Plan Review Details - Permit 07100637
Plan Review Stops For Permit 07100637
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 09:32 Sent To P
Notes
2007-11-07 09:32:55TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 13:00 Rev Time 0.00
Received By mperson Date 2007-10-24 Time 10:47 Sent To  
Notes
2007-10-24 10:47:51TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By mperson Date 2007-11-13 Time 14:54 Rev Time 0.00
Received By mperson Date 2007-11-13 Time 14:54 Sent To PC
Notes
2007-11-13 15:02:13****************PROVISO****************
 NOTE: A SEPERATE RIGHT OF WAY PERMIT IS REQUIRED FOR
 THE WORK CROSSING N. FLAGLER DR. PLEASE CONTACT WINDEL
 G. PALMER, UTILITIES ENGINEERING PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., PHONE: (561) 494-1040
 EXT:1086, FAX: (561) 494-1069, E-MAIL: [email protected]
  
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 11:28 Rev Time 0.00
Received By mperson Date 2007-11-05 Time 11:28 Sent To PC
Notes
2007-11-05 13:00:02DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. AT A MINIMUM THE CORRECT ADDRESS OF 807 N. FLAGLER
 DRIVE IS REQUIRED ON THE PLANS PER *106.1.3 QUALITY OF
 BUILDING PLANS. PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 3. CLEARLY INDICATE THE LOCATION OF THE "RAIN BIRD
 ESP-LX12 STATION CONTROLLER WITH 502-C MINI CLICK RAIN
 SENSOR" AS IT IS INDICATED IN THE IRRIGATION LEGEND ON
 THE RESUBMITTAL.
  
 4. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE
 PRESSURE VACUUM BREAKER WILL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR. PER *FS 489.105(3)(M) "PLUMBING
 CONTRACTOR".
  
 5. THE P. O. C. (POINT OF CONNECTION) SYMBOL IS THE
 SAME AS THE IRRITROL BUBBLER #533 IN THE IRRIGATION
 LEGEND. PLEASE CLARIFY OR CORRECT IF THIS IS OR IS NOT
 THE INTENT ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]