Plan Review Details - Permit 07100688
Plan Review Stops For Permit 07100688
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-07-29 Cont ID  
Sent By jgomez Date 2008-07-29 Time 13:07 Rev Time 0.00
Received By jgomez Date 2008-07-29 Time 13:07 Sent To PC
Notes
2008-07-29 13:08:10RESIDENTIAL(R3) ADDITION,BUILDING REVIEWTHIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
 ***NOTE: THIS MAY BE DONE AT TIME OF PRINTING THE
 PERMIT TO AVOID EXPIRATION OF DOCUMENT.
  
 2-TRUSS PACKAGE:
 A) TRUSS ENGINEER TO COMPLY WITH SEC. 61G15-31.003.
 NEED TO WRITE DESIGNER OF RECORD NAME ANDAND PROVIDE
 THE TRUSS ENGINEER INFORMATION ON EACH SHEET. (REPEAT
 COMMENT).
  
 3-SHEET A-1:
 A) UPDATE ALL REFERENCE STANDARDS SHOWN ON THE
 FOUNDATION NOTES. (REPEAT COMMENT). SEE CHAPTER 43 OF
 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT YEAR TO BE
 REFERENCED AND REVISE AS REQUIRED.
  
 B)FOOTING DETAIL 1/A-1 DOESN'T MATCHFOOTING
 SHOWN ON FOUNDATIONPLAN AND IT DOESN'T SPECIFY
 SPACING FOR DOWELS.PROVIDE COMPLETE AND CORRECT
 INFORMATION. (REPEAT COMMENT).FOUNDATION PLAN CALLS
 FOR 24" X 16"CONT. CONC. STEM WALLW/ (3)# 5 CONT.
 FOOTING, WHILE DETAIL1 CALLS FOR8" MONOLITHIC
 FOOTING. REVISE AS REQUIRED TO MATCH.
  
 4- SHEET A-2:
 A) COMPLY WITH SEC. R311.5.3 OF 2004 FLORIDA
 RESIDENTIAL CODE.PROVIDE DIMENSIONS FOR RISERS AND
 TREADS AND REVISE DRAWING ACCORDINGLY. (REPEAT
 COMMENT).
 *** FLOOR PLAN SHOWS TWORISERS BUT SPECIFIES(2) NEW
 7.5" R STEPS.REVISE AS REQUIRED AND ALSO SPECIFY SIZE
 OF TREAD TO VERIFY COMPLIANCE WITH CODE SECTION CITED
 ABOVE.
  
 5- SHEET A-4:
 A)COORDINATELOADS SHOWN ON TYPICAL END DETAIL
 AND LOADS SHOWN ON ROOF FRAMING NOTE #3. (REPEAT
 COMMENT).TYPICAL END DETAIL CALLS FOR ROOF LOAD 55
 P.S.F., WHILE ROOF FRAMING NOTE CALLS FOR 30 P.S.F.
 ROOF LOAD.
 CLEARLY SPECIFY ALL ROOF LOADS INCLUDING THE DEAD AND
 LIVE LOADS, INCLUDING THE ATTIC LIVE LOAD AS REQUIRED
 BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT).
 ***NOTE: ALSO COORDINATE LOADS WITH THOSE SHOWN ON
 TRUSS PACKAGE.
  
 B)REVISE ROOF NAILING TYPE SPECIFIED FOR GABLE
 ENDS ON ROOF NAILING NOTETO COMPLY WITH SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.(REPEAT
 COMMENT).
  
 C)NOWIS MISSING THE DETAIL SECTIONSHOWING THE
 NEW KNEE WALL.NEEDSTO SPECIFY ALL FASTENERS FOR
 TOP AND BOTTOM OF 2X8 KNEE WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH WIND
 LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT).
  
 D) CONNECTOR SPECIFIED ON TYPICAL WALL SECTION DON'T
 MATCH THOSE SHOWN ON THE TRUSS CONNECTOR SCHEDULE.
 REVISE AS REQUIRED TO MATCH.
  
 E)SPECIFY LOCATION (OR SPACING)OF USP TA22 TO
 RESIST THE UPLIFT LOADS OF GABLE END TRUSS. SEE TRUSS
 PACKAGE FOR LOCATION OF BEARING POINTS WHERE CONNECTOR
 NEEDS TO BE INSTALLED TORESIST THE CALCULATED LOADS.
 (REPEAT COMMENT).
  
 6- DESIGN PROFESSIONAL TO PAYFOUR TIMES THE FEE
 ($1,421.67) FOR REPETITIVE PLAN REVIEWSAS REQUIRED BY
 FLORIDA STATUTE 553.80(2)(B). SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-10 Cont ID  
Sent By jgomez Date 2008-06-10 Time 09:31 Rev Time 0.00
Received By jgomez Date 2008-06-09 Time 13:24 Sent To PC
Notes
2008-06-10 09:31:52RESIDENTIAL ADDITION, BUILDING REVIEWTHIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
 ***NOTE: THIS MAY BE DONE AT TIME OF PRINTING THE
 PERMIT TO AVOID EXPIRATION OF DOCUMENT.
  
 2-MASONRY GABLE END TO COMPLY WITH SEC.R609.4 OF
 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
 DETAILS SHOWN ON PLANS DON'T PROVIDE COMPLETE
 INFORMATION.
 PROVIDE THE FOLLOWING INFORMATION:
 A) SPECIFICATIONS FOR ALL FASTENERS. AND SHOWHOW
 ARE THE LOADS TRANSFERRED TO WALLS TO COMPLY WITH SEC.
 R601.2OF 2004 FLORIDA RESIDENTIAL CODE.
 *** NOTE: SPECIFY LOCATION OF CONNECTOR TA22(L1).SEE
 TRUSSS TO1GE TO SEEPOINTS WHERE CONNECTORS ARE
 REQUIRED TO PROVIDE UPLIFT RESISTANCE.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) AWNING WINDOW. (IF THIS IS THE TYPE OF WINDOW TO
 BE USED ON MASTER BEDROOM EAST WALL. (REPEAT
 COMMENT).
 *** NOTE: FLOOR PLAN CALLS FOR 22SH WINDOW, WHILENEW
 EAST ELEVATIONSHOWS A 36"X20" AWNING WINDOW. CLARIFY
 AS REQUIRED. IN ADDITION, CLARIFY WHY SUBMITTING2
 DIFFERENT PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS.
 TWO FROM LAWSON INDUSTRIES AND ONE FROM SECURITIES
 IMPACT WINDOWS?
  
 B) FRENCH DOORS.
 ***NOTE: ONLY ONE COPY WAS SUBMITTED. NEED TO SUBMIT
 TWO COPIES.
  
 C) ALL SIMPSON OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND DETAILS. (REPEAT COMMENT).
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE WHERE CONNECTOR IS SHOWN. SOME PRODUCT
 APPROVALS SUBMITTED ARE FOR CONNECTORS NOT SPECIFIED ON
 PLANS. EG: NOA 03-0219.02 IF FOR UGTS AND LUGT2
 CONNECTORS. WHERE ARE THESE CONNECTORS SPECIFIED ON
 PLANS?
  
 D) PRECAST LINTELS.
 ***NOTE: ONLY THE COVER PAGE OF NOA 06-0222.01 WAS
 SUBMITTED. NEED TO PROVIDE COMPLETE NOA AND PROVIDE TWO
 COPIES.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BYSEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- SURVEY:
 A) REVISE ADDITION BUILDING DIMENSION TO MATCH
 REVISED FLOOR PLANS. (REPEAT COMMENT).
  
