Plan Review Details - Permit 07100650
Plan Review Stops For Permit 07100650
Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-01-21 Cont ID  
Sent By shill Date 2009-01-21 Time 14:05 Rev Time 0.00
Received By shill Date 2009-01-21 Time 14:05 Sent To  
Notes
2009-01-21 14:05:50REVISED SHEET A1, PRE STORM PREP PLAN, NEW NOAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2008-12-24 Cont ID  
Sent By shill Date 2008-12-24 Time 13:27 Rev Time 0.00
Received By shill Date 2008-12-24 Time 13:27 Sent To  
Notes
2008-12-24 14:51:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE SEE SHEET 1 OF THE PRODUCT APPROVAL, NOTE
 9(D). SITE SPECIFIC (USE OF FASTENERS OTHER THAN THOSE
 SPECIFIED IN THE PRODUCT APPROVAL) ARE TO BE PREPARED
 BY A FLORIDA LICENSED P.E.
  
 EITHER PROVIDE THE ANALYSIS AS REQUIRED OR REVISE THE
 INSTALLATION SCHEDULE TO SPECIFY A FASTNER INCLUDED IN
 THE PRODUCT APPROVAL.
  
 2. PLANS REFER TO NON IMPACT GLASS, NO PRODUCT APPROVAL
 SUBMITTED FOR NON IMPACT PRODUCTS FAC9B72. PLESAE
 SUBMIT PRODUCT APPROVALS, REVIEWED BY DESIGNER OF
 RECORD IF PRODUCT (DOOR) PROPOSED IS NOT THE SAME AS
 ORIGINALLY PERMITTED AND ISSUED.
  
 3. THE SHUTTER STORAGE DETAIL DOES NOT PROVIDE LOADING
 INFORMATION. THIS CAN BE A PROVISO ITEM, PRIOR TO C.C.
  
 4. THE PRESTORM PREPARATION PLAN SUBMITTED BY IAN PLATH
 HAS BEEN APPROVED BY THE BUILDING OFFICIAL. PRIOR TO
 C.C., THE SIGNED ORIGINAL MUST BE SUBMITTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2008-12-22 Cont ID  
Sent By shill Date 2008-12-22 Time 10:02 Rev Time 0.00
Received By shill Date 2008-12-22 Time 10:02 Sent To  
Notes
2008-12-22 10:03:18****CORRECTIONS****
 ****SHUTTER STORAGE (VERTICAL) DETAIL SUBMITTED VIA
 EMAIL****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE DETAIL DOES NOT PROVIDE BASIC INFORMATION SUCH
 AS THE WEIGHT OF THE SHUTTERS, STORAGE LOCATION, HOW
 THE INSTALLATION CONTRACTOR WILL GET ACCESS TO THE
 SHUTTERS AS THEY ARE PADLOCKED, ETC. THE DETAIL IS TO
 BE PREPARED BY A DESIGN PROFESSIONAL.
  
 2. A DETAIL WILL NOT BE NECESSARY UNTIL THE USE OF
 REMOVABLE SHUTTERS HAS BEEN APPROVED. PLEASE REVISE THE
 PRESTORM PREPARATION PLAN AS REQUESTED. FOR YOUR
 CONVENIENCE, THE COMMENTS ARE AS FOLLOWS:
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 4. TO CLARIFY, THE ENTRY DOOR HAS FIXED GLASS ABOVE.
 WILL THIS ALSO BE IMPACT? THIS OPENING DOES NOT SEEM TO
 APPEAR ON THE INSTALLATION SCHEDULE, BUT IS NOT NOTED
 ON THE REVISED SHEET A1. PLEASE PROVIDE A FLOOR PLAN
 WITH NUMBERS TO CORRELATE WITH THE INSTALLATION
 SCHEDULE SO THAT SCOPE IS CLEAR, FBC*106, FBC16. **THE
 PLAN DOES ***NOT*** NEED TO BE REVISED!!!!** IN THE
 INTEREST OF TIME, PLEASE PROVIDE THE INFORMATION WITH
 THE INSTALLATION SCHEDULE. PROVIDE A LOCATION PLAN
 WHICH SHOWS THE PROPOSED SHUTTER LOCATION AND THIS
 WINDOW CAN BE NOTED AS EITHER IMPACT OR BE INCLUDED ON
 THE INSTALLATION SCHEDULE.
  
 5. N/A.
  
 6. WHEN RESUBMITTING, PLEASE PROVIDE TWO COMPLETE SETS
 OF PERMIT DOCUMENTS. THE PRODUCT APPROVALS FOR THE
 IMPACT DOORS ARE NOT REQUIRED AS THEY ARE ALREADY
 STAMPED AND ON FILE. HOWEVER, ONLY ONE SET OF THE STORM
 PANEL PRODUCT APPROVAL WAS SUBMITTED. PLEASE PROVIDE
 TWO LEGIBLE SETS.
  
 7. THE PRESTORM PREPARATION PLAN STATES THAT THE PANELS
 WILL BE STORED IN A CLOSET IN THE TENANT BUILDOUT, BUT
 NO CLOSET IS SHOWN ON THE TENANT BUILDOUT PLAN. IT ALSO
 STATED THAT THE SHUTTERS WILL BE INSTALLED VERTICALLY;
 PLEASE PROVIDE A DETAIL OF HOW THE SHUTTERS WILL BE
 SECURED. ALSO, PLEASE STATE HOW THE SHUTTES WILL BE
 SECURED FROM THEFT. THIS INFORMATION CAN BE SUBMITTED
 VIA EMAIL. AS THE PRESTORM PREPARATION PLAN IS
 CURRENTLY IN REVIEW BY ROBERT BROWN, PLEASE SUBMIT THIS
 INFORMATION (STORAGE LOCATION, SECUREMENT FROM THEFT)
 AS SOON AS POSSIBLE SO THAT THE SUPPORTING INFORMATION
 CAN BE FORWARDED TO MR. BROWN PRIOR TO HIS REVIEW.
  
 8. (REVISED) USE OF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL.
 THE PLAN SUBMITTED IS PENDING REVIEW BY ROBERT BROWN.
 INCLUDE ALL INFORMATION REQUIRED IN ITEM 7. THE DETAIL
 OF HOW THE SHUTTERS WILL BE SECURED CAN BE A PROVISO
 ITEM. PLEASE EMAIL THE REVISED PLAN TO [email protected].
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2008-12-02 Cont ID  
Sent By shill Date 2008-12-02 Time 08:25 Rev Time 0.00
Received By shill Date 2008-12-02 Time 08:25 Sent To  
Notes
2008-12-02 10:42:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE LEGIBLE DOCUMENTS. THE PRODUCT
 APPROVAL FOR THE ALUMINUM STORM PANELS ARE DIFFICULT TO
 READ ON THE INTERNET, AND THE COPY PROVIDED IS A COPY
 OF A FAX, MAKING IT IMPOSSIBLE TO READ. PLEASE PRINT
 TWO COPIES FROM THE WEBSITE, WWW.FLORIDABUILDING.ORG.
 BE SURE TO CHANGE THE CODE VERSION TO 2004 ON THE
 WEBSITE (DEFAULT IS 2007).
  
 2. PLEASE SPECIFY DESIGN PRESSURES ON THE INSTALLATION
 SCHEDULE.
  
 3. THE SHUTTER CONNECTION MOUNTING TYPE AND THE
 SPECIFIC ANCHOR TYPE SHOULD CORRELATE WITH THE ANCHOR
 CHARTS ON THE PRODUCT APPROVAL; FOR INSTANCE, SEE PAGE
 6. PLEASE REVISE THE INSTALLATION SCHEDULE.
  
 4. TO CLARIFY, THE ENTRY DOOR HAS FIXED GLASS ABOVE.
 WILL THIS ALSO BE IMPACT? THIS OPENING DOES NOT SEEM TO
 APPEAR ON THE INSTALLATION SCHEDULE, BUT IS NOT NOTED
 ON THE REVISED SHEET A1. PLEASE PROVIDE A FLOOR PLAN
 WITH NUMBERS TO CORRELATE WITH THE INSTALLATION
 SCHEDULE SO THAT SCOPE IS CLEAR, FBC*106, FBC16. **THE
 PLAN DOES ***NOT*** NEED TO BE REVISED!!!!** IN THE
 INTEREST OF TIME, PLEASE PROVIDE THE INFORMATION WITH
 THE INSTALLATION SCHEDULE. PROVIDE A LOCATION PLAN
 WHICH SHOWS THE PROPOSED SHUTTER LOCATION AND THIS
 WINDOW CAN BE NOTED AS EITHER IMPACT OR BE INCLUDED ON
 THE INSTALLATION SCHEDULE.
  
 5. N/A.
  
 6. WHEN RESUBMITTING, PLEASE PROVIDE TWO COMPLETE SETS
 OF PERMIT DOCUMENTS. THE PRODUCT APPROVALS FOR THE
 IMPACT DOORS ARE NOT REQUIRED AS THEY ARE ALREADY
 STAMPED AND ON FILE. HOWEVER, ONLY ONE SET OF THE STORM
 PANEL PRODUCT APPROVAL WAS SUBMITTED. PLEASE PROVIDE
 TWO LEGIBLE SETS.
  
 7. THE PRESTORM PREPARATION PLAN STATES THAT THE PANELS
 WILL BE STORED IN A CLOSET IN THE TENANT BUILDOUT, BUT
 NO CLOSET IS SHOWN ON THE TENANT BUILDOUT PLAN. IT ALSO
 STATED THAT THE SHUTTERS WILL BE INSTALLED VERTICALLY;
 PLEASE PROVIDE A DETAIL OF HOW THE SHUTTERS WILL BE
 SECURED. ALSO, PLEASE STATE HOW THE SHUTTES WILL BE
 SECURED FROM THEFT. THIS INFORMATION CAN BE SUBMITTED
 VIA EMAIL. AS THE PRESTORM PREPARATION PLAN IS
 CURRENTLY IN REVIEW BY ROBERT BROWN, PLEASE SUBMIT THIS
 INFORMATION (STORAGE LOCATION, SECUREMENT FROM THEFT)
 AS SOON AS POSSIBLE SO THAT THE SUPPORTING INFORMATION
 CAN BE FORWARDED TO MR. BROWN PRIOR TO HIS REVIEW.
  
 8. USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS
 MUST BE APPROVED BY THE BUILDING OFFICIAL. THE PLAN
 SUBMITTED IS PENDING REVIEW BY ROBERT BROWN. HOWEVER,
 IT WOULD BE HELPFUL IF THE PLAN SUBMITTED COULD BE
 REVISED TO INCLUDE THE INFORMATION IN ITEM 7 SO THAT HE
 HAS COMPLETE INFORMATION UPON WHICH TO MAKE HIS
 DECISION. THE DETAIL OF HOW THE SHUTTERS WILL BE
 SECURED CAN BE A PROVISO ITEM. PLEASE EMAIL THE REVISED
 PLAN TO [email protected]. PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-10-22 Cont ID  
Sent By shill Date 2008-10-22 Time 13:56 Rev Time 0.00
Received By shill Date 2008-10-22 Time 13:56 Sent To  
Notes
2008-10-22 13:57:44****CORRECTIONS****
 ****REVISION, FROM IMPACT GLASS TO NON IMPACT GLAZING,
 STORM PANELS, AND PRE-STORM PREPARATION PLAN***
 ****SHUTTER PERMIT APPLIED UNDER 08090146, NOW
 INCORPORATED INTO BUILDING PERMIT PER LUIS MARTINEZ****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM FIRST REVIEW, SHUTTER PERMIT 08090146
  
 1. IMPACT RATED PRODUCT APPROVALS WERE SUBMITTED FOR
 THE BUILDING, 07100650. IF YOU PROPOSE TO USE NON RATED
 PRODUCTS, HAVE THE PROPOSED PRODUCTS REVIEWED BY THE
 ARCHITECT FBC*106.3.3 AND SUBMIT AS A REVISION TO
 07100650.
  
