL BE AWARE OF THESE REQUIREMENTS WITHOUT
 REFERRING TO CORRESPONDING WALL DETAILS.
  
 9.)NO MECHANICAL PLANS WERE SUBMITTED, BUT ENERGY
 CALCS WERE SUBMITTED SHOWING AIR CONDITIONED SPACE.
 SHOW COMPLIANCE WITH FBC716.
  
 ARCHITECT'S RESPONSE STATES THAT THIS COMMENT SEEMS NOT
 TO BE APPLICABLE.MY APOLOGIES FOR ANY CONFUSION.
 PENETRATIONS THROUGH RATED WALLS WILL REQUIRE FIRE
 DAMPERS, REQUIREMENT INCLUDED IN THE CODE SECTION
 REFERENCED. FLOOR PLAN IS TO SHOW ALL REQUIRED FIRE
 RESISTANCE RATINGS, PARTIALLY SO THAT THE MECHANICAL
 CONTRACTOR AND INSPECTORS KNOW WHERE FIRE DAMPERS WILL
 BE REQUIRED.
  
 10.)DECLARE OCCUPANT LOAD, FBC1004, FBC TABLE
 1004.1.2.
  
 RESPONSE LETTER STATES TO SEE MISC DATA, SHEET 1.SAME
 SHEET SUBMITTED, COMMENT NOT ADDRESSED.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE 601, FBC TABLE
 602. PROVIDE A DETAIL FOR ALL FIRE RATED WALLS, EITHER
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
 ALL FIRE RESISTANCE RATING REQUIREMENTS ARE TO BE
 INCLUDED ON THE FLOOR PLAN.
  
 12.)ADDRESSED.
  
 13.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES
 APPROVAL FROM THE BUILDING OFFICIAL.IF YOU ARE
 PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE
 INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM 13.
 PROVIDE PRODUCT APPROVALS AND COMPLETE AN INSTALLATION
 SCHEDULE.TO AVOID PERMIT DELAYS, SUBMIT THE
 INSTALLATION PLAN PRIOR TO RESUBMITTAL OF THE PLANS.
 THIS MAY BE DONE BY EITHER EMAIL OR SUBMITTED AT THE
 FRONT COUNTER.
  
 **COMMENT REVISED 3/20 - FIXED IMPACT PROTECTION IS TO
 BE TESTED AS SUCH.PLEASE ADDRESS.**
  
  
 14.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.THIS MAY BE DONE AT THE TIME OF ROOF
 PERMIT APPLICATION.
  
 15 .)FOR THE FLAT DECK, SEE GENERAL LIMITATION #7.
 CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT REQUIRED FOR ENHANCED FASTENING.THIS
 MAY BE DONE AT TIME OF ROOF PERMIT APPLICATION.
  
 16-17.)ADDRESSED.
  
 18.)SEE FBC1907.7.1 AND SHEET 5, ITEM 10, 1.5 INCH
 CONCRETE COVER REQUIRED AT EXTERIOR SLABS.
  
 PLEASE REVISE.THERE WAS A TYPO DUE TO TRANSFER OF
 DATA ON THE ORIGINAL LIST.PLEASE SEE FBC1907.7.1 AND
 REVISE SHEET 5.THE SLUMP REQUIREMENT WAS CHANGED,
 PLEASE CHECK ALL CONCRETE COVERAGE REQUIREMENTS AND
 REVISE AS NECESSARY.
  
 19.)ACCESSIBLE PARKING IS TO BE ON THE SHORTEST
 ROUTE, FBC11-4.6.2.THE PLANS SHOW THE LONGEST ROUTE
 FROM THIS LOCATION.PLEASE REVISE.
  
 ARCHITECT?S RESPONSE IS NOTED.PLEASE SHOW PARKING LOT
 SLOPE, FBC11-4.6.2.THE CODE REQUIRES THE SHORTEST
 SAFELY ACCESSIBLE ROUTE, WHICH WOULD BE THE REAR
 ENTRANCES.THIS CAN BE SATISFIED BY THE MAXIMUM CROSS
 SLOPE NOTED ON THE PLAN.
  
 20.)FEES WILL BE DETERMINED AFTER OCCUPANCY
 CLASSIFICATION IS ESTABLISHED.
  
 NEW COMMENTS:
  
 21.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 233-5025 FOR MORE
 INFORMATION.
  
 22.SEE FBC11-4.29.5, DETECTABLE WARNINGS AT HAZARDOUS
 VEHICULAR AREAS.PLEASE SHOW LOCATION ON THE SITE
 PLAN, DRIVEWAY APPROACH.
  
 23.SEE ELECTRIC COMMENTS REGARDING THE ADDRESS.
 PLEASE INCLUDE CORRECT ADDRESS ON THE PLANS, FBC106*.
  
 24.SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By shill Date 2007-11-09 Time 15:37 Rev Time 0.00
Received By shill Date 2007-11-09 Time 12:20 Sent To  
Notes
2007-11-09 15:38:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)INFORMATIONAL ONLY; SEPARATE PERMITS WILL BE
 REQUIRED.
  