 B) NEED SURVEYOR'S ORIGINAL SIGNATURE (REPEAT
 COMMENT).SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 472FLORIDA STATUTE.
  
 6- ENERGY CALCULATIONS:
 A) ITEM #7A)IS USING A SPECIFIC U-FACTOR OF U=1.7.
 PROVIDE PROOF THAT WINDOWS AND DOORS MEET THIS SPECIFIC
 U FACTOR. OTHERWISE USE THE DEFAULT VALUE. SEE SEC.
 13-104.4.5 FBC 2004.
  
 7- TRUSS PACKAGE:
 A) TRUSS ENGINEER TO COMPLY WITH SEC. 61G15-31.003.
 NEED TO WRITE DESIGNER OF RECORD NAME AND ALL SHEETS
 NEED TO BE NUMBERED AND COORDINATED WITH THE INDEX
 SHEET AND PROVIDE THE TRUSS ENGINEER INFORMATION ON
 EACH SHEET. (REPEAT COMMENT).
  
 B) INDEX SHEET NEEDS TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE. NOT COPY.SEC. 61G15-31.003 FLORIDA
 ADMINISTRATIVE CODE. (REPEAT COMMENT).
  
 C) REVISE BUILDING DIMENSIONS TO MATCH REVISED
 PLANS. (REPEAT COMMENT).
  
 ***ONE SET WILL BE RETAINED IN THIS OFFICE TO BE SEND
 TO THE BOARD OF ENGINEERS.
  
 8-ARCHITECT TO REVIEW AND APPROVEREVISED TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- SHEET A-1:
 A) UPDATE ALL REFERENCE STANDARDS SHOWN ON THE
 FOUNDATION NOTES. (REPEAT COMMENT). SEE CHAPTER 43 OF
 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT YEAR TO BE
 REFERENCED AND REVISE AS REQUIRED.
  
 B) CLARIFYTHICKNESS OF CONCRETE SLAB. BUILDING
 SECTION 2 ON SHEET A-4 CALLS FOR 6" CONCRETE SLAB,
 WHILE FOUNDATION PLAN CALLS FOR 4" CONCRETE SLAB.
 REVISE AS REQUIRED TO MATCH. (REPEAT COMMENT).
  
 C) FOOTING DETAIL 1/A-1 DOESN'T MATCHFOOTING SHOWN
 ON FOUNDATIONPLAN AND IT DOESN'T SPECIFY SPACING FOR
 DOWELS.PROVIDE COMPLETE AND CORRECT INFORMATION.
 (REPEAT COMMENT).
  
 10- SHEET A-2:
 A) BUILDING SIZE WAS REVISED. NEED TO REVISE AREA
 CALCULATIONS ALSO. (REPEAT COMMENT).
  
 B)COMPLY WITH SEC. R311.5.3 OF 2004 FLORIDA
 RESIDENTIAL CODE.PROVIDE DIMENSIONS FOR RISERS AND
 TREADS AND REVISE DRAWING ACCORDINGLY. (REPEAT
 COMMENT).
 *** FLOOR PLAN SHOWS THREE RISERS BUT SPECIFIES(2)
 NEW 7.5" R STEPS.REVISE AS REQUIRED AND ALSO SPECIFY
 SIZE OF TREAD TO VERIFY COMPLIANCE WITH CODE SECTION
 CITED ABOVE.
  
 C) CLARIFY IF WINDOW ON MASTER BEDROOM EAST WALL IS
 A SINGLE HUNG WINDOW OR AWNING WINDOW. SEE EAST
 ELEVATION AND REVISE AS REQUIRED. (REPEAT COMMENT).
  
 11- SHEET A-4:
 A)COORDINATELOADS SHOWN ON TYPICAL END DETAIL
 AND LOADS SHOWN ON ROOF FRAMING NOTE #3 AND ON NEW ROOF
 LOADING TABLE. (REPEAT COMMENT).
  
 B)SPECIFY ROOF SHEATHING NAIL TYPE AND SPACING TO
 BE USED INCLUDING ON ROOF ZONE #3.SEE SEC. R803.2.3.1
 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. TYPE AND
 SPACING TO BE USED.REVISE INFORMATION ON ROOF NAILING
 NOTE, AND ON BOTH BUILDING SECTIONS TO MATCH. (REPEAT
 COMMENT).
  
 C)DETAIL SECTION#4 NEEDSTO SPECIFY ALL
 FASTENERS FORTOP AND BOTTOM OF 2X8 KNEE WALL. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH WIND LOADS OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE. (REPEAT COMMENT).
 *** NOTE:IN ADDITION, THIS SECTION DOESN'T MATCH
 INFORMATION SHOWN ON ROOF FRAMING PLAN AND TRUSS
 PACKAGE.(REPEAT COMMENT).
  
 D) REVISE ROOF FRAMING NOTE #6.FLORIDA BUILDING
 CODE DOESN'T SPECIFY CONNECTORS.
  
 NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS OFFICE
 FOR FUTURE REFERENCE. ARCHITECT TO SEE ATTACHED COPY OF
 FLORIDA STATUTE 553.80(2)(B) REGARDING MULTIPLE PLAN
 REVIEWS AND FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-07 Cont ID  
Sent By jgomez Date 2008-03-07 Time 16:40 Rev Time 0.00
Received By jgomez Date 2008-03-07 Time 16:40 Sent To  
Notes
2008-03-07 16:56:01RESIDENTIAL ADDITION, BUILDING REVIEWSECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
 ***NOTE: THIS MAY BE DONE AT TIME OF PRINTING THE
 PERMIT TO AVOID EXPIRATION OF DOCUMENT.
  
 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. NEEDTHIS
 RECEIPT FOR CITY.
 NOTE: IF DRAWINGS ARE REVISED, THEN RESUBMIT PAGE WITH
 PALM BEACH COUNTY IMPACT FEES STAMP.
  
 3- MASONRY GABLE END TO COMPLY WITH SEC.R609.4 OF
 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
 DETAILS SHOWN ON PLANS DON'T PROVIDE COMPLETE
 INFORMATION.
 PROVIDE THE FOLLOWING INFORMATION:
 A) SPECIFICATIONS FOR ALL FASTENERS. AND SHOWHOW
 ARE THE LOADS TRANSFERRED TO WALLS TO COMPLY WITH SEC.
 R601.2OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) SPECIFICATIONS FOR GABLE END OUTLOOKERS AND
 FASTENER SPECIFICATIONS.
  
 C) FRAMING OF GABLE END IS NOT CLEAR.TYPICAL GABLE
 END WALL SECTION ON SHEET A-4 CALLS FOR END GABLE TRUSS
 AND IT SHOWS TWO TRUSSES. ON THE OTHER HAND,ROOF
 FRAMING PLAN AND TRUSS PACKAGE DON'TSHOW ANY GABLE
 END TRUSSES.REVISE AS REQUIRED TO MATCH.
  
 4- DETAIL 4/A-4DOESN'T SPECIFY CONNECTORS TO VERIFY
 COMPLIANCE WITH SEC. R601.2.SPECIFYING "SIMPSON
 STRAP"OR "16 GAUGE STRAP" IS NOT ADEQUATE INFORMATION
 TO VERIFY COMPLIANCE WITH THE CALCULATED LOADS OF SEC.
 R301.
 ALSO,SEE CATALOG FOR PROPER MASONRY TO WOOD CONNECTOR
 OR WOOD TO WOOD CONNECTOR TO BE SPECIFIED.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) AWNING WINDOW. (IF THIS IS THE TYPE OF WINDOW TO
 BE USED ON MASTER BEDROOM EAST WALL. PLANS DON'T
 SPECIFY TYPE). (REPEAT COMMENT).
  
