Plan Review Details - Permit 07100633
Plan Review Stops For Permit 07100633
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-10 Cont ID  
Sent By amorse Date 2007-11-10 Time 06:54 Rev Time 0.00
Received By amorse Date 2007-11-10 Time 06:54 Sent To  
Notes
2007-11-10 07:14:09 
  
 DENIED
  
 1)SCOPE OF WORK DOES NOT INCLUDE STRUCTURAL WORK ON
 BUILDING PARAPET AND ROOFING, INCLUDE ALL WORK IN THE
 SCOPE
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*, VALUE TO INCLUDE ALL INTERIOR AND
 EXTERIOR WORK THAT IS IN SCOPE.
  
 3)UPDATE INDEX ON COVER SHEET TO REFLECT NEW SCOPE
 AND ALL NEW SHEETS A/10, A11, A/12 AND S/1
  
 4)UPDATE CODE INFORMATION TO INCLUDE 2004 FBC W/ 2006
 AMENDMENTS ON BOTH COVER SHEET AND STRUCTURAL SHEET
 S/1
  
 5)PER FBC 1609, BASIC WIND SPEED FOR CITY OF WEST
 PALM BEACH IS 140 MPH EXP B PLEASE ADJUST STRUCTURAL
 NOTES ON S/1 ACCORDINGLY
  
 6)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 9) NO PRODUCT APPROVALS WERE SUBMITTED FOR HARDIPLANK
 SIDING, ROOFING AND CONNECTORS AND STRAPS. IN LUE OF
 PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A
 SCHEDULE ON THE DRAWINGS COMPLETE WITH THE STATEWIDE
 PRODUCT APPROVAL NUMBERS
  
 10)PROVIDE ALL ATTACHMENTS FOR NEW PARAPET TO MEET
 WIND LOADS, STRUCTURAL DRAWING SHOW CLIPS ON EXISTING
 BEAMFOR NEW BRACE BUT NO STRAPS/CONNECTORS ON PARAPET
 FRAMING.
  
 11)PROVIDE DETAIL FOR ROOFING TO PREVENT WATER
 INTRUSIONAT PARAPET BRACES AND ROOF
  
 12)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER 61G15-23.002(2) FAC
  
 13)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC.
 PLEASE NOTE THAT STRUCTURAL PAGE WAS NOT DATED.
  
 14)PLEASE NOTE SIGNS AND AWNINGS REQUIRE SEPARATE
 PERMITS
  
 15)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS, PLEASE PUT ALL PAGES IN EACH SET AS
 REVIEW WAS COMPLETED AND FUTHER PAGES WERE NOTICED AT
 LATER TIME BECAUSE THE SETS ARE SEPARATED.INCLUDE 1
 COPY OF THE OLD PAGES ONLY FOR REFERENCE
  
 16)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 16:31 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 16:31 Sent To  
Notes
2007-11-09 16:31:55** DENIED**
  
 ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS
 BEING SUBMITTED FOR REVIEW.
  
 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS
 PREVIOUSLY STATED AND REQUIRED BY FBC.
 2004 FBC/W2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THESE ARE SHOWN ALREADY.
  
 2) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 REVIEW. PLEASE SHOW CIRCUITING FOR NEW AND EXISTING
 ALONG WITH CONTROLS FOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SUBMIT ALONG WITH PANEL SCHEDULE WHICH WILL
 INDICATE THE MINIMUM SIZES OF CONDUCTORS AS REQUIRED W/
 OCP>
 NEC 240.4, 310.16, 408.4
 FBC 106.3.5.1.2
  
 3) NOTE: PLANS CONTAIN A NOTE FOR COMPLIANCE WITH THE
 FBC ENERGY CODE HOWEVER COULD NOT LOCATION INFORMATION
 FOR ANY NEW CONTROLS OR LIGHTING PERFORMANCE
 CALCULATIONS.
 13-415.2, 13-101, 13-415.1.ABC.1.2
 13-413.1.ABC.1.1, .1.2.
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN
 AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-14 Cont ID  
Sent By mcarsill Date 2007-11-14 Time 10:33 Rev Time 0.00
Received By mcarsill Date 2007-11-14 Time 10:20 Sent To  
Notes
2007-11-14 10:33:111. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6"HIGH AND AT LEAST 1" WIDE NUMBERS
 ARE REQUIRED.
  
 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. EXITS ARE TO BE MAINTAINED DURING DEMOLTION AND
 RENOVATION.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS OF THIS NON FIRE SPRINKLER PROTECTED
 OCCUPANCY.
  
 6. FLOOR PLANS DOES NOT ILLUSTRATE ANY PORTABLE FIRE
 EXTINGUISHING EQUIPMENT.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 09:38 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 10:27 Sent To  
Notes
2007-11-08 15:43:28TO "COMM" BD#29
2007-10-24 10:27:56WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 12:59 Rev Time 0.00
Received By choops Date 2007-11-16 Time 12:59 Sent To  
Notes
2007-11-16 13:00:03*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE, AND ONLY
 DOING INTERIOR RENOVATIONS.