 2.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 4.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 5.)IDENTIFY WHETHER THIS IS A SEPARATED USE,
 NONSEPARATED USE, ACCESSORY, INCIDENTAL?SEE FBC302.
  
 6.)SPECIFY MAXIMUM SLOPE AND MINIMUM WIDTH FOR THE
 SIDEWALK (ACCESSIBLE ROUTE) SHOWN ON SHEET 1,
 FBC11-4.1.2.
  
 7.)THERE IS A CONFLICT ON THE PARKING DETAIL FOR THE
 CONCRETE STOP LOCATION ON SHEET 1 PREPARED BY ARCHITECT
 (BELL) AND SHEET 1 PREPARED BY ENGINEER (MCCARTY).
  
 8.)THIS APPEARS TO BE FOUR UNITS.SHOW REQUIRED
 TENANT SEPARATIONS FBC708.1(5).PROVIDE A DETAIL WITH
 EITHER TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC 7.
  
 9.)NO MECHANICAL PLANS WERE SUBMITTED, BUT ENERGY
 CALCS WERE SUBMITTED SHOWING AIR CONDITIONED SPACE.
 SHOW COMPLIANCE WITH FBC716.
  
 10.)DECLARE OCCUPANT LOAD, FBC1004, FBC TABLE
 1004.1.2.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE 601, FBC TABLE
 602. PROVIDE A DETAIL FOR ALL FIRE RATED WALLS, EITHER
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
 ALL FIRE RESISTANCE RATING REQUIREMENTS ARE TO BE
 INCLUDED ON THE FLOOR PLAN.
  
 12.)BUILDING SIZE IS TO COMPLY WITH FBC503.ENGINEER
 STATES ON SHEET 1 THAT THIS IS A 44,448 SF BUILDING.
 PLEASE CORRELATE WITH OTHER INFORMATION (PLANS, ENERGY
 CALCS).
  
 13.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES
 APPROVAL FROM THE BUILDING OFFICIAL.IF YOU ARE
 PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE
 INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM 13.
 PROVIDE PRODUCT APPROVALS AND COMPLETE AN INSTALLATION
 SCHEDULE.TO AVOID PERMIT DELAYS, SUBMIT THE
 INSTALLATION PLAN PRIOR TO RESUBMITTAL OF THE PLANS.
 THIS MAY BE DONE BY EITHER EMAIL OR SUBMITTED AT THE
 FRONT COUNTER.
  
 14.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.THIS MAY BE DONE AT THE TIME OF ROOF
 PERMIT APPLICATION.
  
 15 .)FOR THE FLAT DECK, SEE GENERAL LIMITATION #7.
 CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT REQUIRED FOR ENHANCED FASTENING.THIS
 MAY BE DONE AT TIME OF ROOF PERMIT APPLICATION.
  
 16.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025 (DRAINAGE CALCS).
  
 17.)THE BATHROOM DOOR APPEARS TO SWING INTO THE
 REQUIRED CLEAR FLOOR SPACE FOR THE WATER COOLER.
 PLEASE SHOW CLEAR FLOOR SPACE ON THE PLAN FBC FIGURE
 11-27.
  
 18.)SEE FBC1907.7.1 AND SHEET 5, ITEM 10, 1 ? INCH
 CONCRETE COVER REQUIRED AT EXTERIOR SLABS.
  
 19.)ACCESSIBLE PARKING IS TO BE ON THE SHORTEST
 ROUTE, FBC11-4.6.2.THE PLANS SHOW THE LONGEST ROUTE
 FROM THIS LOCATION.PLEASE REVISE.
  
 20.)FEES WILL BE DETERMINED AFTER OCCUPANCY
 CLASSIFICATION IS ESTABLISHED.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-03-17 Cont ID  
Sent By dpalmer Date 2009-03-17 Time 08:04 Rev Time 0.00
Received By dpalmer Date 2009-03-17 Time 08:04 Sent To PC
Notes
2009-03-17 08:04:29** NOTES REDLINED **
  
  
 1) NOTE: NOT ALL CIRCUITS ON REVISED PANEL SCHEDULE
 CORRELATES WITH THE LAST REVISED PLANS DATED 12/18/08.
 SEE CIRCUITS ON PLANS STILL INDICATE A CIRCUIT #5 FOR
 EXAMPLE HOWEVER THE PANEL SCHEDULE NOW INDICATES THIS
 AS A BLANK SPACE.
 THIS IS ONE EXAMPLE ONLY GIVEN.
 408.4, FBC106.5, 106.1.1
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-02-06 Cont ID  
Sent By dpalmer Date 2009-02-06 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2009-02-06 Time 15:33 Sent To PC
Notes
2009-02-06 15:34:52REDLINED PLANS.
  
 TIME CLOCK AS NOTED NEEDS TO MEET 13-415.1.ABC.1.4.
  