 B) FRENCH DOORS. DRAWINGS SUBMITTED ARE NOT LEGIBLE.
 (REPEAT COMMENT)
  
 C) STORM SHUTTERS.FRENCHDOORS PRODUCT APPROVAL
 IS FOR NON-IMPACT DOORS.PROVIDE COMPLETE INSTALLATION
 SCHEDULE(SEE ATTACHED SAMPLE)AND CLEARLY MARKON
 SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED. (REPEAT COMMENT)
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. (REPEAT COMMENT).
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE WHERE CONNECTOR IS SHOWN.
  
 E) PRECAST LINTELS. (REPEAT COMMENT).
  
 6- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BYSEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. (REPEAT
 COMMENT).
  
 7- SURVEY:
 A) REVISE ADDITION BUILDING DIMENSION TO MATCH
 REVISED FLOOR PLANS.
  
 B) NEED SURVEYOR'S ORIGINAL SIGNATURE (REPEAT
 COMMENT).SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 472FLORIDA STATUTE.
  
 8- ENERGY CALCULATIONS:
 A) PROVIDE CORRECT NAME OF BUILDER AND COMPLETE ALL
 INFORMATION ON TOP OF FORM, INCLUDING ADDRESS OF
 PROJECT. (REPEAT COMMENT).
  
 B) CONDITIONED FLOOR AREA DOESN'T MATCH AREA SHOWN
 FOR THE ADDITION. (REPEAT COMMENT).
  
 C) UNDER ATTIC R-VALUE DOESN'T MATCH R VALUE SHOWN
 ON ARCHITECT'S PLANS. COORDINATE WITH ARCHITECT AND
 REVISE AS REQUIRED. (REPEAT COMMENT).
  
 9- TRUSS PACKAGE:
 A) LOADS DON'T MATCH LOADS SPECIFIED BY THE
 ARCHITECT OF RECORD. (REPEAT COMMENT).
  
 B) TRUSS ENGINEER TO COMPLY WITH SEC. 61G15-31.003.
 NEED TO WRITE DESIGNER OF RECORD NAME AND ALL SHEETS
 NEED TO BE NUMBERED AND COORDINATED WITH THE INDEX
 SHEET. (REPEAT COMMENT).
  
 C) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED AND
 PROVIDE THE ENGINEER'S INFORMATION. (REPEAT COMMENT).
  
 D) INDEX SHEET NEEDS TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE. NOT COPY.SEC. 61G15-31.003 FLORIDA
 ADMINISTRATIVE CODE.
  
 E) ARCHITECT'SBUILDING SECTIONS CALL FOR DOUBLE
 END TRUSSES.COORDINATE WITH ARCHITECT AND REVISE AS
 REQUIRED. (REPEAT COMMENT).
  
 F) REVISE BUILDING DIMENSIONS TO MATCH REVISED
 PLANS.
  
 10- ARCHITECT TO REVIEW AND APPROVETRUSS PACKAGE
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- SHEET SP-1:
 A) TITLE BLOCK IS MISSING ARCHITECT'S LICENSE NUMBER
 REQUIRED BY SEC. 61G1-16.004 FLORIDA ADMINISTRATIVE
 CODE. (REPEAT COMMENT). THIS COMMENT APPLIES TO ALL
 SHEETS.
  
 B) REVISE LOCATION OF REAR 1 STORY STRUCTURE.IT'S
 NOT LOCATED ON THE PROPERTY LINE. COORDINATE WITH
 SURVEY. ALSO, COORDINATE DIMENSIONS WITH SURVEY.
  
 12- SHEET A-1:
 A) UPDATE ALL REFERENCE STANDARDS SHOWN ON THE
 FOUNDATION NOTES. (REPEAT COMMENT). SEE CHAPTER 43 OF
 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT YEAR TO BE
 REFERENCED AND REVISE AS REQUIRED.
  
 B) CLARIFYTHICKNESS OF CONCRETE SLAB. BUILDING
 SECTION 2 ON SHEET A-4 CALLS FOR 6" CONCRETE SLAB,
 WHILE FOUNDATION PLAN CALLS FOR 4" CONCRETE SLAB.
 REVISE AS REQUIRED TO MATCH. (REPEAT COMMENT).
  
 C) DETAIL SECTIONS 3 AND 6 DON'T MATCH THOSE KEYED
 ON TYPICAL OPENING DETAIL #4. REVISE AS REQUIRED.
 (REPEAT COMMENT).
  
 D) FOOTING DETAIL 1/A-1 DOESN'T MATCHFOOTING SHOWN
 ON FOUNDATIONPLAN AND IT DOESN'T SPECIFY SPACING FOR
 DOWELS.PROVIDE COMPLETE AND CORRECT INFORMATION.
  
 13- SHEET A-2:
 A) BUILDING SIZE WAS REVISED. NEED TO REVISE AREA
 CALCULATIONS ALSO.
  
 B) 6" STEPS DON'T COMPLY WITH SEC. R311.5.3 OF 2004
 FLORIDA RESIDENTIAL CODE.PROVIDE DIMENSIONS FOR
 RISERS AND TREADS AND REVISE DRAWING ACCORDINGLY.
 (REPEAT COMMENT).
  
 C) EXISTING BEDROOMDOESN'THAVE ANY EMERGENCY
 EGRESS TO COMPLY WITH SEC. R310 OF 2004 FLORIDA
 RESIDENTIAL CODE.THE ONLY WINDOW WAS BLOCKED BY THE
 NEW ADDITION.
  
 D) SPECIFY ATTIC ACCESS AND LOCATION AS REQUIRED TO
 COMPLY WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 E) SPECIFYWHAT TYPE OF WINDOW IS THE36"X20"
 WINDOW LOCATED ON EAST WALL OF MASTER BEDROOM.
  
 F) WALL LEGEND FOR NEW SAFE ROOM STATES"EXISTING
 CONC. BLK WALL".EXISTING FLOOR PLANS SHOWS THIS AREA
 TO BE AN EXISTING SUN ROOM.CLARIFY/REVISE AS
 REQUIRED.
  
 14- SHEET A-3: REAR ELEVATION CALLS FOR NEW 2X8 KNEE
 WALL. THIS DOESN'T MATCH INFORMATION SHOWN ON BUILDING
 SECTIONS 1 AND 2 ON SHEET A-4. REVISE AS REQUIRED.
 (REPEAT COMMENT). GABLE END ON THIS SIDE DOESN'T HAVE A
 KNEE WALL.
  
 15- SHEET A-4:
 A) THERE ARE TWO SECTIONS ON THE ROOF FRAMING PLAN
 KEYED AS 1/A-4. REVISE AS REQUIRED.
  
 B) BOTH BUILDING SECTIONS CALL FOR DOUBLE GABLE END
 TRUSSES. ROOF FRAMING PLAN AND TRUSS LAYOUT DON'T
 PROVIDE ANYINFORMATION REGARDING THE GABLE END
 TRUSSES. REVISE AS REQUIRED TO MATCH.
  
 C) CLEARLY SPECIFY ALL DEAD AND LIVE LOADS INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BYTABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).NOTE:
 COORDINATE THIS LOADS WITH TRUSS ENGINEER.
  
 D) COORDINATELOADS SHOWN ON TYPICAL END DETAIL AND
 LOADS SHOWN ON ROOF FRAMING NOTE #3. (REPEAT COMMENT).
  