 A. SHEET A1, REVISE NOTE REGARDING USE OF STORM PANELS.
 THE FRONT DOOR, A REQUIRED EXIT, CANNOT BE OBSTRUCTED
 BY REMOVABLE PANELS FBC1003.6.
  
 B. THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD FBC*106.3.3. THIS CAN BE DONE BY EITHER A
 LETTER, SHOP DRAWING REVIEW STAMP, SPECIFYING THE
 PRODUCTS IN THE SIGNED AND SEALED PLAN, OR ANY OTHER
 METHOD WHICH SHOWS COMPLIANCE WITH FBC*106.3.3.
  
 C. NOA 06-0818.02, ARCH ALUMINUM NON-IMPACT OUTSWING
 DOOR WAS SUBMITTED. SEE OTHER COMMENTS REGARDING
 FBC1003.6, MEANS OF EGRESS CONTINUITY.
  
 D. NOA 06-0818.02, SEE SHEET 1 OF 9; THIS PRODUCT IS
 NOT TO BE USED WHERE WATER INFILTRATION IS NOT
 ACCEPTABLE. AS THE OVERHANG IS 2', THE ANGLE (BOTTOM OF
 DOOR TO EDGE OF OVERHANG) APPEARS TO BE LESS THAN THE
 45 DEGREES REQUIRED. PLEASE ADDRESS.
  
 E. NOA 05-0902.01, ARCH ALUMINUM SERIES 4500 STOREFRONT
 NON-IMPACT, APPEARS TO BE CODE COMPLIANT (DESIGN
 PRESSURES). PLEASE ADDRESS THE OTHER COMMENTS REGARDING
 REVIEW BY DESIGNER OF RECORD AND IMPACT PROTECTION.
  
 F. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS IS
 DELEGATED ENGINEERING; PLEASE HAVE REVIEWED BY DESIGNER
 OF RECORD FAC61G15-31.001.
  
 G. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS ,
 SHEET 1, STATES THAT THIS IS EXPOSURE C, BUT APPEARS TO
 USE EXPOSURE B PRESSURES. PLEASE CLARIFY OR REVISE
 FBC1609. THE ENGINEER OF RECORD FOR THE STRUCTURE HAS
 DECLARED EXPOSURE B.
  
 2. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL
 BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
 SUBMIT A PRESTORM PREPARATION PLAN, SEE ITEM 13,
 ATTACHED. THIS MAY BE SUBMITTED VIA EMAIL FOR
 PRELIMINARY APPROVAL. YOU ARE ENCOURAGED TO HAVE THE
 PRESTORM PREPATION PLAN APPROVED PRIOR TO RESUBMITTAL
 OF THE SHUTTER PERMIT.
  
 SEE EMAIL CORRESPONDENCE, 10/2/8 TO 10/8/8. THE
 PRE-STORM PREPARATION PLAN SUBMITTED IS THE SAME PLAN
 SUBMITTED AND DENIED IN THE EMAIL OF 10/2/8. CONTRACTOR
 WAS ADVISED: " PLEASE REVISE THE PLAN TO INCLUDE THE
 NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER
 INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN
 "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST,
 I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT
 THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE
 FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT
 INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION
 PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS." AS THE
 CONTRACTOR HAS SUBMITTED THE PRE-STORM PREPARATION PLAN
 WITHOUT THE REQUESTED REVISIONS, LUIS MARTINEZ (CHIEF
 PLANS EXAMINER) HAD THE PLAN REVIEWED BY ROBERT BROWN,
 INTERIM BUILDING OFFICIAL. HE CONFIRMED THE REQUIREMENT
 FOR THE REQUESTED INFORMATION IN ORDER TO DETERMINE
 WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED FOR
 THIS BUILDING.
  
 PLEASE REVISE THE PRE-STORM PREPARATION PLAN AS
 REQUESTED IN THE EMAIL OF 10/8/8. TO SUMMARIZE:
  
 A. THE PLAN IS TO BE SIGNED BY THE OWNER. ONLY THE
 CONTRACTOR AND DEVELOPER ARE INCLUDED IN THE PRE-STORM
 PREPARATION PLAN SIGNATURE LINES. THIS IS AN AGREEMENT
 MADE BY THE OWNER OF THE BUILDING REGARDLESS OF TENANT
 RESPONSIBILITIES. IN THE INTEREST OF PUBLIC SAFETY, THE
 OWNER MUST DEMONSTRATE THAT HE OR SHE HAS THE ABILITY
 TO ENSURE THAT THE STORM PANELS ARE INSTALLED IN THE
 TIME FRAME REQUIRED.
  
 B. PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND
 CONSTRUCTION SUCH AS WHERE THEY ARE LOCATED, NUMBER OF
 EMPLOYEES, NUMBER OF JOBS THEY ARE RESPONSIBLE FOR.
 NOTE THAT THIS COMPANY IS LOCATED OUTSIDE OF PALM BEACH
 COUNTY. THE IMPLEMENTATION STANDARD REQUIRES THAT THE
 PARTY RESPONSIBLE FOR SHUTTER INSTALLATION IS TO BE
 LOCATED IN PALM BEACH COUNTY. PROVIDE THE INFORMATION
 REQUESTED AND ADDRESS THE LOCATION ISSUE.
  
 C. THE PLAN STATES THAT THE DOOR WILL BE PROTECTED (BY
 STORM PANELS); THE EGRESS PATH CANNOT BE OBSTRUCTED BY
 ELEMENTS OTHER THAN THOSE PERMITTED IN FBC CHAPTER 10.
 PLEASE REVISE TO BE IN COMPLIANCE WITH FBC CHAPTER 10.
  
 D. THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN
 THE NORTH WEST CORNER OF THE BUILDING SLAB. THE FLOOR
 PLAN SHOWS THAT THE AREA OF SHUTTER STORAGE IS THE
 LOCATION OF THE FUTURE ACCESSIBLE BATHROOMS. HOW WILL
 THEY BE SECURED TO PREVENT THEFT? WILL THE PANELS BE
 STORED HORIZONTALLY OR VERTICALLY? IT IS NOT CLEAR WHAT
 WILL HAPPEN TO THE SHUTTERS WHEN THE BATHROOM IS
 INSTALLED; THIS APPEARS TO BE A TEMPORARY STORAGE
 SOLUTION. HOW THESE SHUTTERS WILL BE SECURED,
 ESPECIALLY DURING THE TENANT BUILDOUT, WAS NOT
 ADDRESSED.
  
 3. PROVIDE A FLOOR PLAN SHOWING PROPOSED SHUTTER
 LOCATIONS. (COMMENT FROM PREVIOUS REVIEW.)
  
 THIS ITEM WAS ADDRESSED, BUT THE FRONT DOOR CANNOT BE
 BLOCKED BY STORM PANELS FBC1003.6. REVISE.
  
 4. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106. TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 A. THE INSTALLATION SCHEDULE WAS NOT COMPLETE. IT WAS
 SUBMITTED, BUT COLUMNS 3, 4, 5, 6, 8, 10, 12 ARE BLANK.
  
 B. THE PRODUCT APPROVAL IS DIFFICULT TO READ. IT
 APPEARS TO BE A PHOTOCOPY OF A FAX. PLEASE PROVIDE
 LEGIBLE COPIES; TWO SETS PRINTED DIRECTLY FROM THE
 WEBSITE WWW.FLORIDABUILDING.ORG MAY BE LEGIBLE.
  
 C. THE ANCHOR TYPE IS TO CORRELATE WITH THE ANCHORS ON
 THE PRODUCT APPROVAL, SEE SHEET 6 OF 9. I DID NOT SEE A
 "DROP IN ANCHOR SIDEWALK BOLT" AS A CHOICE, BUT IT'S
 POSSIBLE THAT IT IS THERE, BUT I CAN'T READ IT. BEFORE
 RESUBMITTING, PLEASE BE SURE THAT THE ANCHOR TYPE IS
 CLEARLY SPECIFIED AND CORRELATES WITH INFORMATION IN
 THE PRODUCT APPROVAL.
  
 D. A COMPLETE LIST CANNOT BE DONE AT THIS TIME DUE TO
 INSUFFICIENT INFORMATION.
  
 5. MEANS OF EGRESS CANNOT BE BLOCKED BY A HURRICANE
 STORM PANEL, FBC1003.6, MEANS OF EGRESS CONTINUITY.
  
 THIS ITEM WAS NOT ADDRESSED.
  
 6. THE BUILDING PERMIT WAS FOR A SHELL BUILDING.
 REMOVABLE PANELS, IF APPROVED, ARE TO BE STORED ON
 SITE. IN THE PRE STORM PREPARATION PLAN, INCLUDE
 INFORMATION REGARDING STORAGE OF SHUTTERS.
  
 SEE OTHER COMMENTS. THIS ITEM WAS NOT ADDRESSED;
 INFORMATION REQUESTED WAS NOT PROVIDED. PLEASE REVISE
 THE PLAN TO INCLUDE ALL REQUESTED INFORMATION. WHEN THE
 PLAN IS COMPLETE AND HAS ALL INFORMATION REQUIRED, IT
 WILL THEN BE FORWARDED TO THE BUILDING OFFICIAL FOR
 REVIEW.
  
 ***THE PRE-STORM PREPARATION PLAN (ONLY) CAN BE
 SUBMITTED BY EMAIL FOR PRELIMINARY REVIEW***
  
 A C.O. HOLD HAS BEEN PLACED ON THIS PERMIT PENDING
 RESOLUTION OF THIS ISSUE.
  
 AS DISCUSSED, THIS CAN BE SUBMITTED PRIOR TO
 RESUBMITTAL OF THE REVISION/PLANS. THE CONTRACTOR IS
 ENCOURAGED TO GET THIS APPROVED BEFORE RESUBMITTAL TO
 AVOID ADDITIONAL DELAYS. IN THIS CASE, THE CONTRACTOR
 WAS ADVISED OF MANY OF THESE REQUIREMENTS VIA EMAIL BUT
 ELECTED TO DISREGARD THEM. THE NEED FOR ALL INFORMATION
 REQUESTED HAS BEEN CONFIRMED BY THE BUILDING OFFICIAL.
 AS DISCUSSED, TO AVOID FURTHER DELAYS, THE CONTRACTOR
 IS ENCOURAGED TO SUBMIT THE PRE-STORM PREPARATION PLAN
 BY EMAIL AND TO GET THIS ISSUE RESOLVED PRIOR TO
 RESUBMITTAL OF THE REVISION. PLEASE NOTE THAT MY REVIEW
 IS PRELIMINARY; THE BUILDING OFFICIAL MIGHT REQUIRE
 ADDITIONAL INFORMATION.
  