 THIS IS NOT SHELL SPACE. AS NOTED PER MR. ROBERT BELL
 ON PLANS AS WELL AS SUBMITTED SIGNED AND SEALED LETTER.
 SPOKE TO MR. BELL ON PHONE TO CONFIRM.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-30 Cont ID  
Sent By dpalmer Date 2008-12-30 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2008-12-30 Time 11:14 Sent To  
Notes
2008-12-30 11:15:36** DENIED REVISIONS**
  
 1) NOTE: NOTES ON PLANS CALL FOR SPACES A AND B AS
 SHELL SPACES YET THE PLANS STILL SHOW ALL ELECTRICAL AS
 IT WAS BEING BUILT OUT. THIS IS CONFUSING.
 A MINIMUM EXIT AND EGRESS LIGHT IS REQUIRED HOWEVER NOT
 ALL AS SHOWN. IF DELETING THIS SCOPE OF WORK THEN
 PLEASE REVISE PLANS ACCORDINGLY AND REVISE PANEL
 SCHEDULES FOR THE UNITS.
 NEC 2005
 408.4,240.4,310.16, ETC AS COMMON ELECTRICAL CODE
 SECTIONS FOR REFLECTED PLANS.
 FBC 106.1.1,106.1.2, 106.5. FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 2) NOTE: PLEASE REVISE METHOD OF ENERGY CALCULATIONS
 PER 13-101.1.6 FOR INCOMPLETE/SHELL BUILDINGS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 18:00 Sent To  
Notes
2008-05-05 18:02:34ELEC OK ON CALCULATIONS. LOOK FOR ANY POSSIBLE COMMENTS
 FROM OTHER TRADES.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-02 Cont ID  
Sent By dpalmer Date 2008-04-02 Time 16:18 Rev Time 0.00
Received By dpalmer Date 2008-04-02 Time 16:18 Sent To  
Notes
2008-04-02 16:18:52** DENIED3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: ADDRESS IS STILL PENDING. THE TITLE BLOCKS DO
 SHOW THE APPLIED ADDRESS AND ANY CHANGES FORTHCOMING
 MAY BE CHANGED. THE FINAL DETERMINATION HAS NOT YET
 BEEN MADE. INFORMATION SENT TO ADDRESSING REVIEWER.
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ONCE AGAIN DO NOT COORDINATE WITH PLANS. PLEASE SEE THE
 INPUT DATA REPORT WILL BE NOTED BELOW AS IDR. PLEASE
 SEE PREVIOUS REVIEWS GAVE SOME SPECIFIC EXAMPLES OF
 LIGHTING ON PLANS AND THE IDR WHICH DID NOT CORRELATE.
 THE NOTES EVEN STATED * THOSE EXAMPLES WERE NOT THE
 ONLY ONES.
 PLEASE SEE THE FOLLOWING EXAMPLES WILL BE GIVEN ONCE
 AGAIN.
 EXAMPLE:
 PLANS SHOW 10-250W LOW BAY FIXTURES, YET THE IDR ONLY
 SHOWS 5.
 PLANS SHOW 6-96W FIXTURES, YET THE IDR ONLY SHOWS 3.
 PLANS SHOW 4-32W FIXTURES, YET THE IDR ONLY SHOWS 3.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1. **
 SHEET STATES RETAIL? PLANS STATE INDUSTRIAL.?? *** IF
 THERE ARE QUESTIONS, PLEASE CALL. THE LIGHTING ON PLANS
 IS OK, AS THIS COMMENT IS NOT FOR CHANE ENGINEERING.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 5 GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECTTO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THAT CODE SECTIONS FOR ENERGY CALCULATIONS
 COMPLIANCE WERE GIVEN THREE TIMES FOR THE SAME ITEMS.
 AS REQUIRED BY FLORIDA STATUTES NOTED ABOVE A FEE HAS
 NOW BEEN ASSESSED AS REQUIRED AND IS REQUIRED TO BE
 PAID BEFORE PLANS ARE PERMITTED TO BE RESUBMITTED. THE
 FEE IS $5,146.80 WILL BE DUE BEFORE RESUBMISSION OF
 PLANS. THE 10% RE-SUB FEE WILL NOT BE CHARGED PER
 BUILDING OFFICIAL.
 ***DOCUMENTS ARE BEING RETAINED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2008-02-14 Time 19:22 Sent To  
Notes
2008-02-15 13:06:30*** DENIED2ND REVIEW***
  