 ALSO, COORDINATE WITH TRUSS ENGINEER.
  
 E) SPECIFY ROOF SHEATHING NAIL TYPE AND SPACING TO
 BE USED INCLUDING ON ROOF ZONE #3.SEE SEC. R803.2.3.1
 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. TYPE AND
 SPACING TO BE USED.REVISE INFORMATION ON ROOF NAILING
 NOTE, AND ON BOTH BUILDING SECTIONS TO MATCH. (REPEAT
 COMMENT).
  
 F) FOOTING SHOWN ON BUILDING SECTION 2 DOESN'T MATCH
 FOOTING SHOWN ONBUILDING SECTION 1 AND FOUNDATION
 PLAN. REVISE AS REQUIRED.
  
 G) SECTIONS 1, 2AND 4 NEED TO SPECIFY ALL
 FASTENERS FOR GABLE END TRUSSES, GABLE END RAFTERS AND
 TOP AND BOTTOM OF 2X8 KNEE WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH WIND
 LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT).
 NOTE: JUST SPECIFYING SIMPSON STRAPS IS NOT ENOUGH
 INFORMATION.
 ALSO, MAKE SURE PROPER CONNECTORS ARE SPECIFIED. EG:
 WOOD TO WOOD CONNECTORS OR WOOD TO MASONRY CONNECTORS.
 SEE CATALOG.
  
 H) REVISE ROOF FRAMING NOTE #6.FLORIDA BUILDING
 CODE DOESN'T SPECIFY CONNECTORS.
  
 I) DETAIL 4 DOESN'T MATCHDETAIL 4 KEYED ON ROOF
 FRAMING PLAN. REVISE AS REQUIRED. (REPEAT COMMENT).
  
 NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS OFFICE
 FOR FUTURE REFERENCE. ARCHITECT TO SEE ATTACHED COPY OF
 FLORIDA STATUTE 553.80(2)(B) REGARDING MULTIPLE PLAN
 REVIEWS AND FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-07 Cont ID  
Sent By jgomez Date 2007-11-07 Time 16:57 Rev Time 0.00
Received By jgomez Date 2007-11-07 Time 07:41 Sent To P
Notes
2007-11-07 16:58:37RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST.
 REVIEW UNDER EXISTING BUILDING CODE 2004, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 OWES $799.04 FOR UPDATED VALUATION AND RADON FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 4- SPECIFY THE CALCULATED DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS AS REQUIRED BYSEC. R301 AND TABLE
 R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- MASONRY GABLE END TO COMPLY WITH SEC. R609.4 OF 2004
 FLORIDA RESIDENTIAL CODE. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH ABOVE MENTIONED
 SECTION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) AWNING WINDOW.
  
 B) FRENCH DOORS. DRAWINGS IN PRODUCT APPROVAL FL8795
 SUBMITTED ARE NOT LEGIBLE. NEED LEGIBLE DRAWINGS.
  
 C) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
 ***NOTE: PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE CONNECTOR ONLY.
  
 E) PRECAST LINTELS.
  
 7- ARCHITECT TO REVIEW AND APPROVE IN WRITING(NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- SPECIFY ONE HOUR FIRE RATED WALL ASSEMBLY FOR EAST
 WALL INCLUDING THE PROJECTION AS REQUIRED BY SEC.
 R302.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- PROJECTION ON EAST WALL IS NOT ALLOWED BECAUSE IT
 DOESN'T COMPLY WITH SEC. R302.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 10- OPENINGS ON EAST WALL ARE NOT ALLOWED BY SEC.
 R302.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 11-A) SURVEY TO SPECIFY SIDE SETBACK AND DISTANCE
 FROM PROPOSED ADDITION TO EXISTING 1 STORY BUILDING TO
 VERIFY COMPLIANCE WITH SEC. R302 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) SURVEY TO HAVE SURVEYOR ORIGINAL SIGNATURE AS
 REQUIRED BY SEC. 472 FLORIDA STATUTE.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE CORRECT NAME OF BULDERAND COMPLETE
 ALL-INFORMATION ON TOP OF FORM INCLUDING THE ADDRESS OF
 THIS PROJECT.
  
 B) CONDITIONED FLOOR AREA DOESN'T MATCH AREA SHOWN
 ON PLANS FOR THE ADDITION. REVISE AS REQUIRED.
  
 C) MAKE SURE UNDER ATTIC AREA ON ITEM 10(A) IS
 COORDINATED WITH ITEM 6.
  
 D) UNDER ATTIC R-VALUE DOESN'T MATCH R-VALUE
 SPECIFIED ON ARCHITECTURAL PLANS. REVISE AS REQUIRED.
  
 13- SOIL TEST REPORT ENGINEER TO PROVIDE HIS LICENSE
 NUMBER AS REQUIRED BY SEC. 61G15-23.002OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 14- TRUSS PACKAGE:
 A) LOADS DON'TMATCH LOADS SPECIFIED BY THE
 ARCHITECT OF RECORD.
 ***NOTE: COORDINATE WITH ARCHITECT FOR SPECIFIED LOADS
 TO AVOID CONFLICTS.
  
 B) IF ENGINEER WANTS TO COMPLY WITH SEC.
 61G15-31.003, THEN NEEDS TO PROVIDE THE DESIGNEROF
 RECORD NAME AND ALL SHEETS NEED TO BE NUMBERED SO THEY
 CAN BE REFERENCED BACK IN THE INDEX SHEET.
  
 C) TRUSS LAYOUT NEEDS TO BE SIGNED, SEALED, DATED
 AND WITH THE ENGINEER'S COMPLETE INFORMATION AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 D) ARCHITECTURAL PLANS CALL FOR DOUBLE GABLE END
 TRUSSES. COORDINATE FRAMING LAYOUT WITH ARCHITECT PRIOR
 TO SUBMITTAL TO AVOID CONFLICTS.
  
 15- SHEET SP-1:
 A) REVISE CONCRETE BLOCK ALLOWABLE STRESS SHOWN ON
 TYPICAL PRIVACY WALL SECTION. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 B) NORTH ARROW IS INCORRECT. SEE SURVEY AND REVISE.
  
 C) TITLE BLOCK IS MISSING ARCHITECT'S LICENSE NUMBER
 AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 16- SHEET A-1:
 A) UPDATE ALL REFERENCE STANDARDS SHOWN ON
 FOUNDATION NOTES. SEE CHAPTER 43 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT STANDARDS AND YEAR ADOPTED
 BY THIS CODE AND REVISE AS REQUIRED.
  
 B) CLARIFY THICKNESS OF CONCRETE SLAB.WALL
 SECTIONS ON SHEET A-4 CALL FOR 6" CONCRETE SLAB, WHILE
 FOUNDATION PLAN CALLS FOR 4". REVISE AS REQUIRED.
  
 C) DETAIL SECTIONS 3 AND 6 DON'T MATCH THOSE KEYED
 ON TYPICAL OPENING DETAIL #4.REVISE AS REQUIRED.
  
 17- SHEET A-2:SPECIFY SIZE OF TREADS AND RISERS AT
 STEPS BY FRENCH DOORS TO VERIFY COMPLIANCE WITH SEC.
 R311.5.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ALSO, STEPS ARE NOT DRAWN TO SCALE. THEY ARE SHOWN AS
 6"WIDE TREADS. REVISE AS REQUIRED.
  
 18- SHEET A-3:REAR ELEVATION CALLS FOR NEW 2X8 KNEE
 WALL. THIS DOESN'T MATCH INFORMATION SHOWN ON TYPICAL
 WALL SECTION 1/A-4 AND BUILDING SECTION 2/A-4. REVISE
 AS REQUIRED TO MATCH.
  