  
  
 ****END OF PLAN REVIEW COMMENTS*****
  
 *******************************************************
 **
 *******************************************************
 **
 *******************************************************
 **
  
 ****FOR REFERENCE ONLY, EMAILS BETWEEN SAMANTHA HILL
 (BUILDING PLANS EXAMINER) AND ADAM SPIEWAK (CONTRACTOR)
  
 EMAIL CORRESPONDENCE, PRE-STORM PREPARATION PLAN:
  
  
 EMAIL #3 OF 3
 (EMAIL SENT ON 10/8/8)
  
 THE PRESTORM PREPARATION PLAN SHOULD BE REVISED TO
 INCLUDE THE REQUESTED INFORMATION. THE INFORMATION
 SHOULD BE CONSOLIDATED INTO ONE DOCUMENT, WHICH IS AN
 AGREEMENT SIGNED BY THE OWNER. THE CONTRACT WITH THE
 ENTITY WHO WILL BE RESPONSIBLE FOR INSTALLATION OF THE
 SHUTTERS SHOULD BE AN ATTACHMENT TO THE PRESTORM
 PREPARATION PLAN. THE REQUESTED INFORMATION REGARDING
 THE COMPANY COULD BE INCLUDED IN EITHER THE PLAN OR THE
 CONTRACT, BUT THIS INFORMATION IS REQUIRED AS THE
 POLICY, ITEM 13, STATES PARAMETERS FOR THE INDIVIDUALS
 DOING THE INSTALLATION.
  
 CHAPTER 10 DOES NOT PERMIT USE OF REMOVABLE STORM
 PANELS TO PROVIDE IMPACT PROTECTION FOR A REQUIRED EXIT
 DOOR. THERE IS A PROVISION FOR EMERGENCY IMPACT
 PROTECTION FOR RESIDENTIAL OCCUPANIES WITH PROVISIONS
 FOR ALTERNATE MEANS OF EGRESS, BUT NOT FOR OTHER
 OCCUPANCIES. YOU CANNOT BLOCK THE MAIN EXIT IN A
 COMMERCIAL BUILDING WITH STORM PANELS, FBC1003.6.
  
 THE PRESTORM PREPARATION PLAN SHOULD INCLUDE THE
 SIGNATURE LINE OF THE INDIVIDUALS WHO ARE GOING TO SIGN
 THE PLAN. IT DID NOT APPEARS THAT THE OWNER WAS ONE OF
 THE INDIVIDUALS. PLEASE REVISE THE PLAN TO INCLUDE THE
 NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER
 INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN
 "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST,
 I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT
 THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE
 FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT
 INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION
 PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS. I DO A
 PRELIMINARY REVIEW OF THE PLAN FOR COMPLETENESS OF
 INFORMATION; THE BUILDING OFFICIAL MAKES THE DECISION
 AS TO WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED
 ON A CASE BY CASE BASIS. PLEASE KEEP IN MIND THAT THIS
 PERMIT WAS ISSUED WITH IMPACT GLAZING. ANY CHANGE OF
 PRODUCTS SHOULD HAVE BEEN SUBMITTED AS A REVISION PRIOR
 TO INSTALLATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
 * * * * * * * * * * * * * * * * * * * * * * * * * * * *
  
 EMAIL #2 OF 3
  
 "ADAM SPIEWAK"
 10/07/2008 03:57 PM
 TO
 
 CC
 "'GARY WILLIAMS'" , "'RANDY
 DEGLER'"
 SUBJECT
 RE: BAYWINDS RETAIL - PRE-STORM PREPARATION PLAN
  
  
  
  
  
 MRS. HILL,
  
 PLEASE KEEP IN MIND THAT FOR ALL INTENSIVE PURPOSES,
 THIS BUILDING WILL
 REMAIN UNOCCUPIED. THE SHUTTER PERMIT IS ATTACHED TO
 THE MASTER PERMIT
 07100650, WHICH IS A PERMIT FOR THE SHELL CONSTRUCTION
 ONLY. THE INTERIOR
 PERMIT APPLICATION IS CURRENTLY BEING REVIEWED BY THE
 BUILDING DEPARTMENT.
 THE PRE-STORM PREPARATION PLAN THAT HAS BEEN SUBMITTED
 FOR YOUR REVIEW IS
 ONLY TEMPORARY UNTIL SUCH TIME AS THE INTERIOR
 CONSTRUCTION IS COMPLETE
 AND THE TENANT TAKES RESIDENCY. AT WHICH TIME, A NEW
 PERMANENT PRE-STORM
 PREPARATION PLAN SHALL BE DEVISED AND SUBMITTED FOR
 APPROVAL. IN ORDER TO
 OBTAIN A CERTIFICATE OF COMPLETION FOR THE SHELL PERMIT
 ONLY, THE SHUTTER
 PERMIT WILL NEED TO BE APPROVED, INSPECTED AND CLOSED,
 BEFORE A BUILDING
 FINAL INSPECTION CAN TAKE PLACE.
  
 WITH THAT IN MIND, PLEASE FIND THE ANSWERS TO YOUR
 INQUIRES LISTED BELOW:
  
 1) J. RAYMOND CONSTRUCTION IS A COMMERCIAL GENERAL
 CONTRACTOR WITH A MAIN
 OFFICE LOCATED IN LONGWOOD FLORIDA. WE ARE RESPONSIBLE
 FOR THE
 CONSTRUCTION OF MANY PROJECTS LOCATED IN VARIOUS
 MUNICIPALITIES THROUGHOUT
 THE STATE. WE DO HOWEVER, HAVE A STRONG PRESENCE IN THE
 TRI-COUNTY AREA,
 AS WELL AS MANY EMPLOYEES WHO LIVE HERE.
  
 2) THE FRONT DOOR SHALL BE PROTECTED AS REQUIRED BY
 CHAPTER 10 IN THE FBC.
 THE EMERGENCY MEANS OF EGRESS THROUGH THE REAR STEEL
 EXIT DOORS (EQUIPPED
 WITH A PANIC DEVICE) WILL NOT BE OBSTRUCTED.
  
 3) THE PANELS WILL BE STORED HORIZONTALLY ON THE EMPTY
 SHELL SLAB IN THE
 NW CORNER OF THE BUILDING. A FLOOR PLAN WITH THIS
 INFORMATION WILL BE
 ATTACHED TO THE FINAL SUBMISSION PACKAGE. THE PANELS
 WILL BE PROTECTED
 FROM THEFT BY KEEPING ALL DOORS LOCKED DURING NON
 CONSTRUCTION HOURS. AT
 WHICH TIME THE INTERIOR CONSTRUCTION IS COMPLETE, THE
 PANELS WILL BE MOVED
 TO A MORE SECURE STORAGE CLOSET.
  
 4) AT THE TIME OF THE OFFICIAL SUBMITTAL OF THE
 PRE-STORM PREPARATION
 PLAN, ALL REQUIRED SIGNATURES WILL BE OBTAINED.
  
  
 - SHOULD YOU HAVE ANY QUESTION, PLEASE DO NOT HESITATE
 TO CONTACT ME.
  
 THANK YOU,
  
 ADAM SPIEWAK
 ASSISTANT SUPERINTENDANT
 P: (954) 464-6112 - F: (407) 712-6859
 J. RAYMOND
 CONSTRUCTION
 WWW.JRAY.COM
  
  
 EMAIL #1 OF 3
  
 -----ORIGINAL MESSAGE-----
 FROM: [email protected] [MAILTO:[email protected]]
 SENT: TUESDAY, OCTOBER 07, 2008 10:51 AM
 TO: ADAM SPIEWAK
 SUBJECT: RE: BAYWINDS RETAIL - PRE-STORM PREPARATION
 PLAN
  
 PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND
 CONSTRUCTION SUCH AS
 WHERE THEY ARE LOCATED, NUMBER OF EMPLOYEES, NUMBER OF
 JOBS THEY ARE
 RESPONSIBLE FOR.
  
 THE PLAN STATES THAT THE DOOR WILL BE PROTECTED; THE
 EGRESS PATH CANNOT BE
 OBSTRUCTED BY ELEMENTS OTHER THAN THOSE PERMITTED IN
 FBC CHAPTER 10.
  
 THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN
 THE NORTH WEST CORNER
 OF THE BUILDING SLAB. IT IS NOT CLEAR WHAT THAT MEANS.
 HOW WILL THEY BE
 SECURED TO PREVENT THEFT? WILL THE PANELS BE STORED
 HORIZONTALLY OR
 VERTICALLY?
  
 THE PLAN IS TO BE SIGNED BY THE OWNER. THE OWNER ON
 RECORD IS UG
 OKEECHOBEE LP.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 561-805-6724
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
  
  
  
  
  
  
  
 "ADAM SPIEWAK"
  
 
  
 M> TO
  
 
  
 10/02/2008 09:32 CC
  
 AM "'GARY WILLIAMS'"
  
 
  
 SUBJECT
  
 BAYWINDS RETAIL - PRE-STORM
  
 PREPARATION PLAN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 MRS. HILL,
  
 PLEASE SEE THE ATTACHED PRE-STORM PREPARATION PLAN
 SUBMITTED FOR YOUR
 REVIEW.
  
 THANK YOU FOR YOUR TIME AND ATTENTION THROUGHOUT THIS
 PROCESS.
  
  
 ADAM SPIEWAK
  
  
 P: (954) 464-6112
  
  
 F: (407) 712-6859
  
  
  
  
 J. RAYMOND
  
 CONSTRUCTION
  
 WWW.JRAY.COM
  
  
  
  
  
 (SEE ATTACHED FILE: PRE-STORM PREPARATION PLAN -
 2008-10-02.PDF)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-10-17 Cont ID  
Sent By shill Date 2008-10-17 Time 14:28 Rev Time 0.00
Received By shill Date 2008-10-17 Time 14:28 Sent To E
Notes
2008-10-17 14:28:34REVISED ENERGY CALCS W/ROOF INSULATION INFORMATION
 CO HOLD REMOVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-10-15 Cont ID  
Sent By shill Date 2008-10-15 Time 10:22 Rev Time 0.00
Received By shill Date 2008-10-15 Time 10:22 Sent To  
Notes
2008-10-15 10:41:08****CORRECTIONS****
 ****ENERGY CALCS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE ENGINEER SUBMITTED A LETTER STATING THAT THREE
 INCHES OF INSULATION WAS INSTALLED, AND R20 PROVIDED.
 PLEASE PROVIDE SPECS FOR THE INSULATION AS MOST
 INSULATION RANGES FROM 2.5 TO 6 R VALUE PER INCH.
 COMPLIANCE IS NOT CLEAR, FBC13-404.1.
  
 THE SPEC SHEETS FOR THE ROOF SHOWING COMPLIANCE WITH
 R19 REQUIREMENTS CAN BE SUBMITTED VIA EMAIL. THIS WILL
 BE HELD AT MY DESK PENDING RECEIPT FOR THREE BUSINESS
 DAYS. PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-09-02 Cont ID  
Sent By shill Date 2008-09-02 Time 09:23 Rev Time 0.00
Received By shill Date 2008-09-02 Time 09:23 Sent To E
Notes
2008-09-02 09:28:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. SEE FBC 13-101.1.6, SHELL BUILDINGS TO USE METHOD B
 OR METHOD C WITH A LIST OF ALL ASSUMPTIONS ATTACHED.
  