 ** PLEASE SEE SOME OF THE SAME COMMENTS FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SOME NEW COMMENTS BASED ON SUBMITTING OF NEW
 DOCUMENTS NOT ON PREVIOUS SUBMISSION.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 ADDRESS ON THE PROJECT NEEDED COORDINATION WITH THE
 DETERMINED ADDRESS YET THE PLANS STILL SHOW ONLY
 *GEORGIA AVE* AND NO REFERENCE TO ACTUAL APPLIED
 ADDRESS LOCATION OF 605 GLENRIDGE.
 PLEASE BE SURE PLANS ARE UPDATED WITH THE ADDRESS AS
 APPLIED AND LOCATED. IF APPLICATION IS GOING TO BE MADE
 FOR CHANGES OF ADDRESS PLEASE CONTACT THE ADDRESSING
 REVIEWER.
 FBC 106.1.2, 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 DO NOT COORDINATE WITH ALL OF THE LIGHTING FIXTURES ON
 PLANS FOR INTERIOR LIGHTING.
 PLEASE ALSO SEE VERSION SUBMITTED IS NOT ADOPTED IN THE
 FBC 13-400.3.A EVEN UNDER THE 2006 REVISIONS. PLEASE
 ADJUST. THE INPUT DATA REPORT WILL BE NOTED AS IDR.
 PLEASE SEE ONE EXAMPLE: PLANS SHOWS A TOTAL OF 10 TOTAL
 250W INTERIOR LOW BAY FIXTURES YET THE INPUT DATA
 REPORT ONLY SHOWS 6?
 PLEASE ALSO SEE OTHER INTERIOR FIXTURES WHICH DO NOT
 CORRELATE WITH THE TOTAL NUMBER OF FIXTURES. THE LOW
 BAY 250VA FIXTURES ARE NOT THE ONLY ONES.
 PLEASE COORDINATE SPACES ON IDR WITH PLANS.
 PLEASE SEE 13-415.2.ABC.1, 13-415.2, 13-415.1.A FOR
 INTERIOR LOADS TO BE USED. PLEASE DETERMINE THE VA
 RATINGS OF BALLAST WITH ACTUAL OUTPUT AND USAGE BASED
 ON THE FIXTURE WHICH HAS BEEN NOTED BY CHANE
 ENGINEERING.
 PLEASE ALSO COORDINATE EXTERIOR LIGHTING PER
 13-415.2.ABC.1.3. FOR EXAMPLE: PLANS SHOWS TWO FIXTURES
 ON LIGHT POLE AT REAR OF BUILDING YET THE IDR ONLY
 SHOWS ONE FIXTURE BEING FIGURED INTO CALCULATIONS.
 PLEASE SEE THE ENERGY CALCULATIONS STILL SHOW GEORGIA
 AVE, (SEE NOTE ABOVE WITH RESPECT TO ADDRESS)
 PLEASE SEE SPACE STILL SHOWN AS *RETAIL*.
  
 ** THE LIGHTING CALCULATIONS ON SHEET 7 SHOWS A HIGHER
 WATTAGE THAN ON ENERGY CALCULATIONS. (PLANS ARE OK)
  
 3) NOTE: PLEASE SEE PLANS STILL INDICATE IN TITLE
 BLOCKS A *NEW INDUSTRIAL BUILDING* YET THE USE ON PLANS
 AND ENERGY CALCULATIONS DO NOT APPEAR TO SHOW THIS SAME
 OCCUPANCY.
 PLEASE COORDINATE WITH ALL DOCUMENTS AND ONCE FINAL
 OCCUPANCY USAGE IS DETERMINED, PLEASE ADJUST DESIGNS
 ACCORDINGLY.
 FBC 106.1
  
 4) NOTE: PLEASE VERIFY THE MAINS SHOWN ON RISER. SHOWS
 2-POLE 200AMP MAINS/125AMP. THESE APPEAR THEY ARE
 200AMP DISCONNECTS WITH 2-POLE 125AMP MAINS.
 THIS IS ONLY A MISPRINT OF DESIGNATION.
 230,
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE AS SOME OF THE COMMENTS WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE WERE
 ACTUALLY THE SAME CODE SECTIONS AND ITEMS FROM PREVIOUS
 REVIEW PLEASE SEE A NOTICE ONLY IS BEING GIVEN FOR FS
 553.80(2)(B).
 THIS IS ONLY A NOTICE AT THIS TIME.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-14 19:22:442008-02-14 19:22:44
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 15:35 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 15:11 Sent To  
Notes
2007-11-26 15:36:18** DENIED**
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006/2007 REVISIONS
 TO THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006/07 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** ELECTRICAL PLAN NOTES MENTIONS *PALM BEACH COUNTY
 AMENDMENTS* HOWEVER THIS PROJECT IS LOCATED IN THE CITY
 OF WEST PALM BEACH.PLEASE ADJUST.
  
 2) NOTE:PLEASE SEE ADDRESS OF LOCATION AS APPLIED IS
 605 GLENRIDGE DR.
 PLEASE BE SURE TO ADJUST ALL PLANS, AND SUPPORTING
 DOCUMENTATION.
 PLEASE DO NOT ATTACH/STAPLE SUPPORTING DOCUMENTATION
 DOWN THE LEFT HAND SIDE OF PLANS.
 FBC 106.1.2, 106.3
  