 18- SHEET A4:
 A) ROOF FRAMING PLAN IS MISSING THE RIDGE LINE AND
 DOESN'T MATCH TRUSS LAYOUT.COORDINATE WITH TRUSS
 ENGINEER AND REVISE AS REQUIRED.
  
 B) CLEARLY SPECIFY ALLDEAD AND LIVE LOADS
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BYSEC. R301
 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: COORDINATE THESE LOADSWITH TRUSS ENGINEER.
  
 C) LOADS SPECIFIED ON ITEM #3 OF ROOF FRAMING NOTES
 DON'T MATCH WITH THOSE LOADS SPECIFIED ON TYPICAL END
 DETAIL. REVISE AS REQUIRED.
  
 D) ROOF NAILING NOTE AND SPECIFICATIONS FOR ROOF
 SHEATHING FASTENING ON WALL SECTIONS 1 AND 2 DON'T
 MATCH.SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM TYPE OF NAIL AND FASTENER
 SPACING REQUIRED INCLUDING FOR ROOF ZONE 3 AND REVISE
 AS REQUIRED.
  
 E) SECTIONS 1,2 AND 4 NEED TO SPECIFY ALL
 FASTENERS FOR GABLE END TRUSSES, GABLE END RAFTERS AND
 TOP AND BOTTOM OF2X8 KNEE WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 CALCULATED UPLIFT LOADS PERSEC. R301OF 2004 FLORIDA
 RESIDENTIAL CODE. SEE SIMPSON CATALOG AND SPECIFY
 CONNECTORACCORDING TO APPLICATION WOOD TO WOOD
 CONNECTOR OR WOOD TO MASONRY CONNECTOR.
  
 F) REVISE ROOF FRAMING NOTE #6. IT'S THE ARCHITECT
 RESPONSIBILITY TO SPECIFY CONNECTIONS, NOT THE FBC.
  
 19- DETAILS 3 AND 4DON'T MATCH THE DETAIL SECTION AS
 KEYED ON THE ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2008-07-25 Time 16:50 Sent To M
Notes
2008-07-28 08:36:27 
 ** DENIED4TH REVIEW **
  
 *** SOME NOTES FROM PREVIOUS REVIEW ARE STILL THE SAME.
 SOME ARE NOW NEW DUE TO REVISED PLANS.
  
 1) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR IS
 STILL MISSING AFTER THE FIRST MEANS OF DISCONNECT TO
 THE 150 AMP SUB PANEL.
 250.110,250.122
  
 2) NOTE: PLEASE SEE THE RISER STILL DOES NOT SHOW ANY
 GROUNDING ELECTRODE SYSTEM AT THE MAIN HOUSE AS
 REQUIRED PER 250.50,250.32
  
 3) NOTE: THE RISER HAS BEEN REVISED HOWEVER THE
 EXISTING PANEL IN THE MAIN HOUSE IS NOT SHOWN. HOW IS
 THIS PANEL FED? WHERE IS THE OVER CURRENT PROTECTION?
 THE NEW PANEL SCHEDULE DOES NOT INDICATE ANY BREAKER OR
 FEED TO THIS EXISTING PANEL WHICH IS SHOWN TO REMAIN.
 PLAN SHOWS TWO PANELS AT MAIN HOUSE YET NO PANEL
 SCHEDULES ETC ARE SHOWN
 NO FEEDERS, ETC.
 215.5,220, 240, 310.16, ETC
 FBC106.3.5.4
  
 4) NOTE: THE RISER HAS BEEN REVISED AND NOW SHOWS NEW
 150AMP COMING FROM WHAT IS BEING CALLED AN EXISTING
 2-GANG METER. WHAT SIZE IS THIS EXISTING SERVICE AND
 WHAT IS THE AMPERAGE OF THE 2-GANG METER CAN?
 ADDING NEW 150AMP MAIN AND INCREASING THE LOAD ON THE
 SERVICE YET NO LOAD CALCULATIONS ON THE SERVICE OR SIZE
 OF THE EXISTING SERVICE ARE SHOWN.
 230.70, 230.71, 240,220 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE
 AHU IS STILL NOT CORRECT. THE PREVIOUS PLANS WAS TOO
 HIGH AND DID NOT MEET 424.11E AND NOW THE OVER CURRENT
 PROTECTION IS NOT LARGE ENOUGH PER 424.3B. PLEASE
 ADJUST.
  
 6) NOTE: PLEASE SEE THERE ARE STILL NO DISCONNECTS ETC
 SHOWN FOR NEW AC SYSTEM. 440.11,210.63,210.70.
  
 *** PLEASE SUBMIT ELECTRICAL PLANS MEETING THE
 *MINIMUM* PER THE NATIONAL ELECTRICAL CODE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 13:56 Sent To M
Notes
2008-06-03 13:57:08** DENIED 3RD REVIEW **
  
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
 **PLEASE SEE SOME ITEMS BROUGHT UP IN MEETING HELD
 BEFORE PLANS WERE RESUBMITTED ARE STILL IN NEED OF
 ADDRESSING.
 **PLEASE SEE SOME NEW ITEMS ARE NOW NOTED AS ITEMS
 CHANGED OR REVISED SINCE LAST REVIEW. THESE ITEMS WERE
 GONE OVER IN MEETING HOWEVER NOT CORRECTED ON PLANS.
  
 1) NOTE: PLEASE SEE THE MINIMUM CODES ARE STILL NOT
 STATED ON PLANS. THIS HAS BEEN REQUESTED THREE TIMES
 AND YET STILL NOT DONE.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC/ RESIDENTIAL/ EXISTING W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE SMALL APPLIANCE CIRCUITS ARE NOW
 BEING SHOWN WITH 30AMP 1-POLE BREAKERS WHICH IS NOT
 PERMITTED.
 210.20
  
 3) NOTE: PLEASE SEE AHU IS NOW SHOWING 60AMP OVER
 CURRENT PROTECTION ON 7.5KW/8KW HEAT FOR AHU WHICH IS
 TOO HIGH.
 424.3B (125% MIN, 424.11E 150% MAXIMUM)
  
 4) NOTE: PLEASE SEE #6 CONDUCTORS NOW BEING SHOWN ON
 30AMP BREAKER FOR WATER HEATER WHICH IS NOT POSSIBLE.
 THE BREAKER IS NOT RATED NOR WILL IT ACCEPT #6 AWG. NEC
 110.3
  
 5) NOTE: PLEASE SEE THE RISER STILL SHOWS A #6/0 FOR
 EQUIPMENT GROUNDING. THERE IS NO SUCH CONDUCTOR SIZE.
 PLEASE SEE 250.122 FOR SIZING OF EQUIPMENT GROUNDING
 CONDUCTORS.
 BROUGHT UP IN MEETING.
  