 2. THE DESIGN PROFESSIONAL REESPONSIBLE FOR THE DESIGN
 OF LIGHTING, ELECTRICAL, AND THE BUILDING SHELL ARE TO
 CERTIFY THE BUILDING. THESE LINES WERE LEFT BLANK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-07-29 Cont ID  
Sent By shill Date 2008-07-29 Time 11:17 Rev Time 0.00
Received By shill Date 2008-07-29 Time 11:17 Sent To  
Notes
2008-07-29 11:21:02REVISION, NEW ROOF PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-07-29 Cont ID  
Sent By shill Date 2008-07-29 Time 11:12 Rev Time 0.00
Received By shill Date 2008-07-29 Time 11:12 Sent To  
Notes
2008-07-29 11:17:10****CORRECTIONS****
 ***REVISION***
 NEW ROOF PRODUCT APPROVALS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE THE ENERGY CALCS WHICH WERE SUBMITTED WITH THE
 BUILDING.THE ENERGY CALCS SPECIFIED A SHINGLE ROOF,
 1/2" WOOD DECK, WOOD TRUSSES, 9" BATT INSULATION,
 GYPSUM BOARD.THIS IS NOT CONSISTENT WITH THE PRODUCT
 APPROVALS SUBMITTED.
  
 2.ENERGY CALCS INPUT DATA REPORT SPECIFIES CONCRETE
 SLAB WITH CARPET AND RUBBER PAD.IS THIS CONSISTENT
 WITH THE SPECIFICATIONS ON THE PLAN?PLEASE CONFIRM
 THIS AND ALL OTHER ITEMS ON THE INPUT DATA REPORT.
  
 3.THE NEW REVISED ENERGY CALCS ARE TO BE CERTIFIED BY
 ALL DESIGN PROFESSIONALS INCLUDING THE ARCHITECT,
 FBC13-103.1.1.1.PLEASE INFORM ARCHITECT OF HIS
 RESPONSIBILITY TO CONFIRM THAT ALL ITEMS ON THE INPUT
 DATA REPORT ARE CONSISTENT WITH HIS DESIGN AND THE
 PLANS SUBMITTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 16:37 Rev Time 0.00
Received By shill Date 2008-05-08 Time 16:37 Sent To  
Notes
2008-05-08 16:37:29PROVISO - SEPARATE ROOF PERMIT REQUIRED
  
 ROOF TILE REVIEWED BY DOR NOA EXPIRED, MONIER SPANISH
 S, 02-1205.07, NEED METHOD OF FASTENING
 JOHNS MANVILLE 06-0626.09, NEED APPROVED ASSEMBLY AND
 ENGINEERING FOR ENHANCED FASTENING
  
 PERMIT ISSUED IS "AT RISK" (SHELL ONLY)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 11:03 Rev Time 0.00
Received By shill Date 2008-05-02 Time 16:26 Sent To  
Notes
2008-05-05 11:42:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PROVIDE THE IMPACT FEE RECEIPT FROM PALM BEACH
 COUNTY.
  
 2.THE PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 PROVISO - SEPARATE ROOF PERMIT REQUIRED
  
 ROOF TILE REVIEWED BY DOR NOA EXPIRED, MONIER SPANISH
 S, 02-1205.07, NEED METHOD OF FASTENING
 JOHNS MANVILLE 06-0626.09, NEED APPROVED ASSEMBLY AND
 ENGINEERING FOR ENHANCED FASTENING
  
 PERMIT ISSUED IS "AT RISK" (SHELL ONLY)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-14 Cont ID  
Sent By shill Date 2008-04-14 Time 11:28 Rev Time 0.00
Received By shill Date 2008-04-14 Time 11:28 Sent To  
Notes
2008-04-14 11:29:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY).
 INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.
  
 2-5). ADDRESSED.
  
 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL
 ONLY (SIGNS, ETC.).
  
 7.-8.)ADDRESSED.
  
 9.)SEE C7, TYPICAL PARKING DETAIL.THE DETAIL STATES
 THAT THE SURFACE WILL COMPLY WITH FIGURE 40(A) AND (B),
 BUT SEE OTHER COMMENTS REGARDING TACTILE SURFACE.
 GROOVES ARE NOT PERMITTED OUTDOORS, AND ADA TITLE III
 REQUIRES TRUNCATED DOMES, ADA 4.1.3.
  
 10-11.)ADDRESSED.
  
 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN
 ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE
 MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR
 TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND
 LOADING AREA AT NORTH SIDE).
  
 2ND REVIEW - NOT ADDRESSED.IT IS NOT CLEAR WHERE
 ACCESS TO THE PUBLIC SIDEWALK IS LOCATED, IF ANY.NONE
 SHOWN ON SHEET 1 PREPARED BY LAND DESIGN SOUTH, BUT
 THIS IS NOT SHOWN FOR THE ACCESSIBLE PARKING ACCESS
 AISLE EITHER.THE REQUIREMENT FOR THE ACCESS AISLE TO
 SIDEWALK CHANGE IN ELEVATION REQUIREMENT IS COMMON
 KNOWLEDGE, BUT THE REQUIREMENT OF ACCESSIBILITY TO THE
 PUBLIC WAY MAY NOT BE.PLEASE SHOW ON THE PLANS AS
 REQUESTED.SHEET A1 IS NOT CLEAR; WHAT ARE THE DASHED
 LINES?I CANNOT DETERMINE WHETHER OR NOT THE CONCRETE
 IS CONTINUOUS, OR IF THE DASHED LINES REPRESENT A CURB
 WITH A CHANGE IN ELEVATION EXCEEDING THAT PERMITTED BY
 FBC11-3.
  
 3RD REVIEW, LAND DESIGN SOUTH SHEETS HAVE BEEN REMOVED
 AND THE COMMENT IS STILL NOT ADDRESSED.SEE THE REAR
 EXIT DOOR.THERE SHOULD BE A CURB RAMP SO THAT
 DISABLED INDIVIDUALS CAN GET AWAY FROM THE BUILDING.
 SEE SHEET C4, NONE SHOWN.THERE SHOULD BE AN
 ACCESSIBLE ROUTE TO THE PUBLIC WAY, BUT THIS APPEARS TO
 BE FULLY LANDSCAPED WITH CURBS, SEE THE SOUTH PROPERTY
 LINE.
  
 IT IS NOT CLEAR WHICH DESIGNER, IF ANY, IS RESPONSIBLE
 FOR THE ACCESSIBILITY TO THE SITE.THE ARCHITECT?S
 RESPONSE LETTER STATES THAT THE LANDSCAPE ARCHITECT
 WILL SHOW THIS ON THEIR PLAN.IS THE NEW LANDSCAPE
 ARCHITECT, DAVE BODKER, AWARE THAT HIS PLAN IS BEING
 USED TO SHOW CODE COMPLIANCE FOR FLORIDA AND FEDERAL
 ACCESSIBILITY REQUIREMENTS?IT APPEARS THAT HIS PLAN
 IS FOR TREES AND SHRUBS, NOTHING RELATED TO
 ACCESSIBILITY WAS SHOWN.THE CIVIL ENGINEER?S TITLE
 BLOCK STATES THAT THEY ALSO DO LANDSCAPE ARCHITECTURE;
 IS THIS THE LANDSCAPE ARCHITECT PLAN THE ARCHITECT IS
 REFERRING TO?
  
 13.)ADDRESSED.
  
 14.) PROVIDE A SITE PLAN SHOWING DISTANCE BETWEEN THE
 BUILDINGS AND LOCATION OF THIS BUILDING ON THE LOT. THE
 SITE PLAN PREVIOUSLY IN THE PACKAGE HAS BEEN REMOVED,
 NEW SITE PLAN DOES NOT HAVE ALL OF THE REQUIRED
 DIMENSIONS.
  
 15-16.) ADDRESSED.
  
 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY.
  
 2ND REVIEW; YOU ARE REQUESTING A ROOF PERMIT.THIS
 INFORMATION IS REQUIRED SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.THE RESPONSE LETTER STATES "SEE ATTACHED
 PRODUCT APPROVAL INFORMATION SHEETS."NOTHING WAS
 PROVIDED AND THE APPROVED ASSEMBLY (CHOICES LOCATED
 BETWEEN SHEETS 7 THROUGH 18 OF THE NOA) WAS NOT
 SELECTED.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR
 CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY
 AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 AS PER GENERAL LIMITATION 7 ON THE NOA.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 19.)ADDRESSED.
  
 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF
 ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE
 PROVIDE PRODUCT APPROVALS, FAC9B72.
  
 2ND REVIEW - THIS INFORMATION IS REQUIRED AT THIS TIME
 AS YOUR ROOFER HAS SIGNED ON AND A ROOF PERMIT HAS BEEN
 ASSIGNED.IF YOU WOULD LIKE, PLEASE REMOVE THIS,
 CANCEL THE PERMIT THROUGH THE FRONT COUNTER WHEN
 RESUBMITTING, AND THE ROOFING CONTRACTOR CAN APPLY FOR
 A SUBCONTRACTOR PERMIT WITH ALL OF THE REQUIRED
 INFORMATION.PRODUCT APPROVALS ARE TO REMAIN IN THE
 PACKAGE.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 21-23.)ADDRESSED.
  
 24.)THE ADDRESS FOR THE ENGINEER, RICHARD ADAMS PE,
 CONFLICTS WITH DBPR WEBSITE.
 PLEASE CORRELATE.
  
 3RD REVIEW, NOT ADDRESSED.PLEASE ADVISE AS TO HOW
 THIS WILL BE RESOLVED.
  
 25.)PLEASE KEEP THE IMPACT FEE STAMP AND RECEIPT IN
 THE PERMIT PACKAGE.
  
 WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 INDICATING HOW ALL COMMENTS HAVE BEEN ADDRESSED.ONLY
 EIGHT OUT OF 22 COMMENTS WERE INCLUDED IN THE RESPONSE
 LETTER.OTHER COMMENTS CAN BE ADDRESSED WITH A LETTER
 FROM THE CONTRACTOR OR OTHER PARTY FAMILIAR WITH THE
 PROJECT IF THE ARCHITECT IS NOT RESPONSIBLE FOR THE
 OTHER ITEMS.NOTE THAT SEVERAL ITEMS WERE NOT
 ADDRESSED.PLEASE ADDRESS ALL COMMENTS.
  
 NEW COMMENTS:
  
 NOTE THAT NEW PLANS WERE SUBMITTED, CIVIL SHEETS, IN
 PLACE OF LAND DESIGN SOUTH.
  
 26. REGARDING THE DETECTABLE WARNINGS ON THE PLAN
 FBC11-4.29, SEE ADA 4.29.2* DETECTABLE WARNINGS ON
 WALKING SURFACES. DETECTABLE WARNINGS SHALL CONSIST OF
 RAISED TRUNCATED DOMES WITH A DIAMETER OF NOMINAL 0.9
 IN (23 MM), A HEIGHT OF NOMINAL 0.2 IN (5 MM) AND A
 CENTER-TO-CENTER SPACING OF NOMINAL 2.35 IN (60 MM) AND
 SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER
 LIGHT-ON-DARK, OR DARK-ON-LIGHT.
  
 A. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C8.
 HTTP://WWW.ACCESS-BOARD.GOV/ADAAG/DWS/UPDATE.HTM.
 TACTILE SURFACE SHOWN, PLEASE REVISE DETAIL TO SHOW
 TRUNCATED DOMES.
  
 B. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C8,
 TO SHOW THE VISUAL CONTRAST REQUIRED.IF THE DESIGN
 INTENT AND COMPLIANCE ARE NOT CLEAR, CALCULATIONS PER
 ADA4.29.2 MAY BE REQUIRED.
  