 3) NOTE: PLEASE COMPLETE LOAD INFORMATION ON PANELS.
 THESE ARE CURRENTLY SHOWN WITH ASTERISK.
 NEC 220,408.4
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE PLANS MENTIONS NEW *INDUSTRIAL
 BUILDING* HOWEVER ENERGY CALCULATIONS AND OTHER PARTS
 OF PLANS MENTIONS NEW RETAIL/MERCANTILE OCCUPANCY.
 PLEASE SEE FOR OTHER EXAMPLE: LIGHT LEGEND ON
 ELECTRICAL PLANS INDICATE 175W AND 250W FIXTURES, AND
 THE HIGHEST WATTAGE OF FIXTURES ON THE IDR IS 75W.
 PLEASE CORRELATE.
 PLEASE CORRELATE ALL LIGHTING ON PLANS WITH THAT OF THE
 SUBMITTED ENERGY CALCULATIONS. FOR EXAMPLE: PLEASE SEE
 SITE LIGHTS WHICH ARE ON PLANS BUT NOT ON EXTERIOR
 LIGHTING IN THE INPUT DATA REPORT.
 PLEASE SEE THE LIGHTING POWER USAGE ON PLANS IS HIGHER
 THAN THAT IN THE IDR ALSO.
 PLEASE COORDINATE.
 13-415.2, 13-415.1.A
  
 5) NOTE: PLEASE SEE SIGN CIRCUIT VA IS REQUIRED TO BE A
 MINIMUM OF 1200VA. THE AMPERAGE LOAD ON PANEL SCHEDULE
 IS SHOWN LESS THAN THAT FOR THE MINIMUM VA.
  
 6) NOTE: PLEASE SEE FOOTER STEEL IS REQUIRED FOR
 GROUNDING ELECTRODE SYSTEM.
 (SHOWS BUILDING STEEL WHICH IS SEPARATE).
  
 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS AND
 INFORMATION FOR NEW SITE POLE.
 PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING
 REVIEWER.
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-04-04 Cont ID  
Sent By rchokshi Date 2008-04-04 Time 11:11 Rev Time 0.00
Received By rchokshi Date 2008-04-04 Time 11:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-02-27 Cont ID  
Sent By rchokshi Date 2008-02-27 Time 11:33 Rev Time 0.00
Received By rchokshi Date 2008-02-27 Time 11:19 Sent To  
Notes
2008-02-27 11:33:48FAILED FOR FOLLOWING REASONS:
  
 1.PLEASE SHOW DUMPSTER & ITS ENCLOSURE DETAILS PER CITY
 OF WPB, &LOCATION ON DWG, LOCATION MUST BE ACCESSIBLE
 FOR PICKUP TRUCK.PER CITY,DUMPSTER SHOULD BE 13'-8"
 X 13'-8" MINIMUM. CITY'S DIMENTIONAL SKETCH FOR
 DUMPSTER IS INCLUDED FOR YOUR USE. ONE OF YOUR DUMPSTER
 DIMENTION IS 10' WHICH IS NOT ACCEPTABLE UNLESS YOU GET
 AN APPROVAL LETTER FROM SANITATION DEPT.
  
 2. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
 THE WATER QUALITY CALCULATION MUST BE APPROVED FROM
 1000 45TH STREET ENGINEERING BEFORE WE APPROVED .
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By rchokshi Date 2007-11-26 Time 13:35 Rev Time 0.00
Received By rchokshi Date 2007-11-26 Time 13:30 Sent To  
Notes
2007-11-26 13:35:46FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 PLEASE INCLUDE 1" OVER ENTIRE SITE & 2.5" CRITERIA. IN
 YOUR CALS YOU DEDUDCTED 0.109 AC FROM 0.236AC, PLEASE
 EXPLAIN THIS.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-01-21 Cont ID  
Sent By mwennerg Date 2009-01-21 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2009-01-21 Time 14:57 Sent To  
Notes
2009-01-21 14:57:40REVISION DATED 12/17/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-04-24 Cont ID  
Sent By mwennerg Date 2008-04-24 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2008-04-24 Time 14:05 Sent To  
Notes
2008-04-24 14:12:20SHEET 3 STAMPED,SIGNED AND DATED
  
 1) PLANS APPEAR TO BE CODE COMPLIANT, BUT WILL REMAIN
 IN FAILED STATUS UNTIL ALL OTHER REVIEW COMMENTS HAVE
 BEEN SATISFIED.
  
 2) PLEASE ADD THE CLASSIFICATION OF EITHER A,B OR C TO
 INTERIOR FINISH FOR WALLS AND CEILINGS. SHEET 3
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By mawillia Date 2008-03-17 Time 17:10 Rev Time 0.00
Received By mawillia Date 2008-03-17 Time 15:32 Sent To  
Notes
2008-03-17 17:06:33****DENIED*****
 THE FOLLOWING COMMENTS (NOT MARKED OK) TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.THE ADDRESS (CORRECT) OF THE PROPOSED SCOPE OF WORK
 SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.OK
  
 3.EMERGENCY LIGHTING FOR THE WAREHOUSE PORTION OF
 THIS GENERAL INDUSTRIAL OCCUPANCY SHALL BE REQUIRED AS
 PER NFPA 101, LIFE SAFETY CODE, 2003 EDITION 40.2.9.1,
 EXCEPT AS OTHERWISE EXEMPTED BY 40.2.9.2
  
 4.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.BOTH PLAN SHEET 3 & 6 SHOW WALL SEPARATION BETWEEN
 THE SHOWROOM AND THE WAREHOUSE FOR SPACE A & SPACE B.
 WHAT IS THE WALL RATING BETWEEN THE SHOWROOM AND
 WAREHOUSE?WHAT IS THE DOOR RATING?
  