 6) NOTE: PLEASE SEE RISER SHOWS EQUIPMENT GROUNDING
 AFTER METER AND BEFORE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED PER 250.6, 250.24
 THIS CREATES OBJECTIONABLE CURRENTS WHICH IS NOT
 PERMITTED.
 ** PREVIOUS NOTES AND MEETING
  
 7) NOTE: PLEASE PROVIDE AN ACCURATE AND CODE COMPLIANT
 RISER DIAGRAM AND COORDINATEWITH PLANS.
 THE PLANS SHOWS EXISTING METERS AT REAR BUILDING AND
 RISER EVEN CONTAINS A NOTE WHICH STATES THIS HOWEVER IF
 THIS IS THE CASE, NO MAIN IS SHOWN AT REAR BUILDING FOR
 GROUPING PER 230.72
 PLEASE KNOW IF SERVICE IS AT MAIN HOUSE, THEN NO FEEDS
 ARE SHOWN TO REAR BUILDING. AT MEETING IT WAS
 DETERMINED THE WATER HEATER ETC MAY HAVE BEEN FED FROM
 REAR BUILDING WHICH IS ON ANOTHER SERVICE.
 PLEASE STILL SHOW THE MAIN HOUSE CONTAINING A SERVICE
 AND IT IS SHOWN TO BE RELOCATED.
 HOW IS ANY OF THIS CODE COMPLIANT PER 215.5, 240.4,
 310.16, 230.70, 230.2, 230.71, 230.72, 230.76, 230.79.
 PLEASE SEE 225.31-225.9 FOR BRANCH CIRCUITS AND FEEDERS
 AT DETACHED BUILDINGS.
 PLEASE SUBMIT COMPLETE PLANS SHOWING ALL ELECTRICAL
 EQUIPMENT, SERVICE, DISCONNECTS, GROUNDING ETC. PLEASE
 SEE 2005 NATIONAL ELECTRICAL CODE/ NFPA-70. FBC
 106.3.5.4, 106.1.2
 ** PREVIOUS NOTES AND MEETING**
  
 8) NOTE: PLEASE SEE 250.32, 250.50 WITH RESPECT TO
 GROUNDING ELECTRODE SYSTEMS AT DETACHED BUILDINGS. AS
 THE ACTUAL SERVICE, LOCATION, MAINS, SERVICE ETC HAS
 NOT BEEN CLEARLY SHOWN OR DETERMINED, THE GROUNDING
 ELECTRODE SYSTEM CAN NO BE REVIEWED AT LAST POSSIBLE
 SCENARIO FOR CODE COMPLIANCE.
 ** PREVIOUS NOTES AND MEETING*
  
 9) NOTE: PLEASE SEE NO AIC RATING IS STILL SHOWN.110.9
 ** PREVIOUS NOTES AND MEETING**.
  
 10) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION WAS GONE
 OVER IN MEETING HELD BEFORE PLANS WERE RESUBMITTED
 ALONG WITH PREVIOUS REVIEW COMMENTS.
 PLEASE SEE RISER STILL NOTES AFCI PROTECTION FOR
 RECEPTACLES ONLY. THE NOTES ON THE RIGHT HAND SIDE OF
 PLANS DO NOTE AFCI FOR BRANCH CIRCUITS IN BEDROOMS
 WHICH IS OK.
 PLEASE REMOVE NOTE ABOVE THE PANEL.
  
 11) NOTE: PLANS/RISER STILL SHOWS A NOTE WHICH MENTIONS
 SUB PANEL TO BE USED FOR CONDENSING UNIT, SPRINKLER
 TIME CLOCK ETC AS ALTERNATIVE. THERE IS NO OTHER SUB
 PANEL SHOWN ON PLANS. PLANS ONLY SHOW ONE PANEL. ??
  
 12) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW NEW
 CONDENSING UNIT, DISCONNECT, WP GFI REQUIRED ETC.
 PLEASE SEE 440.11 FOR MISSING DISCONNECT.
 PLEASE SEE 210.63 FOR RECEPTACLE AND 210.8A FOR GFI
 PROTECTION.
  
 13) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW ANY
 NEW ELECTRICAL FOR NEW AHU LOCATED AT FRONT OF EXISTING
 HOUSE.
 440.11, 210.63, 210.70
  
 14) NOTE: R313 OF THE 2004 RESIDENTIAL CODE SHALL BE
 REDLINED ON PLANS ONCE ALL OTHER ITEMS ARE ADDRESSED.
  
 15) NOTE: PLEASE KNOW IF PLANS COME BACK WITH OUT
 MINIMUM CODE COMPLIANCE FOR ELECTRICAL THIS OFFICE MAY
 HAVE NO CHOICE BUT TO RETAIN PLANS AND POSSIBLY FORWARD
 TO THE STATE BOARD OF ARCHITECTS.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-06 Cont ID  
Sent By dpalmer Date 2008-03-06 Time 16:46 Rev Time 0.00
Received By dpalmer Date 2008-03-06 Time 16:46 Sent To B
Notes
2008-03-06 16:47:15** DENIED 2NDREVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 MANY OF THESE COMMENTS BELOW ARE THE SAME AS PREVIOUS.
  
 ** PLEASE SEE THERE ARE SEVERAL NEW COMMENTS ALSO AS
 SOME ITEMS ARE NOW ONLY BEING SUBMITTED FOR THE FIRST
 TIME FOR REVIEW.
  
 ** PLEASE ALSO KNOW THERE ARE ITEMS STILL NOT SHOWN ON
 PLANS WHICH SIMPLY CAN NOT BE REVIEWED IF NOT SHOWN OR
 SUBMITTED.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE REQUIRED ON
 THE ELECTRICAL PLANS.
 2004 FBC W2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 ** PLANS STILL ONLY STATE PER LOCAL CODES BUT DONOT
 PROVIDE WHAT CODES THIS DESIGNED TO AS REQUIRED.
  
 2) NOTE: PLEASE SEE PLANS ARE NOW SHOWING A NEW RISER
 WHICH NOW CONTAINS SEVERAL COMMENTS.
 A) PLEASE SEE THE RISER NOW SHOWS NEW MAIN AND THEN
 STATES *IF REQUIRED* ??? HOW CAN THIS SAY *IF REQUIRED*
 WHEN A MAIN IS REQUIRED.
 B) PLEASE SEE THE RISER SHOWS A 125AMP MAIN FEEDING A
 100AMP PANEL WHICH IS NOT PERMITTED. THE PANEL AS SHOWN
 ON PLANS (PANEL SCHEDULE) SHOWS 125AMP. PLEASE
 COORDINATE.
 C) HOW CAN THIS BE A 100AMP PANEL WHEN THE LOAD SHOWN
 AT 114AMPS EXCEEDS THAT RATING?
 D) PLEASE SEE THE RISER STILL DOES NOT SHOW OTHER
 STRUCTURE ON PROPERTY, LOAD ETC??
 E) PLEASE INDICATE THE REQUIRED AIC RATING OF
 MAINS/EQUIPMENT.
 230.70, 230.71, 230.72, 230.2, 110.9 ETC
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULES MEETING NEC
 408.4, 240.4, 310.16 ETC
 PLEASE SEE THE ROOMS ARE AREAS ON PANEL SCHEDULE NEED
 TO BE SPECIFIC.
 PLEASE SEE THE PANEL SCHEDULE SHOWS FOR EXAMPLE #8 ON
 20AMP BREAKER, THIS IS NOT POSSIBLE.
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C1, 210.52 AS ONE
 OR MORE OF THE SMALL APPLIANCE AND LAUNDRY CIRCUITS
 SHALL MEET THESE SECTIONS FOR LOADS AND HOW THEY ARE
 FIGURED INTO CALCULATIONS.
 PLEASE SEE THE MINIMUM PER CIRCUIT SHALL BE 1500VA
 EACH.
 HOW DO 4 CIRCUITS WHICH ARE SUPPOSED TO BE 1500VA
 MINIMUM ADD UP TO 3500VA. (SEE CIRCUITS 10-13)
  
 5) NOTE: PLANS MENTIONS PANELS AND SERVICE TO BE
 RELOCATED HOWEVER BASED ON PLANS AND RISER THE PLANS
 ARE NOT CLEAR WHERE ALL EQUIPMENT IS BEING INSTALLED.
 PLEASE CLEAR THIS UP.
 110.26, 240.24
  
 6) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS ON
 EXISTING SERVICES; PLEASE SEE THE REST OF 220 FOR NEW
 SERVICES.
  