 C. NOTE THAT THE DETAIL STATES THAT IT IS TO CONFORM TO
 FDOT STANDARD 304, BUT THE DETAIL ON THE PLAN IS
 OUTDATED.PLEASE SEE THE CURRENT DETAIL,
 HTTP://WWW.DOT.STATE.FL.US/RDDESIGN/PUBLICATIONS/PUB.HT
 M.NOTE THAT THE CURRENT STANDARD ALSO REQUIRES
 TRUNCATED DOMES.PER RASIK CHOKSHI, CITY OF WEST PALM
 BEACH ENGINEERING SERVICES, PLEASE CHECK ALL DETAILS AT
 IT APPEARS THAT OTHER DETAILS ARE OUTDATED (DATED 2004
 AND 2006).
  
 D. C4, SIDEWALK FROM THE FRONT DOOR GOING SOUTH, THERE
 SHOULD BE A DETECTABLE WARNING ON THE WEST SIDE WHERE
 THE SIDEWALK CROSSES THE PARKING LOT.A DETECTABLE
 WARNING IS SHOWN ON THE EAST SIDE OF THIS CROSSING BUT
 NOT THE WEST SIDE.
  
 E. C4, A DETECTABLE WARNING IS SHOWN ON THE SIDEWALK AT
 THE ACCESSIBLE PARKING ACCESS AISLE AND NO CURB RAMP
 SHOWN (THERE IS A NOTE STATING THAT IT WILL NOSE DOWN).
 PLEASE REVISE.NOTE THAT DETECTABLE WARNING AT A
 SIDEWALK WHERE IT DOES NOT CROSS TRAFFIC IS CONFUSING.
 THIS SHOULD BE A PART OF THE CURB RAMP ONLY.
  
 F. PLEASE NOTE THAT DETECTABLE WARNINGS WERE PREVIOUSLY
 ENFORCED IN THE FIELD.TO AVOID INSPECTION ISSUES, ALL
 REQUIRED DETECTABLE WARNINGS FOR THE SITE AND FOR THE
 ACCESSIBLE ROUTE ARE TO BE SHOWN ON THE PLAN AT THE
 TIME OF ISSUANCE.
  
 27.)PLEASE HAVE THE ARCHITECT CERTIFY THE ENERGY
 CALCS, FBC13-103.1.1.1.
  
 28.)REGARDING EXITING ISSUES, PLEASE SEE FBC1023.6 AS
 WELL AS THE DEFINITIONS FOR EXIT DISCHARGE AND PUBLIC
 WAY.PLANS DO NOT CURRENTLY SHOW CODE COMPLIANCE, SEE
 OTHER COMMENTS.IS THERE A PERMANENT DEEDED ACCESS FOR
 THE SIDEWALK GOING TO THE WEST AND EVENTUALLY TO THE
 PUBLIC WAY?WHERE IS THE PUBLIC WAY IN RELATION TO THE
 LOTS?AS DISCUSSED, A COMPLETE SITE PLAN WILL BE
 SUBMITTED FOR PRELIMINARY BUILDING REVIEW PRIOR TO
 RESUBMITTAL OF THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-06 Cont ID  
Sent By shill Date 2008-02-06 Time 10:11 Rev Time 0.00
Received By shill Date 2008-02-06 Time 10:11 Sent To  
Notes
2008-02-06 10:18:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED:
  
 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY).
 INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.
  
 2.)DOCUMENTS PREPARED BY A LANDSCAPE ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.PLANS STATE THAT THIS IS
 "INFORMATIONAL ONLY" AND "PAD ONLY" BUT THIS SHEET IS
 USED TO DETERMINE CODE COMPLIANCE FOR ACCESSIBLE
 PARKING AND FBC CHAPTER 5; SEE OTHER COMMENTS.
  
 3.)STATE THE TOTAL NUMBER OF ACCESSIBLE PARKING AND
 TOTAL NUMBER OF PARKING SPACES FOR THIS PARCEL.NOTE
 THAT THE SITE PLAN STATES THAT THEREARE 176 TOTAL, 6
 ACCESSIBLE WOULD BE REQUIRED BUT ONLY FIVE SHOWN, BUT
 IT APPEARS THAT THIS TOTAL IS FOR FOUR PARCELS.PLEASE
 SHOW COMPLIANCE WITH FBC11-4.1.2(5)(A).
  
 2ND REVEW - THE SPECIFIC INFORMATION FOR PARKING IS
 SHOWN ON SHEET 1 PREPARED BYLAND DESIGN SOUTH.THE
 INFORMATION PROVIDED FOR PARCEL 4 IS CODE COMPLIANT.
 HOWEVER, SEE COMMENT 2 ABOVE.IF THIS UNSEALED SHEET
 IS REMOVED, SOMETHING MUST BE INCLUDED IN THE PERMIT
 PACKAGE TO SHOW CODE COMPLIANCE WITH ACCESSIBILITY
 REQUIREMENTS.
  
 4.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY.
  
 2ND REVIEW - IF REQUIRED FOR CODE COMPLIANCE, THE
 SURVEY IS TO BE A SIGNED, SEALED, DATED ORIGNAL.NO
 SURVEY WAS SUBMITTED.TWO SETS REQUIRED.
  
 5.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.
  
 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL
 ONLY (SIGNS, ETC.).
  
 7.-8.)ADDRESSED.
  
 9.)SEE ZONING COMMENTS REGARDING PARKING STRIPING
 DETAIL.
  
 10-11.)ADDRESSED.
  
 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN
 ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE
 MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR
 TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND
 LOADING AREA AT NORTH SIDE).
  
 2ND REVIEW - NOT ADDRESSED.IT IS NOT CLEAR WHERE
 ACCESS TO THE PUBLIC SIDEWALK IS LOCATED, IF ANY.NONE
 SHOWN ON SHEET 1 PREPARED BY LAND DESIGN SOUTH, BUT
 THIS IS NOT SHOWN FOR THE ACCESSIBLE PARKING ACCESS
 AISLE EITHER.THE REQUIREMENT FOR THE ACCESS AISLE TO
 SIDEWALK CHANGE IN ELEVATION REQUIREMENT IS COMMON
 KNOWLEDGE, BUT THE REQUIREMENT OF ACCESSIBILITY TO THE
 PUBLIC WAY MAY NOT BE.PLEASE SHOW ON THE PLANS AS
 REQUESTED.SHEET A1 IS NOT CLEAR; WHAT ARE THE DASHED
 LINES?I CANNOT DETERMINE WHETHER OR NOT THE CONCRETE
 IS CONTINUOUS, OR IF THE DASHED LINES REPRESENT A CURB
 WITH A CHANGE IN ELEVATION EXCEEDING THAT PERMITTED BY
 FBC11-3.
  
 13.)ADDRESSED.
  
 14.) ON THE SITE PLAN, SHOW THE DISTANCE TO THE
 PROPERTY LINES, INCLUDING THE DISTANCE FROM THE
 BUILDING TO THE ASSUMED LOT LINE.THIS APPEARS TO BE
 5'.SEE FBC TABLE 602 AND SHOW COMPLIANCE ON THE PLAN.
 ANY REQUIRED FIRE RATED WALLS ARE TO BE NOTED ON BOTH
 THE ARCHITECTURAL PLAN AND THE MECHANICAL PLAN.IF
 FIRE RATED WALLS ARE REQUIRED BY FBC TABLE 602 (OR
 OTHER CODE REQUIREMENTS) PLEASE PROVIDE A DETAIL;
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
  
 2ND REVIEW - THE ARCHITECT'S RESPONSE LETTER STATES:
 THE ASSUMED LOT LINE WAS AN ARBITRARY LINE, AND WE HAVE
 REMOVED IT ON THE REVISED SITE PLAN.
  
 A REVISED SITE PLAN WAS NOT SUBMITTED; SAME INFORMATION
 WAS PROVIDED SHOWING THE BUILDING LOCATED 5' TO THE
 "ASSUMED LOT LINE" TO THE EAST.ALSO, ON SHEET A2, THE
 ARCHITECT STATES THAT THE EAST WALL IS 5' FROM THE
 PROPERTY LINE WITH UNLIMITED OPENINGS ALLOWED.NOTE
 THE FOLLOWING:
  
 A.IN MY CONVERATION WITH THE ARCHITECT'S OFFICE, I
 WAS INFORMED THAT THIS IS A LEASE LINE.NOTE THAT
 LEASE LINES ARE NOT ADDRESSED IN THE BUILDING CODE AND
 THEREFORE DO NOT HAVE BUILDING CODE REQUIREMENTS.
 HOWEVER, SEE FBC704.3 REGARDING BUILDINGS LOCATED ON
 THE SAME LOT.THE LINE IS NOT AN ARBITRARY LINE; IT IS
 TO BE DETERMINED BY THE DESIGN PROFESSIONAL AND IS
 REQUIRED TO BE CODE COMPLIANT WITH CODES PREVIOUSLY
 REFERENCED.NOT ONLY IS THIS BUILDING TO COMPLY WITH
 THESE REQUIREMENTS, BUT BY CREATING A NEW ASSUMED
 PROPERTY LINE, THE ADJACENT BUILDING IS ALSO TO BE
 COMPLIANT (CANNOT CREATE A SITUATION WHERE A COMPLIANT
 BUILDING IS MADE NONCOMPLIANT).
  
 B.SEE FBC TABLE 602; 1 HOUR EXTERIOR WALL REQUIRED ON
 THE EAST SIDE BASED ON INFORMATION DECLARED BY
 ARCHITECT.
  
 C.SEE FBC TABLE 704.8; NO OPENINGS PERMITTED.NOTE
 THAT FOOTNOTE 6 DOES NOT APPLY AS, DUE TO THE 1 HOUR
 REQUIREMENT FBC TABLE 602.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE IN RESOLVING
 THIS MATTER.
  
 15.)SEE FBC TABLE 704.8 REGARDING ALLOWABLE OPENINGS
 AND SHOW COMPLIANCE ON THE PLAN (EAST SIDE AND OTHER
 BUILDING ELEVATIONS LESS THAN 30').NOTE THAT IF THE
 BUILDING IS 5? FROM THE ASSUMED LOT LINE AS SHOWN, ALL
 OPENINGS ARE TO BE PROTECTED.IF ANY OPENING
 PROTECTION IS REQUIRED, NOTE ON PLAN AND SUBMIT PRODUCT
 APPROVALS AND FIRE RATING INFORMATION.
  
 2ND REVIEW, SEE ITEM 14.
  
 16.) PLEASE NOTE FLOOD ZONE INFORMATION ON THE PLAN
 AND, IF IN A SPECIAL FLOOD HAZARD AREA, MINIMUM FFE
 (REQUIRED TO BE 6" ABOVE BFE) IS REQUIRED TO BE SHOWN
 ON THE PLAN CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B)).
  