 6.OK
  
 7.ADD THE INTERIOR FINISH CLASSIFICATION (CLASS C, AS
 PER YOUR RESPONSE LETTER) TO AN APPROPIATE PLAN SHEET.
  
 NEW COMMENT:
  
 A.ON SHEET 6, IN SPACE A AND SPACE B, AN EXIT LIGHT
 IS SHOWN ON BOTH SIDES OF THE DOOR BETWEEN THE
 WAREHOUSE AND SHOWROOM.ELIMINATE THE EXIT LIGHT
 DIRECTING PATRONS BACK INTO THE MORE HAZARDOUS
 WAREHOUSE AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8054-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-14 Cont ID  
Sent By mcarsill Date 2007-11-14 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2007-11-14 Time 10:42 Sent To  
Notes
2007-11-14 10:49:521. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. PLEASE PROVIDE HOURLY RATING ON TENANT DEMISING
 PARTITION SECTION 2/4 ON PAGE 4.
  
 3. ARE THERE ANY EMERGENCY LIGHT CONTAINED WITHIN THE
 SPACES.
  
 4. ARE THERE ANY PORTABLE FIRE EXTINGUISHERS LOCATED
 WITHIN THE TENANT SPACES.
  
 5. IS THERE ANY FIRE RATING BETWEEN THE WAREHOUSE AREA
 AND THE SHOWROOMS.
  
 6. IS ANY STORAGE OF FLAMMABLE,COMBUSTIBLE,TOXIC,
 CORROSIVE, OR POISONOUS SOLIDS, LIQUIDS, OR GASES
 PLANNED AT THE SITE.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-04-07 Cont ID  
Sent By adarroug Date 2009-04-07 Time 08:50 Rev Time 0.00
Received By adarroug Date 2009-04-07 Time 08:50 Sent To P
Notes
2009-04-07 08:50:54TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 16:04 Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:04 Sent To E
Notes
2009-03-16 16:04:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 11:08 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 11:08 Sent To P
Notes
2009-02-27 11:09:03TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 11:06 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 11:06 Sent To  
Notes
2009-01-30 11:08:18TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 09:23 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 09:23 Sent To Z
Notes
2009-01-29 09:24:03TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 08:57 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 08:57 Sent To  
Notes
2008-12-24 08:57:24TO "COMM" BD#27

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 14:31 Sent To  
Notes
2008-05-05 14:35:38TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 16:44 Sent To  
Notes
2008-03-31 16:47:30TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 15:55 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 15:55 Sent To  
Notes
2008-02-12 15:55:35TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-07 Cont ID  
Sent By kstevens Date 2007-12-07 Time 17:56 Rev Time 0.00
Received By kstevens Date 2007-10-25 Time 10:15 Sent To  
Notes
2007-11-13 09:21:23TO "COMM" BD#13
2007-10-25 10:16:39WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By rregueir Date 2008-05-21 Time 15:17 Rev Time 0.00
Received By rregueir Date 2008-05-21 Time 15:41 Sent To  
Notes
2008-05-21 15:48:31ENERGY CALCS OK. SIGNED FOR BUILDING OFFICIAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-12 Cont ID  
Sent By rregueir Date 2008-04-12 Time 12:53 Rev Time 0.00
Received By rregueir Date 2008-04-12 Time 11:37 Sent To  
Notes
2008-04-12 12:49:01PAGE 6 HAS BEEN STAMPED FOR MECHANICAL. REVIEW WILL
 REMAIN IN FAILED STATUS UNTIL ENERGY CALCULATIONS ARE
 PASSED BY ALL INTERESTED TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-16 Cont ID  
Sent By rregueir Date 2008-03-16 Time 14:00 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 13:31 Sent To  
Notes
2008-03-16 14:00:19REVIEW #: 2ND
 ACTION: PASSED/DENIED - SEE NOTES BELOW
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PREVIOUS REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED. HOWEVER, PLANS CAN NOT BE STAMPED AT THIS
 TIME. INFORMATION REGARDING VENTILATION IS INCLUDED ON
 ELECTRICAL SHEETS AND WILL NOT BE STAMPED UNTIL
 ELECTRICAL REVIEW IS PASSED AND ENERGY CCALCULATIONS
 HAVE BEEN PASSED. THIS REVIEW WILL BE IN FAILED STATUS
 UNTIL PLANS CAN BE STAMPED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By rregueir Date 2007-11-26 Time 14:59 Rev Time 0.00
Received By rregueir Date 2007-11-26 Time 14:20 Sent To  
Notes
2007-11-26 14:59:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL PLANS WERE PROVIDED WITH THIS
 APPLICATION. ENERGY CALCULATIONS HAVE BEEN PROVIDED
 INDICATING THAT AIR CONDITIONING IS TO BE PROVIDED IN
 THIS BUILDING. THE PLANS AND SPECIFICATIONS, INCLUDING
 THE ENERGY CODE CALCULATIONS, SHALL SHOW, IN SUFFICIENT
 DETAIL, ALL PERTINENT DATA AND FEATURES OF THE BUILDING
 AND THE EQUIPMENT AND SYSTEMS AS HEREIN GOVERNED
 INCLUDING, BUT NOT LIMITED TO: SIZE AND TYPE OF
 APPARATUS AND EQUIPMENT, EQUIPMENT AND SYSTEMS CONTROLS
 AND OTHER PERTINENT DATA TO INDICATE CONFORMANCE WITH
 THE REQUIREMENTS OF THE CODE. FBC 13-103.2. PLEASE
 INCLUDE EXHAUST FANS WITH RATINGS ON EQUIPMENT
 SCHEDULE.
  
