Plan Review Details - Permit 07100632
Plan Review Stops For Permit 07100632
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-11-09 Cont ID  
Sent By mjacobs Date 2007-11-09 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2007-11-09 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 16:27 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 16:19 Sent To  
Notes
2007-11-09 16:28:05** DENIED**
  
 ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS
 BEING SUBMITTED FOR REVIEW.
  
 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS
 PREVIOUSLY STATED AND REQUIRED BY FBC.
 2004 FBC/W2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THESE ARE SHOWN ALREADY.
  
 2) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 REVIEW. PLEASE SHOW CIRCUITING FOR NEW AND EXISTING
 ALONG WITH CONTROLS FOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SUBMIT ALONG WITH PANEL SCHEDULE WHICH WILL
 INDICATE THE MINIMUM SIZES OF CONDUCTORS AS REQUIRED W/
 OCP>
 NEC 240.4, 310.16, 408.4
 FBC 106.3.5.1.2
  
 3) NOTE: PLANS CONTAIN A NOTE FOR COMPLIANCE WITH THE
 FBC ENERGY CODE HOWEVER COULD NOT LOCATION INFORMATION
 FOR ANY NEW CONTROLS OR LIGHTING PERFORMANCE
 CALCULATIONS.
 13-415.2, 13-101, 13-415.1.ABC.1.2
 13-413.1.ABC.1.1, .1.2.
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN
 AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By mawillia Date 2007-11-13 Time 17:26 Rev Time 0.00
Received By mawillia Date 2007-11-13 Time 16:53 Sent To  
Notes
2007-11-13 17:25:36*****DENIED*****
  
 1.THE LOCATION MAP ON THE COVER SHEET IS INCORRECT.
 THE SITE MORE CLOSELY ILLUSTRATES THE PROJECT SITE AS
 BEING IN THE BOCA RATON AREA.
  
 2.NO COMPASS/DIRECTION LEGEND ON THE APPROPIATE PLAN
 SHEETS.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 08:51 Rev Time 0.00
Received By kstevens Date 2007-10-24 Time 10:12 Sent To  
Notes
2007-11-08 13:40:01TO "COMM" BD#51
2007-10-24 10:15:39WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 08:41 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 08:41 Sent To  
Notes
2007-12-05 10:14:34DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE APPLICATION STATES "DESCRIBE THE PROJECT IN
 DETAIL" (FAILURE TO DO SO MAY RESULT IN DELAYS). WORK
 NOT INDICATED ON THE DESCRIPTION OF WORK INCLUDES
 PLUMBING WORK, ELECTRICAL WORK, DEMO AND REPLACE
 CEILINGS, DOOR FRAMES, DRYWALL, FLOORING ETC. PLEASE
 INDICATE ALL WORK IN THE DESCRIPTION OF WORK. SECTION
 105.3.
  
 2. SHT K1 INDICATES AN EQUIPMENT SCHEDULE. PLEASE
 INDICATE IF ANY OF THE KITCHEN EQUIPMENT WILL BE
 CHANGED OF IF ANY OTHER WORK WILL BE PROVIDED IN THE
 KITCHEN AREA. IF SO THAT SHALL BE ADDED TO THE
 DESCRIPTION OF WORK. SECTION 105.3.
  
 3. ALL SHEETS. THE ARCHITECTS FIRM LICENSE NUMBER.
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET AS WELL AS THE PRINTED NAME
 OF THE ARCHITECT. FAC 61G1-16.004(2)(6) & FS 481.2055.
 PLEASE SHOW THE FIRM LICENSE NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENTS.
  
 4. THE VALUE OF THE WORK SHOWN ON THE PLANS SEEMS TO BE
 LOW. FOR PERMITTING PURPOSES, THE VALUATION SHALL BE
 FOR TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, INTERIOR FINISH, LABOR,
 ARCHITECTURAL AND DESIGN FEES MARKETING COSTS, OVERHEAD
 AND PROFIT: EXCLUDING ONLY LAND VALUE. SECTION 108.3.
 PLEASE SHOW THE CORRECT VALUE OF ALL THE WORK ON THE
 APPLICATION.
  
 5. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM AND AN
 ISOMETRIC WATER RISER DIAGRAM FOR THE NEW PLUMBING
 WORK. SHOW THE PIPE SIZES, TRAPS, VENTS ETC. FOR THE
 SANT. AND THE PIPE SIZES, VALVES ETC. FOR THE WATER
 PIPING. SHOW THE CONNECTIONS TO EXISTING PLUMBING
 SYSTEMS. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 13:03 Rev Time 0.00
Received By choops Date 2007-11-16 Time 13:03 Sent To  
Notes
2007-11-16 13:04:03*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE, AND ONLY
 DOING INTERIOR RENOVATIONS.