 2ND REVIEW, DESIGN PROFESSIONAL (ARCHITECT OR ENGINEER)
 IS TO DETERMINE HEIGHT OF FINISHED FLOOR ELEVATION FOR
 THIS PROJECT.THERE IS A HANDWRITTEN NOTE ON THE
 ENGINEERING COMMENT LIST STATING THAT THE INFORMATION
 IS IN ANOTHER PERMIT.THIS PERMIT IS SEPARATE FROM THE
 PERMIT REFERENCED, AND THIS PERMIT IS TO SHOW CODE
 COMPLIANCE.AS PER FEMA REQUIREMENTS, A FORM BOARD
 ELEVATION CERTIFICATE WILL BE REQUIRED BEFORE CONCRETE
 POUR.THE REQUIRED ELEVATION IS TO BE SHOWN ON THE
 PLAN FOR THIS PERMIT.EVEN IF THE SITEWORK PERMIT
 ADDRESSED THE ELEVATION FOR THIS BUILIDNG, IT IS
 UNLIKELY THAT THIS WILL BE AVAILABLE TO THE INSPECTOR
 WHEN HE DOES THE INSPECTION ON THIS PERMIT.NOTE THAT
 THIS REQUIREMENT AFFECTS THE CITY'S COMMUNITY RATING
 WITH FEMA AND THE RATES WHICH PROPERTY OWNERS PAY FOR
 FLOOD INSURANCE.THIS IS REQUIRED TO BE ON THE PLAN.
  
  
 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY.
  
 2ND REVIEW; YOU ARE REQUESTING A ROOF PERMIT.THIS
 INFORMATION IS REQUIRED SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.THE RESPONSE LETTER STATES "SEE ATTACHED
 PRODUCT APPROVAL INFORMATION SHEETS."NOTHING WAS
 PROVIDED AND THE APPROVED ASSEMBLY (CHOICES LOCATED
 BETWEEN SHEETS 7 THROUGH 18 OF THE NOA) WAS NOT
 SELECTED.
  
 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR
 CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY
 AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 AS PER GENERAL LIMITATION 7 ON THE NOA.
  
 19.)ADDRESSED.
  
 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF
 ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE
 PROVIDE PRODUCT APPROVALS, FAC9B72.
  
 2ND REVIEW - THIS INFORMATION IS REQUIRED AT THIS TIME
 AS YOUR ROOFER HAS SIGNED ON AND A ROOF PERMIT HAS BEEN
 ASSIGNED.IF YOU WOULD LIKE, PLEASE REMOVE THIS,
 CANCEL THE PERMIT THROUGH THE FRONT COUNTER WHEN
 RESUBMITTING, AND THE ROOFING CONTRACTOR CAN APPLY FOR
 A SUBCONTRACTOR PERMIT WITH ALL OF THE REQUIRED
 INFORMATION.PRODUCT APPROVALS ARE TO REMAIN IN THE
 PACKAGE.
  
 21-22.)ADDRESSED.
  
 NEW COMMENTS:
  
 23.)BOTH THE ARCHITECT AND ENGINEER HAS SPECIFIED
 DESIGN PRESSURES FOR COMPONENTS AND CLADDING, BUT THE
 PRESSURES SHOWN ON A6 APPEAR TOO LOW FOR THIS WIND ZONE
 AND CONFLICT WITH S0.2.PLEASE PROVIDE ONLY ONE DESIGN
 PRESSURE CRITERIA.IF YOU USE THE PRESSURES ON A6,
 PLEASE PROVIDE CALCULATIONS.
  
 24.)THE ADDRESS FOR THE ENGINEER, RICHARD ADAMS PE,
 CONFLICTS WITH DBPR WEBSITE.PLEASE CORRELATE.
  
 25.)PLEASE KEEP THE IMPACT FEE STAMP AND RECEIPT IN
 THE PERMIT PACKAGE.
  
 WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 INDICATING HOW ALL COMMENTS HAVE BEEN ADDRESSED.ONLY
 EIGHT OUT OF 22 COMMENTS WERE INCLUDED IN THE RESPONSE
 LETTER.OTHER COMMENTS CAN BE ADDRESSED WITH A LETTER
 FROM THE CONTRACTOR OR OTHER PARTY FAMILIAR WITH THE
 PROJECT IF THE ARCHITECT IS NOT RESPONSIBLE FOR THE
 OTHER ITEMS.NOTE THAT SEVERAL ITEMS WERE NOT
 ADDRESSED.PLEASE ADDRESS ALL COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By shill Date 2007-11-09 Time 10:44 Rev Time 0.00
Received By shill Date 2007-11-08 Time 17:53 Sent To  
Notes
2007-11-09 10:46:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY).
 INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.
  
 2.)DOCUMENTS PREPARED BY A LANDSCAPE ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.PLANS STATE THAT THIS IS
 ?INFORMATIONAL ONLY? AND ?PAD ONLY? BUT THIS SHEET IS
 USED TO DETERMINE CODE COMPLIANCE FOR ACCESSIBLE
 PARKING AND FBC CHAPTER 5; SEE OTHER COMMENTS.
  
 3.)STATE THE TOTAL NUMBER OF ACCESSIBLE PARKING AND
 TOTAL NUMBER OF PARKING SPACES FOR THIS PARCEL.NOTE
 THAT THE SITE PLAN STATES THAT THEREARE 176 TOTAL, 6
 ACCESSIBLE WOULD BE REQUIRED BUT ONLY FIVE SHOWN, BUT
 IT APPEARS THAT THIS TOTAL IS FOR FOUR PARCELS.PLEASE
 SHOW COMPLIANCE WITH FBC11-4.1.2(5)(A).
  
 4.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY.
  
 5.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.
  
 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL
 ONLY (SIGNS, ETC.).
  
 7.)THE ENERGY CALCS STATE THIS IS AN OFFICE, PLANS
 SHOW RETAIL.PLEASE CORRELATE.
  
 8.)ENERGY CALCS STATE 4005 SF, PLANS SHOW 4019,
 ARCHITECT DECLARES 4000.THE DIFFERENCE AFFECTS
 OCCUPANT LOAD; PLEASE CORRELATE.
  
 9.)SEE ZONING COMMENTS REGARDING PARKING STRIPING
 DETAIL.
  
 10.)THE SITE PLAN AND ARCHITECTURAL PLANS STATE THAT
 THIS IS A RETAIL SHELL BUILDING, BUT THE ARCHITECT
 DECLARES B OCCUPANCY ON AR1 AND OTHER SHEETS.SEE
 FBC304, FBC309 AND REVISE EITHER BUILDING DESCRIPTION
 OR OCCUPANCY CLASSIFICATION.
  
 11.)SEE FBC1004 AND COMMENT ABOVE REGARDING SF AREA
 AND REVISE OCCUPANT LOAD.SEE FBC TABLE 1004.1.2; 30
 SF PER PERSON REQUIRED FOR MERCANTILE (NOT 100SF AS FOR
 BUSINESS OCCUPANCY).ALSO WHEN REVISING, PLEASE ROUND
 UP AS FBC 1004 REQUIRES OCCUPANT LOAD TO BE NOT LESS
 THAN THE TABLE.
  
 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN
 ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE
 MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR
 TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND
 LOADING AREA AT NORTH SIDE).
  
 13.)AR1, PLEASE STATE BUILDING TYPE AS A OR B (RATHER
 THAN ?UNPROTECTED?, TERMINOLOGY FROM FBC2001).SEE FBC
 TABLE 601.
  
 14.) ON THE SITE PLAN, SHOW THE DISTANCE TO THE
 PROPERTY LINES, INCLUDING THE DISTANCE FROM THE
 BUILDING TO THE ASSUMED LOT LINE?.THIS APPEARS TO BE
 5?.SEE FBC TABLE 602 AND SHOW COMPLIANCE ON THE PLAN.
 ANY REQUIRED FIRE RATED WALLS ARE TO BE NOTED ON BOTH
 THE ARCHITECTURAL PLAN AND THE MECHANICAL PLAN.IF
 FIRE RATED WALLS ARE REQUIRED BY FBC TABLE 602 (OR
 OTHER CODE REQUIREMENTS) PLEASE PROVIDE A DETAIL;
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
  
 15.)SEE FBC TABLE 704.8 REGARDING ALLOWABLE OPENINGS
 AND SHOW COMPLIANCE ON THE PLAN (EAST SIDE AND OTHER
 BUILDING ELEVATIONS LESS THAN 30?).NOTE THAT IF THE
 BUILDING IS 5? FROM THE ASSUMED LOT LINE AS SHOWN, ALL
 OPENINGS ARE TO BE PROTECTED.IF ANY OPENING
 PROTECTION IS REQUIRED, NOTE ON PLAN AND SUBMIT PRODUCT
 APPROVALS AND FIRE RATING INFORMATION.
  
 16.) PLEASE NOTE FLOOD ZONE INFORMATION ON THE PLAN
 AND, IF IN A SPECIAL FLOOD HAZARD AREA, MINIMUM FFE
 (REQUIRED TO BE 6? ABOVE BFE) IS REQUIRED TO BE SHOWN
 ON THE PLAN CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B)).
  
 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY.
  
 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR
 CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY
 AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 AS PER GENERAL LIMITATION 7 ON THE NOA.
  
 19.)A5, PLANS STATE CLAY ROOF, CONCRETE ROOF TILE
 PRODUCT APPROVAL SUBMITTED.PLEASE CORRELATE.
  
 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF
 ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE
 PROVIDE PRODUCT APPROVALS, FAC9B72.
  
 21.)SHEATHING IS TO COMPLY WITH FBC TABLE 2304.7(3),
 1/180 PLF.STATE DESIGN CRITERIA ON THE PLAN, SHEET S2
 (DUE TO USE OF ?? PLYWOOD WITH A TILE ROOF).
  
 22.)ROOF DRAINAGE TO COMPLY WITH FBC1503.4; PLEASE
 SUBMIT CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 08:46 Sent To PC
Notes
2008-10-28 08:46:51 
 ** DENIED 2ND REVIEW**
  
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW, PLEASE SEE
 13-101.1.6
 13-101.1.6 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED.
  
 ** PLEASE SEE SENTENCE #2 ABOVE. HOW CAN THE TOTAL
 WATTAGE *ASSUMED* FOR THE SHELL OF THE BUILD OUT BE
 THIS LOW?
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-02 Cont ID  
Sent By dpalmer Date 2008-09-02 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2008-09-02 Time 14:16 Sent To M
Notes
2008-09-02 14:16:50** DENIED REVISION **
  
  
  
 1) NOTE: PLEASE SEE 13-101.6. MAY ONLY USE METHOD B OR
 C. MAY NOT USE METHOD *A* FOR A SHELL BUILDING.
  
 ** PLEASE BE SURE ALL INFORMATION ON THE INPUT DATA
 REPORT COORDINATES WITH PLANS. AS SUBMITTED SOME
 INFORMATION ON THE IDR DOES NOT COORDINATE WITH PLANS.
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 2) NOTE: PLEASE SEE 13-103.1 AS ALL INFORMATION ON THE
 CERTIFICATION SHEET SHALL BE COMPLETED AS REQUIRED.
 FS 481/471
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-20 Cont ID  
Sent By dpalmer Date 2008-03-20 Time 14:05 Rev Time 0.00
Received By dpalmer Date 2008-03-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By dpalmer Date 2008-01-11 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2008-01-11 Time 16:00 Sent To  
Notes
2008-01-11 16:00:29*** DENIED 2ND REVIEW ***
  
 **NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS REVIEW WITH
 RESPECT TO FBC CHAPTER 13.
 PLEASE SEE 13.101.1.6, 13-415.2, 13-415.2.ABC.1.3
 PLEASE SEE NEW METHOD *B* CALCULATIONS ARE NOW BEING
 SUBMITTED HOWEVER THEY DO NOT COORDINATE WITH THE
 ELECTRICAL PLANS AS SUBMITTED.
 PLEASE SEE FOR EXAMPLE ONLY ONE FIXTURE TYPE IS SHOWN
 FOR INTERIOR LIGHT FIXTURES ON THE INPUT DATA REPORT
 YET THE PLANS CLEARLY SHOW OTHER TYPES AND WATTAGES.
 PLEASE SEE FOR EXAMPLE THE PLANS CLEARLY SHOW EXTERIOR
 LIGHT FIXTURES YET THE INPUT DATA REPORT CONTAINS NO
 FIXTURES AT ALL. (THIS SECTION ON THE IDR IS BLANK)
 HOW IS THIS POSSIBLE?
 PLEASE SEE THE SECTION OF THE CODE ABOVE AND PLEASE SEE
 USE AND ASSUMPTIONS WHICH ARE REQUIRED.
  