 2. PROVIDE VENTILATION CALCULATIONS FOR EACH AREA OF
 THE BUILDING INCLUDING OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD, CFM REQUIRED AND CFM PROVIDED IN
 ACCORDANCE WITH FBC,M 403.3.
  
 3. OUTDOOR EQUIPMENT IS TO BE SECURED TO MEET WIND LOAD
 REQUIREMENTS IN ACCORDANCE WITH FBC, M 301.13 AND FBC
 CH.16. PROVIDE DETAIL FOR HOW EQUIPMENT IS TO BE
 SECURED WITH WALL BRACKETS AS SHOWN ON PG 2 TO MEET
 WIND LOADS. PROVIDE WIND LOAD CALCULATIONS FOR BUILDING
 PLAN REVIEW.
  
 4. SHOW LOCATION OF BATHROOM EXHAUST FAN DISCHARGE
 LOCATION TO BE IN COMPLIANCE WITH FBC,M401.5.
  
 NOTE: THIS IS A PRELIMINARY LIST OF MISSING INFORMATION
 IN THIS APPLICATION. IT IS NOT INTENDED TO BE AN
 EXHAUSTIVE LIST AS NO INFORMATION OUTSIDE OF ENERGY
 CALCULATIONS HAS BEEN PROVIDED. ADDITIONAL REVIEW
 COMMENTS ARE LIKELY ONCE ALL MISSING INFORMATION IS
 PROVIDED. SEE FBC 106.3.5.1.4 FOR MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-05-26 Cont ID  
Sent By dwise Date 2009-05-26 Time 20:29 Rev Time 0.00
Received By dwise Date 2009-05-26 Time 20:29 Sent To PC
Notes
2009-05-26 20:30:37REVISED SANITARY AND WATER ISOMETRICS.

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-05-01 Cont ID  
Sent By kstevens Date 2009-05-01 Time 16:44 Rev Time 0.00
Received By kstevens Date 2009-05-01 Time 16:44 Sent To  
Notes
2009-05-01 16:50:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 8 SHOWS A REVISION CHANGING THE WATER SERVICE
 FROM 1" TO 3/4". PER SECTION 603.1 THE WATER SERVICE
 SHALL BE SIZED IN ACCORDANCE WITH TABLE 603.1 OR OTHER
 APPROVED METHODS.
 TABLE 603.1 INDICATES 1" REQUIRED FOR 30 FIXTURE UNITS
 FLUSH TANK W/C. PER TABLE 709.1 THERE ARE 30 FIXTURE
 UNITS. MINIMUM 1" WATER SERVICE IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-03-13 Cont ID  
Sent By kstevens Date 2009-03-13 Time 18:20 Rev Time 0.00
Received By kstevens Date 2009-03-13 Time 18:20 Sent To  
Notes
2009-03-13 18:20:54REVISION OK -- SHT 8.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-19 Cont ID  
Sent By kstevens Date 2008-05-19 Time 12:40 Rev Time 0.00
Received By kstevens Date 2008-05-19 Time 12:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 15:56 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 15:56 Sent To  
Notes
2008-04-12 16:00:04PLUMBING PLANS ARE APPROVED BUT WILL REMAIN IN FAILED
 STATUS UNTIL THE ADDRESSING COMMENT IS ADDRESSED. (SEE
 COMMENT NUMBER 1 OF THE ELECTRICAL PLAN REVIEW)

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-15 Cont ID  
Sent By kstevens Date 2008-03-15 Time 12:52 Rev Time 0.00
Received By kstevens Date 2008-03-15 Time 12:51 Sent To  
Notes
2008-03-15 13:04:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. INDICATE CODE REFERENCE BY WHICH PLANS WERE
 DESIGNED. SECTION 106.1.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 2. OK
  
 3. SUBMIT CALCULATIONS FOR THE ROOF DRAINAGE. SHOW THE
 SQUARE FOOTAGE OF THE ROOF AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPTES ADDED TO ROOF AREA.
 SECTION 1106.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 CALCULATIONS ARE REQUIRED IN ORDER TO VERIFY THE SIZE
 OF THE GUTTERS AND THE DOWNSPOUTS PER TABLES 1106.2 &
 1106.6.
  