 7) NOTE: PLEASE SEE THE WATER HEATER IS SHOWING 7.5KW
 AND THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES ARE
 SMALLER THAN REQUIRED.
 PLEASE SEE 422.13
  
 8)NOTE: PLEASE SEE THE PLANS INDICATE ARC FAULT
 PROTECTION ONLY FOR RECEPTACLES HOWEVER UNDER THE 2002
 AND 2005 NEC 210.12 REQUIRES AFCI PROTECTION FOR ALL
 OUTLETS. SEE THIS CODE SECTION FOR REQUIREMENTS
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 08:23 Rev Time 0.00
Received By dpalmer Date 2007-10-26 Time 16:28 Sent To M
Notes
2007-10-27 08:23:212007-10-27 08:23:21
  
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE SEE THAT PLANS ARE NOT COMPLETE AT THIS
 TIME WITH ALL INFORMATION FOR MINIMUM CODE REVIEW.
 PLEASE SEE THE BELOW COMMENTS FOR ITEMS WHICH ARE
 MISSING.
 **THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE THE SEALS ON MANY OF THE SHEETS ARE
 NOT CLEAR AND VISIBLE AS REQUIRED PER FS 481.221.
 PLEASE BE SURE TO ADDRESS.
  
 4) NOTE: PLEASE SEE ZONING COMMENTS AS THE SET BACK ON
 THE WEST SIDE OF THE DWELLING WILL HAVE AN AFFECT ON
 ALL TRADES AND THE DESIGN AS SET-FORTH.
  
 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS.
 PLANS INDICATE A NEW SERVICE HOWEVER NO ELECTRICAL
 RISER DIAGRAM WAS SUBMITTED FOR REVIEW.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM.
 PLEASE SHOW ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS,
 GROUNDING, SIZE OF EQUIPMENT, AIC RATINGS ETC. PLEASE
 SEE 215.5, 230.4, 310.16, 250.50, 250.122, 250.66,
 110.9 ETC.
 FBC 106.3.5.4.
  
 6) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 NEW ADDITION AND EXISTING LOADS.
 PLEASE SEE 220.16A1 AND 220.87.
 PLEASE SEE THE CODE AS REFERENCED IN PARTIAL LOAD
 CALCULATIONS IS NO LONGER IN VALID. THE NEW CODE AS OF
 DECEMBER 06 IS THE 2005 NEC.
 PLEASE INDICATE ALL MINIMUM LOADS ALONG WITH NEW LOADS
 AND DEDICATED LOADS AS REQUIRED.
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1.
 PLEASE SEE MISSING SMOKE ALARMS FOR NEW AREAS. PLEASE
 ALSO PROVIDE A COMPLETED FLOOR PLAN OF THE EXISTING
 DWELLING WHICH INDICATES SMOKE ALARMS EITHER EXISTING
 OR NEW TO BE INSTALLED. THESE SHALL MEET NFPA-72
 11.5.1.1, 11.8.3.
  
 8) NOTE: PLEASE SEE THAT THE ELECTRICAL PLANS DO NOT
 CONTAIN ANY INFORMATION ON THE NEWA/C SYSTEM TO BE
 INSTALLED. PLEASE PROVIDE THE MINIMUM WIRING, OVER
 CURRENT PROTECTION, LOADS ETC ON PANEL SCHEDULE. PLEASE
 PROVIDE MINIMUM DISCONNECTS PER 440.11. PLEASE SEE
 210.63 AND 210.8 FOR MINIMUM SERVICE RECEPTACLES
 REQUIRED.
  
 9) NOTE: PLEASE PROVIDE A COMPLETED PANEL SCHEDULE
 SHOWING THE EXISTING CIRCUITS AND NEW TO BE INSTALLED.
 PLEASE SEE 408.4, 240.4, 310.16 ETC.
  
 10) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 REQUIRED DEDICATED BATH CIRCUIT(S).
 MUST BE 20AMP AND MUST BE #12.
 PLEASE SEE THE PARTIAL PANEL SCHEDULE SHOWN ONLY
 CONTAINS ONE 20AMP GFI CIRCUIT WHICH INDICATES THIS AS
 *OPTIONAL*??
 PLEASE COMPLETE.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED
 CIRCUITS PER 210.12.
 PLEASE LIST ON PANEL SCHEDULE TO BE PROVIDED. 210.12,
 408.4.
  
 12) NOTE: PLEASE SEE RECEPTACLES MISSING PER 210.52.
 PLEASE SEE NORTH WALL AND SOUTH WALLS OF NEW LIVING
 ROOM AREA.
  
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 14:28 Sent To E
Notes
2008-07-18 14:28:59TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 16:24 Sent To Z
Notes
2008-07-09 16:25:12TO "Z" BOX/RESUB--NEW SHEETS SUBMITTED, ALL TRADES TO
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 16:39 Sent To Z
Notes
2008-05-19 16:39:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 10:50 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 10:50 Sent To Z
Notes
2008-02-26 10:50:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-09 Cont ID  
Sent By mperson Date 2007-11-09 Time 15:54 Rev Time 0.00
Received By mperson Date 2007-10-24 Time 11:38 Sent To  
Notes
2007-10-24 11:42:17TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-07-28 Cont ID  
Sent By tgordon Date 2008-07-28 Time 09:19 Rev Time 0.40
Received By tgordon Date 2008-07-28 Time 09:19 Sent To P
Notes
2008-07-28 09:22:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE EQUIPMENT SCHEDULE IS NOW MISSING FROM THE NEW
 MECHANICAL PLAN. PLEASE ADD AN EQUIPMENT SCHEDULE TO
 THE MECHANICAL PLANS SHOW THE MANUFACTURE, MODEL
 NUMBER, SEER, ETC. AND ALL OTHER PERTINENT INFORMATION,
 SEE WPB AMEND. 106.3.5.4.
  
 2) PLEASE SHOW THE BATHROOM EXHAUST FANS ON THE
 MECHANICAL PLAN AS THEY ARE ON THE ELECTRICAL PLAN AND
 PER 2004 FBC/R M1506.1 THE MASTER BATHROOM SHOWER AREA
 IS REQUIRED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-03 Cont ID  
Sent By tgordon Date 2008-06-03 Time 15:34 Rev Time 0.30
Received By tgordon Date 2008-06-03 Time 15:34 Sent To P
Notes
2008-06-03 15:37:03*** PROVISO ***
 1) VENTILATION SHALL BE PROVIDED FOR THE MASTER
 BATHROOM SHOWER AREA PER 2004 FBC/R M1506.1.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-26 Cont ID  
Sent By tgordon Date 2008-02-26 Time 15:34 Rev Time 0.30
Received By tgordon Date 2008-02-26 Time 15:34 Sent To P
Notes
2008-02-26 15:37:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-29-07 NOTE #2 THE
 MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT (STEPHAN A. YECKES) AS HIS INFORMATION IS IN
 THE TITLE BLOCK, SEE FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By tgordon Date 2007-10-29 Time 13:30 Rev Time 0.30
Received By tgordon Date 2007-10-29 Time 13:30 Sent To P
Notes
2007-10-29 13:42:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) A MECHANICAL PLAN IS UP SIDE DOWN IN ONE OF THE SETS
 OF PLANS, PLEASE CORRECT.
  