 ** RESPONSE LETTER DOES NOT ADDRESS COMMENT #4.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 14:32 Sent To  
Notes
2007-11-26 14:33:03** DENIED **
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW. THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH MAY NOT BE MADE AT THIS TIME.
  
 1) NOTE: PLEASE KNOW THE FOLLOWING CODES SHALL BE ON
 PLANS AS WELL AS ELECTRICAL SHEET E-1.
 FBC 2004 W/2007 REVISIONS
 NFPA-101 2003
 NFPA-72 2002 (WHEN APPLICABLE)
 NFPA-70 2005
  
 ** PLANS NOTE A 2000 NEC, HOWEVER AS NOTED ABOVE THE
 CODE IS 2005. PLEASE KNOW THERE WAS A 1999, AND THEN
 2002 NFPA-70.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS FOR MEP DESIGN
 TEAM IS NOT COMPLETE WITH INFORMATION AS REQUIRED PER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA
 STATUTES 471.023
 ( MISSING CA #)
  
 3) NOTE: PLEASE BE SURE RAISED SEALED IS CLEAR AND
 VISIBLE WITH ALL INFORMATION ON RAISED SEAL AS REQUIRED
 PER FAC 61G15-23.001.
 PLEASE SEE THE SEAL IS VERY FAINT NOT EASILY READ.
  
 4) NOTE: PLEASE SEE FBC 13-101.1.6 AS THIS IS A SHELL
 BUILDING AND METHOD *A* ENERGY CALCULATIONS ARE BEING
 SUBMITTED WHICH IS NOT PERMITTED.
 PLEASE SUBMIT AND INDICATE ALL TO COMPLY WITH 13-415.2
  
 5) NOTE: PLEASE SEE 250.6, 250.24 AS AN *EQUIPMENT
 GROUNDING CONDUCTOR* IS NOT PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
 RISER SHOWS THIS WHICH IS NOT PERMITTED.
  
 6) NOTE: PLEASE SEE GROUNDING ELECTRODE NOTE WHICH
 MENTIONS TO *BUILDING STEEL*, IS THIS FOOTER STEEL? AS
 BUILDING STEEL IS ALSO REQUIRED (DEPENDING ON
 CONSTRUCTION) , PLEASE LIST FOOTER STEEL.
 250.50
  
 7) NOTE: PLEASE KNOW AS PER THE FIRE MARSHAL CHIEF AND
 LIFE SAFETY CODE, PLEASE PROVIDE MINIMAL LIGHTING FOR
 EGRESS INTO SPACE.
 EM AND EXT LIGHTS ARE SHOWN; HOWEVER NO LIGHTING FOR
 NORMAL CONDITIONS IS SHOWN AND WILL BE REQUIRED. PLEASE
 SEE 700.12F FOR CIRCUITING OF EM AND EXT LTS. (LOCAL
 BRANCH CIRCUIT) (AS NOTED ON PLANS)
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2008-05-08 Cont ID  
Sent By rchokshi Date 2008-05-08 Time 15:30 Rev Time 0.00
Received By rchokshi Date 2008-05-08 Time 15:30 Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2008-05-02 Cont ID  
Sent By rchokshi Date 2008-05-02 Time 13:36 Rev Time 0.00
Received By rchokshi Date 2008-05-02 Time 13:25 Sent To  
Notes
2008-05-02 13:35:39FAILED
  
 I TALKED TO ASSISTANT ENGINEER OF JUSTIN POLK, P.E.
 THAT THEY WILL SHOW THE SILT FENCE AROUND THE 4 SIDES
 OF THE SITE FOR POLLUTION PREVENTION.
 PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS MUSTSHOW
 SILT FENCE AROUND THE WHOLESITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE. PLEASE SHOW
 HEIGHT OF SILT FENCE, &POSTDETAILS ON THE DRAWINGS
 .HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO
 STOP DUST PARTICLES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-03-28 Cont ID  
Sent By rchokshi Date 2008-03-28 Time 14:20 Rev Time 0.00
Received By rchokshi Date 2008-03-28 Time 14:18 Sent To  
Notes
2008-03-28 14:20:11FAILED
  
  
 PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE. PLEASE SHOW
 HEIGHT OF SILT FENCE IN DETAILS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-01-10 Cont ID  
Sent By rchokshi Date 2008-01-10 Time 10:58 Rev Time 0.00
Received By rchokshi Date 2008-01-10 Time 10:42 Sent To  
Notes
2008-01-10 10:57:53FAILED FOR FOLLOWING REASONS:
  
 OUR RESPONSE TO YOUR LETTER 12/13/07:WE LOOKED AT
 PERMIT# 07030860, AND CORRECTED ACCORDINGLY.HOWEVER,
 ACCORDING TO YOUR LETTER "THIS APPLICATION IS FOR BLDG
 SHELL& PAD ONLY"DOES NOT MATCH PER YOU WROTE IN
 PERMIT .DESCRIBE PROJECT IN DETALYOU WROTE
 "CONSTRUCT NEW RETAIL BUILDING PER PLAN"THEN YOU NEED
 TO APPLY SEPARATE PERMIT.
  
 1.IF YOU ARE ADDING ANY SIDEWALK, DRIVEWAY,
 APPROACHES, PARKING/HANDICAP PARKING OTHER THAN
 PREVIOUSLY ISSUED PERMIT # 07030860,PLEASE SHOW ON
 DRAWING ALL CITY STANDARDS NOTES FOR SIDEWALK,
 DRIVEWAY, APPROACH, PARKINGS, HANDICAP PARKINGS,
 DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL CITY
 STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASEMAKE SURE YOU MEET PREVIOUSLY ISSUED SFWMD
 PERMIT ( WPB PERMIT # 07030860) REQUIREMENT FORFLOOD
 ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA AND
 CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST FLOOR
 ELEVATION.
 4. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By rchokshi Date 2007-11-26 Time 11:37 Rev Time 0.00
Received By rchokshi Date 2007-11-26 Time 11:30 Sent To  
Notes
2007-11-26 11:37:27FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 13:26 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 13:03 Sent To  
Notes
2008-04-07 13:22:29*****APPROVED*****
  
  
 PLAN SHEETS A1, A2.0, M1, AND E1 WERE STAMPED,
 INTIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-12 Cont ID  
Sent By mawillia Date 2008-02-12 Time 12:49 Rev Time 0.00
Received By mawillia Date 2008-02-12 Time 12:25 Sent To  
Notes
2008-02-12 12:39:01*****PROVISO*****
  
  
 PLANS WERE PREVIOUSLY APPROVED ON 11/14/07 BY FIRE
 MARSHAL MIKE CARSILLO, HOWEVER THE APPROPIATE PLAN
 SHEETS TO BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE
 BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-11-14 Cont ID  
Sent By mcarsill Date 2007-11-14 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2007-11-14 Time 09:54 Sent To  
Notes
2007-11-14 10:07:171. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SUITABLE ACCESS IS TO BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. EXITS SHALL BE PROVIDED DURING CONSTRUCTION.
  
 5. BUILDING ADDRESS, AND PORTABLE FIRE EXTINGUISHER
 REQUIREMENT ARE LISTED ON PLANS. INTERIOR FINISH
 REQUIREMENTS ARE ALSO LISTED ON THE PLANS.
  
 APPROVED PROVISIO;
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 10:51 Sent To B
Notes
2008-12-22 10:51:21TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 08:53 Sent To B
Notes
2008-11-25 08:53:45TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 09:04 Sent To B
Notes
2008-10-10 09:05:10TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:28 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:28 Sent To M
Notes
2008-10-03 16:29:08TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 11:50 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 11:50 Sent To M
Notes
2008-09-10 11:51:14TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 15:52 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 15:51 Sent To B
Notes
2008-08-27 15:52:40TO "BUILD" SAMANTHA H.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 12:10 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 12:00 Sent To  
Notes
2008-05-08 12:14:25TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 08:46 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 08:38 Sent To  
Notes
2008-04-28 08:48:54TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-18 Cont ID  
Sent By adarroug Date 2008-03-18 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-03-18 Time 11:39 Sent To  
Notes
2008-03-19 13:28:17TO "COMM" BD#63
2008-03-18 11:39:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-08 Time 08:40 Rev Time 0.00
Received By adarroug Date 2008-01-08 Time 08:40 Sent To  
Notes
2008-01-08 08:41:05TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 16:12 Rev Time 0.00
Received By kstevens Date 2007-10-24 Time 12:02 Sent To  
Notes
2007-11-13 09:14:03TO "COMM" BD#2
2007-10-24 12:03:05WIATING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-10-06 Cont ID  
Sent By rregueir Date 2008-10-06 Time 09:15 Rev Time 0.00
Received By rregueir Date 2008-10-06 Time 09:15 Sent To B
Notes
2008-10-06 09:16:16REVISED CALCS AND SYSTEM SIZING SUMMARY. MECH ONLY OK.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-10-06 Cont ID  
Sent By rregueir Date 2008-10-02 Time 09:02 Rev Time 0.00
Received By rregueir Date 2008-09-18 Time 16:58 Sent To PC
Notes
2008-10-06 09:02:12REVISED CALCS WITHDRAWN BY CONTRACTOR. WILL BE
 RESUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-09-04 Cont ID  
Sent By rregueir Date 2008-09-04 Time 08:17 Rev Time 0.00
Received By rregueir Date 2008-09-04 Time 08:06 Sent To PC
Notes
2008-09-04 08:17:00REVIEW: REVISED ENERGY CALCULATIONS
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHELL BUILDINGS SHALL COMPLY WITH THIS CODE BY
 METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED DESIGN
 PARAMETERS ARE KNOWN, A METHOD A CALCULATION MAY BE
 RESUBMITTED IN ACCORDANCE WITH FBCB 13-400.2.A.2. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT IN ACCORDANCE WITH FBCB
 13-101.1.6.
  
 2. COOLING LOAD CALCULATIONS SHALL BE ATTACHED TO THE
 ENERGY CODE COMPLIANCE FORMS IN ACCORDANCE WITH FBCB
 13-407.1.ABC.1.
  
 3. THE NAMES AND LICENSE NUMBERS OF THE ARCHITECT,
 LIGTING AND ELECTRICAL DESIGNERS ARE MISSING FROM THE
 CERTIFICATIONS PAGE (PAGE 3 OF THE COMPLIANCE FORM).
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 TYPED NAMES AND REGISTRATION NUMBERS MAY BE PROVIDED IN
 LIEU OF A SIGNATURE WHERE ALL RELEVANT INFORMATION HAS
 BEEN INCLUDED ON SIGNED AND SEALED PLANS IN ACCORDANCE
 WITH FBCB 13-103.1.1.1.
  