 4. OK
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTION AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE TROUBLE BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT
 BEEN ADDRESSED.
  
 6. SHT 4 SHOW THE GUTTER & DOWNSPOUT SIZES PER TABLES
 1106.3 & 1106.6. INDICATE THE SLOPE OF THE GUTTER AND
 SHOW THE HIGH POINT OF THE GUTTER.
 ****RESPONSE NOTED, BUT THE SLOPE OF THE GUTTER AND THE
 HIGH POINT OF THE GUTTER HAS NOT BEEN ADDRESSED.
  
 7. SHT 4 SHOWS 1/4"/FT SLOPE, BUT THE TOTAL DROP OVER
 53' WOULD REQUIRED 13.25". ONLY 12" DROP IS SHOWN.
 PLEASE CLAIRFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE WEST SIDE, (DETAIL 5/4),
 INDICATES THE TOP OF THE TIE BEAM AT 18'10" AND THE
 EAST SIDE, (DETAIL 6/4), INDICATES THE TOP OF THE TIE
 BEAM AT 19'10-3/4". PER 1507.10.1 SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM
 OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR
 BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A
 MINIMUM ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). PLEASE CLARIFY.
  
 8. OK
 9. OK
 10. OK
 11. DELETED
 12. OK
  
 **********NEW COMMENT**********
  
 1B. SHT 8, THE WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE DRINKING FOUNTAINS. THE
 DRINKING FOUNTAIN IS SHOWN ON THE SAME WALL WITH THE
 SERVICE SINK ON THE FLOOR PLAN, BUT IS SHOWN ACROSS THE
 ROOM FROM THE LAV ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By kstevens Date 2007-12-07 Time 17:37 Rev Time 0.00
Received By kstevens Date 2007-12-07 Time 17:37 Sent To  
Notes
2007-12-07 17:56:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE CODE REFERENCE BY WHICH PLANS WERE
 DESIGNED. SECTION 106.1.1.
  
 2. INDICATE OCCUPANCE OF BUILDING. SECTION 106.1.1.
  
 3. SUBMIT CALCULATIONS FOR THE ROOF DRAINAGE. SHOW THE
 SQUARE FOOTAGE OF THE ROOF AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPTES ADDED TO ROOF AREA.
 SECTION 1106.
  
 4. TABLE 403.1 REQUIRES A SERVICE SINK IN EACH SPACE.
 PLEASE INDICATE THE LOCATION OF THE SERVICE SINK.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTION AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 6. SHT 4 SHOW THE GUTTER & DOWNSPOUT SIZES PER TABLES
 1106.3 & 1106.6. INDICATE THE SLOPE OF THE GUTTER AND
 SHOW THE HIGH POINT OF THE GUTTER.
  
 7. SHT 4 SHOWS 1/4"/FT SLOPE, BUT THE TOTAL DROP OVER
 53' WOULD REQUIRED 13.25". ONLY 12" DROP IS SHOWN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 8. SHT 8A SERVICE SINK WIL BE REQUIRED TO BE SHOWN ON
 THE SANITARY ISOMETRIC AND ON THE WATER ISOMETRIC. HOT
 WATER WILL BE REQUIRED TO THE SERVICE SINK PER SECTION
 607.1. PLEASE SHOW ON RISERS. SECTION 106.3.5.1.3.
  
 9. SHT 8 WATER ISOMETRIC ENTERS THE BUILDING AS 1", BUT
 IS SHOWN AS 1/2" AT THE TOP OF THE FIRST RISER, THEN
 BACK TO 3/4". PLEASE CLARIFY. SECTION 106.1.1.
  
 10. SHT 8 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. SECTION 608.13.2.
  
 11. SHT 1 OF 1 THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR LICENSE NUMBER ON THE SHEET. FAC 61G15-23.002(2)
 & FS 471.025.
  
 12. AN IRRIGATION PERMIT AND PLANS WILL BE REQUIRED.
 SECTION 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-15 Cont ID  
Sent By kdfreema Date 2008-02-15 Time 14:39 Rev Time 0.00
Received By kdfreema Date 2008-02-15 Time 14:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-15 Cont ID  
Sent By kdfreema Date 2007-11-15 Time 16:23 Rev Time 0.00
Received By kdfreema Date 2007-11-15 Time 16:23 Sent To  
Notes
2007-11-15 16:25:19***FAILED**
  
 SITE PLAN AND STORMWATER MANAGEMENT PLAN CONTAIN
 CONFLICTING PARKING LOT STRIPING DETAILS. PLEASE REMOVE
 THE NON-COMPLIANT DETAIL FROM STORMWATER PLANS OR
 REPLACE IT WITH THE COMPLIANT DRAWING FOUND ON THE SITE
 PLAN.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH ANY QUESTIONS.