 2) THE MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY
 THE ARCHITECT (STEPHAN A. YECKES) AS HIS INFORMATION IS
 IN THE TITLE BLOCK, SEE FAC 61G1-16.003.
  
 3) NEED TO ADD AN EQUIPMENT SCHEDULE TO THE MECHANICAL
 PLANS SHOW THE MANUFACTURE, MODEL NUMBER, SEER, ETC.
 AND ALL OTHER PERTINENT INFORMATION, SEE WPB AMEND.
 106.3.5.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-28 Cont ID  
Sent By mperson Date 2008-07-28 Time 13:20 Rev Time 0.00
Received By mperson Date 2008-07-28 Time 13:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-04 Cont ID  
Sent By mperson Date 2008-06-04 Time 08:25 Rev Time 0.00
Received By mperson Date 2008-06-04 Time 08:25 Sent To B
Notes
2008-06-04 09:26:24****************PROVISO****************
 A} THE SHOWER WASTE PIPE MINIMUM SIZE SHALL BE 1-1/2"
 IN DIAMETER. PER FBC-2004 PLUMBING SECTION 417.3 SHOWER
 WASTE OUTLETS.
  
 B} A CLEANOUT IS REQUIRED AT THE BASE OF THE LAVATORY
 WASTE STACK DUE TO INDICATING THAT AN 1-1/4" TRAP IS
 BEING USED. PER FBC-2004 PLUMBING SECTION 708.3.4 BASE
 OF STACK AND SECTION 708.7 MINIMUM SIZE, EXCEPTIONS
 (1).
  
 C} NOTE: IF SANITARY SYSTEM IS NOT INSTALLED PER SHEET
 A-1 APPROVED PLUMBING RISER A REVISION WILL BE
 REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By mperson Date 2008-03-05 Time 10:21 Rev Time 0.00
Received By mperson Date 2008-03-05 Time 10:21 Sent To E
Notes
2008-03-05 11:05:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS
 PLUMBING REVIEW COMMENTS.
 **NOTE: THERE WERE NO DESIGNER RESPONSES TO THE
 PLUMBING COMMENTS.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **OK** COMMENT ADDRESSED.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. SHEET A-1 SANITARY PLUMBING RISER: THE WASTE PIPING
 TO THE NEW BATH SHOWER IS INCOMPLETE. A TRAP IS BEING
 INDICATED HOWEVER IT IS NOT BEING SHOWN AS CONNECTING
 TO THE WASTE OR VENT SYSTEM. PER FBC PLUMBING SECTION
 701.1 SCOPE AND SECTION 901.1 SCOPE.
  
 6. SHEET A-1 SANITARY PLUMBING RISER: THE LAVATORY
 WASTE DOES NOT REFLECT THE FLOOR PLAN. THE LAVATORY
 TRAP IS BEING INDICATED IN THE WALL. PER FBC PLUMBING
 701.1 SCOPE. ALSO THE LAVATORY TRAP IS BEING INDICATED
 AS 2". LAVATORY TRAPS ARE USUALLY 1-1/2" OR 1-1/4"
 (REFERENCE FBC PLUMBING TABLE 709.1). PLEASE CLARIFY IF
 IT IS THE INTENT TO HAVE A 2" TRAP TO THE LAVATORY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By mperson Date 2007-11-09 Time 15:42 Rev Time 0.00
Received By mperson Date 2007-11-09 Time 15:42 Sent To PC
Notes
2007-11-09 15:54:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: ON SOME SHEETS THE ARCHITECT SEAL IS WEAK PER
 FAC-CODE-61G1-16001 ARCHITECT'S AND
 INTERIOR DESIGNER'S SEAL:
 EACH ARCHITECT AND INTERIOR DESIGNER
 SHALL ACQUIRE A SEAL WITH WHICH HE OR
 SHE SHALL IDENTIFY ALL PLANS,
 SPECIFICATIONS OR REPORTS PREPARED OR
 ISSUED BY HIM OR HER AND FILED FOR
 PUBLIC RECORD. THE SEAL SHALL BE OF A
 TYPE WHICH WILL MAKE AN IMPRESSION ON
 THE SURFACE OF PRINTS OR OTHER
 DUPLICATIONS OF DRAWINGS, AND AS
 APPROPRIATE, UPON SPECIFICATION PAGES,
 AND OTHER ARTICLES OF SERVICE.
  
 2. SHEET A-1 SANITARY RISER DIAGRAM: PER FBC-2004
 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE AND
 TWO-FAMILY) PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS.
 **NOTE: NOT ALL WASTE VENTS OR TRAPS ARE SIZED.
  
 3. SHEET A-1 SANITARY RISER DIAGRAM: THE CLEANOUT AT
 THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER
 SHALL BE A TWO-WAY CLEANOUT PER *708.3.5, DUILDING
 DRAIN AND BUILDING SEWER JUNCTION.
  
 4. SHEET A-1 SANITARY RISER DIAGRAM: A TRAP IS
 REQUIRED FOR THE SHOWER PER *1002.1 FIXTURE TRAPS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-07-17 Cont ID  
Sent By mcruz Date 2008-07-17 Time 12:00 Rev Time 0.00
Received By mcruz Date 2008-07-17 Time 12:00 Sent To E
Notes
2008-07-17 12:00:35**ZONING APPROVED, RESUB #3**
  
  
 SENT TO "E" ~MC

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By choops Date 2008-05-27 Time 10:00 Rev Time 0.00
Received By choops Date 2008-05-27 Time 10:00 Sent To E
Notes
2008-05-27 10:01:19***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-26 Cont ID  
Sent By choops Date 2008-02-26 Time 14:46 Rev Time 0.00
Received By choops Date 2008-02-26 Time 14:46 Sent To M
Notes
2008-02-26 14:47:18***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)SITE PLAN AND SURVEY DO NOT CORRESPOND WITH
 RESPECT TO THE REAR PROPERTY LINE.THE SURVEY SHOWS A
 SETBACK OF 5.2 FEET TO THE ACCESSORY STRUCTURE, WHILE
 THE SITE PLAN SHOWS THE REAR PROPERTY LINE RIGHT AT THE
 ACCESSORY STRUCTURE. CLARIFY.THE SITE PLAN'S SHOWN
 SETBACK DIMENSION FROM THE ADDITION TO THER REAR
 PROPERTY LINE DOES NOT SEEM ACCURATE GIVEN THE
 DIMENSIONS ON THE SURVEY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By choops Date 2007-10-25 Time 08:40 Rev Time 0.00
Received By choops Date 2007-10-25 Time 08:40 Sent To E
Notes
2007-10-25 08:47:15***FAILED***
  
  
 1)NORTH ARROWS DO NOT MATCH BETWEEN SITE PLAN AND
 SURVEY.CLARIFY.
  
 2)SITE PLAN AND SURVEY DO NOT CORRESPOND WITH
 RESPECT TO THE REAR PROPERTY LINE.CLARIFY.
  
 3)DOES NOT MEET MINIMUM REQUIRED SETBACK AS SET
 FORTH IN SECTION 94-72(A)(2) OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS: MINIMUM
 SETBACKS FOR PRINCIPAL BUILDING.
 A.FRONT: 25 FEET;
 B.CORNER: 12.5 FEET;
 C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE
 CITY'S DEPARTMENT OF PUBLIC UTILITIES (1ST FLOOR, CITY
 HALL) REGARDING THE PROPOSED SITE WALL.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720