 PLEASE MAKE ALL NECESSARY CORRECTIONS AND RESUBMIT FOR
 REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 16:25 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 10:48 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 10:37 Sent To  
Notes
2008-01-22 10:48:45REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THRU 3: OK
  
 4. THE SYSTEM SIZING SUMMARY IS TO BE SIGNED AND SEALED
 BY THE ENGINEER AND ATTACHED TO THE CODE COMPLAINCE
 FORM IN ACCORDANCE WITH FBC 13-407.1.ABC.1. SEE THE
 TEXT OF EXCEPTION #1 BELOW:
 "WHERE MECHANICAL SYSTEMS ARE DESIGNED BY AN ENGINEER
 REGISTERED IN THE STATE OF FLORIDA, THE ENGINEER HAS
 THE OPTION OF SUBMITTING A SIGNED AND SEALED SUMMARY
 SHEET IN LIEU OF THE COMPLETE SIZING CALCULATION(S)."
 PLEASE PROVIDE SIGNED AND SEALED SYSTEM SIZING SUMMARY
 ATTACHED TO THE ENERGY CALCULATIONS AND RESUBMIT. THIS
 ITEM COULD BE HANDLED AS A PROVISO IF IT WERE THE ONLY
 ITEM OUTSTANDING.
  
 5 THRU 7: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By rregueir Date 2007-11-26 Time 17:11 Rev Time 0.00
Received By rregueir Date 2007-11-26 Time 15:39 Sent To  
Notes
2007-11-26 17:10:38REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS BASED ON OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD AND CFM REQUIRED AS
 STATED IN FBC,M TABLE 403.3 OR ASHRAE 62.1-2004. ALSO,
 PROVIDE MECHANICAL VENTILATION FOR THE TOILET ROOMS IN
 ACCORDANCE WITH THIS SECTION.
  
 2. SHOW LOCATION OF EXHAUST DISCHARGE IN COMPLIANCE
 WITH FBC,M 401.5.
  
 3. ENERGY CALCULATIONS: AS THIS IS A SHELL BUILDING,
 PROVIDE METHOD B OR C COMPLIANCE FORMS IN ACCORDANCE
 WITH FBC 13-101.1.6. ALL ASSUMPTIONS MADE ABOUT
 FEATURES NOT INSTALLED UNTIL LATER THAT ARE NOT ON THE
 BUILDING PLANS SHALL BE LISTED AND APPENDED TO THE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A
 METHOD A CALCULATION MAY BE RESUBMITTED IN ACCORDANCE
 WITH FBC 13-400.2.A.2.
  
 4. ENERGY CALCULATIONS: A COOLING LOAD CALCULATION
 SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED
 TO THE BUILDING DEPARTMENT WHEN THE BUILDING IS
 PERMITTED IN ACCORDANCE WITH FBC 13-407.1.ABC.1. HVAC
 SYSTEMS AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE
 THAN THE SPACE AND SYSTEM LOADS CALCULATED IN
 ACCORDANCE WITH SECTION 407.1.ABC.1.
  
 5. PROVIDE SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBC 13-409.1.ABC.3.3.
  
 6. ENGINEERING BUSINESS (C.O.A.) NUMBER IS MISSING FROM
 ENGINEERING FIRM'S TITLE BLOCK. SEE FAC RULE
 61G15-23.002.
  
 7. SHOW MEANS OF AUXILIARY DRAIN PROTECTION TO PREVENT
 THE OVERFLOW OF CONDENSATE INTO THE STRUCTURE IN
 ACCORDANCE WITH FBC,M 307.2.3(2). A WATER LEVEL
 DETECTION DEVICE, SUCH AS A FLOAT SWITCH, INSTALLED
 INTERNALLY ON THE PRIMARY DRAIN PAN OF THE RTU WOULD
 MEET THIS REQUIREMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By kstevens Date 2008-02-01 Time 15:28 Rev Time 0.00
Received By kstevens Date 2008-02-01 Time 16:48 Sent To  
Notes
2008-02-06 15:36:58PASSED/PROVISO--CLEANOUT REQUIRED PER SECTION
 708.3.5 & AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE PER SECTION 608.13.2

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 15:56 Rev Time 0.00
Received By kstevens Date 2007-12-06 Time 15:56 Sent To  
Notes
2007-12-06 16:11:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT AR1 FLORIDA BUILDING CODE DATA INDICATES
 CLASSIFICATION OF OCCUPANCY AS BUSINESS, BUT THE TITLE
 SHEET AND APPLICATION STATES RETAIL. PLEASE CORRELATE
 OCCUPANCY. SECTION 106.1.1.
  
 2. SHT A5 DETAIL 2A5 SCUPPER DETAIL. PROVIDE DIMENSIONS
 FOR THE SCUPPER. PROVIDE LENGTH, WIDTH AND HEIGHT OF
 OPENING IN THE SCUPPER AS WELL AS THE SIZE OF THE
 DOWNSPOUT. SECTION 1106.
  
 3. SUBMIT CALCULATIONS FOR THE PRIMARY AND THE
 EMERGENCY OVERFLOW SCUPPERS. INDICATE THE SQUARE
 FOOTAGE OF EACH AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING THE PARAPETS TO EACH AREA AS WELL AS
 ANY AREA FROM ROOFS DRAINING ONTO THE ROOF AREAS FROM
 ABOVE. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND
 TABLES.
  
 4. SHT P1 A CLEANOUT IS REQUIRED NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING SEWER PER SECTION
 708.3.5. PLEASE SHOW ON THE PLANS.
  
 5. SHT P1 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW
 ON THE PLANS. (NOTE STATES SEE CIVIL PLANS FOR
 CONTINUATION, BUT THE CIVIL PLANS HAVE NOT BEEN
 SUBMITTED).
  
 6. THE MPE SHEETS TITLE BLOCKS ARE MISSING THE
 CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK OF THE
 ENGINEERING FIRM. FAC 61G15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-05-02 Cont ID  
Sent By jroach Date 2008-05-02 Time 15:43 Rev Time 0.00
Received By jroach Date 2008-05-02 Time 15:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-04-01 Cont ID  
Sent By jroach Date 2008-04-01 Time 10:15 Rev Time 0.00
Received By jroach Date 2008-04-01 Time 10:14 Sent To  
Notes
2008-04-01 10:19:12***FAILED***
  
 THE FOLLOWING ARE NEW COMMENTS BASED UPON
 NEWLY-SUBMITTED PLANS...
  
 1) THE PROPOSED SITE PLANS SHOWS AN EXISTING
 TRANSFORMER LOCATED AT THE NORTHEAST CORNER OF THE
 BUILDING.AS SHOWN ON THE SUBMITTED LANDSCAPE PLANS,
 THIS IS TO BE THE LOCATION OF A SHADE TREE, AS WELL AS
 ADDITIONAL GROUNDCOVER.THE LANDSCAPE PLANS SHALL BE
 REVISED TO MATCH THE PROPOSED SITE PLAN, OR THE
 TRANSFORMER SHALL BE RELOCATED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By jroach Date 2008-01-18 Time 15:37 Rev Time 0.00
Received By jroach Date 2008-01-18 Time 15:37 Sent To  
Notes
2008-01-18 15:38:03***FAILED***
  
 ALL OF THE FOLLOWING ARE REPEAT COMMENTS...
  
 1) PLANS DO NOT MATCH THOSE APPROVED AS PART OF THE
 MINOR AMENDMENT PROCESS.PLANS SHALL MATCH THE LATEST
 APPROVAL, OTHERWISE ANOTHER MINOR AMENDMENT SHALL BE
 REQUIRED.
  
 2) LANDSCAPE PLANS (SIGNED AND SEALED BY A REGISTERED
 LANDSAPE ARCHITECT) SHALL BE PROVIDED.
  
 3) PLEASE CLARIFY WHY THE SITE PLAN IS FOR "REFERENCE
 ONLY."I BELIEVE THERE ARE SITE IMPROVEMENTS THAT WILL
 NEED TO BE INSTALLED AS PART OF THIS PERMIT (I.E.
 DUMPSTER ENCLOSURE, RECONFIGURATION OF THE PARKING IN
 THE FRONT, ETC.).
  
 4) AS THE BUILDING HAS BEEN EXPANDED CLOSER TO THE
 WESTERN ACCESS DRIVE, IT APPEARS THAT THE PROPOSED
 OVERHANGS OVER THE WINDOWS EXTEND INTO THE DRIVE AISLE.
 THE DRIVE AISLE IS TO BE 24 FEET IN CLEAR WIDTH...WITH
 NO OBSTRUCTIONS.
  
 5) THE PROPOSED LOADING ZONE DOES NOT CONFORM TO THE
 MINIMUM DIMENSIONAL REQUIREMENTS.SECTION 94-485(P)
 REQUIRES THAT A 10 FOOT X 25 FOOT LOADING ZONE BE
 PROVIDED.
  
 6) BIKE RACK SHALL BE PROVIDED.
  
 7) DETAILS SHALL BE PROVIDED OF THE DUMPSTER ENCLOSURE
 AS WELL HAS THE PARKING STRIPING DETAIL (SEE
 ATTACHED).
  
 8) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL
 BE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By jroach Date 2007-11-29 Time 21:12 Rev Time 0.00
Received By jroach Date 2007-11-29 Time 21:12 Sent To  
Notes
2007-11-29 21:31:51***FAILED***
  
 1) PLANS DO NOT MATCH THOSE APPROVED AT TIME OF FORMAL
 SITE PLAN REVIEW.MINOR AMENDMENT TO THE BAYWINDS
 RESIDENTIAL PLANNED DEVELOPMENT SHALL BE APPROVED PRIOR
 TO ISSUANCE OF THE BUILDING PERMIT.(THIS IS IN
 PROCESS)
  
 2) LANDSCAPE PLANS (SIGNED AND SEALED BY A REGISTERED
 LANDSAPE ARCHITECT) SHALL BE PROVIDED.
  
 3) PLEASE CLARIFY WHY THE SITE PLAN IS FOR "REFERENCE
 ONLY."I BELIEVE THERE ARE SITE IMPROVEMENTS THAT WILL
 NEED TO BE INSTALLED AS PART OF THIS PERMIT (I.E.
 DUMPSTER ENCLOSURE, RECONFIGURATION OF THE PARKING IN
 THE FRONT, ETC.).
  
 4) AS THE BUILDING HAS BEEN EXPANDED CLOSER TO THE
 WESTERN ACCESS DRIVE, IT APPEARS THAT THE PROPOSED
 OVERHANGS OVER THE WINDOWS EXTEND INTO THE DRIVE AISLE.
 THE DRIVE AISLE IS TO BE 24 FEET IN CLEAR WIDTH...WITH
 NO OBSTRUCTIONS.
  
 5) THE PROPOSED LOADING ZONE DOES NOT CONFORM TO THE
 MINIMUM DIMENSIONAL REQUIREMENTS.SECTION 94-485(P)
 REQUIRES THAT A 10 FOOT X 25 FOOT LOADING ZONE BE
 PROVIDED.
  
 6) BIKE RACK SHALL BE PROVIDED.
  
 7) DETAILS SHALL BE PROVIDED OF THE DUMPSTER ENCLOSURE
 AS WELL HAS THE PARKING STRIPING DETAIL (SEE
 ATTACHED).
  
 8) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL
 BE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  