Plan Review Details - Permit 07100626
Plan Review Stops For Permit 07100626
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 16:01 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 16:01 Sent To PC
Notes
2007-12-17 16:03:40****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 10:02 Rev Time 0.00
Received By mperson Date 2007-11-05 Time 10:02 Sent To PC
Notes
2007-11-05 10:34:28DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE.
 PLEASE RESUBMIT DRAWINGS IN PEN. PER *106.1.3, QUALITY
 OF BUILDING PLANS.
  
 2. ONLY ONE SET OF WATER HEATER MANUFACTURER
 SPECIFICATION SHEETS WERE SUBMITTED.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: CORRESPONDING LENGTH TO THE CUT SECTION OF PIPE
 TO THE WATER HEATER IS MISSING. PLEASE PROVIDE THIS
 INFORMATION ON THE RESUBMITTAL.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 (TWO COPIES REQUIRED) OF THE MP GAS REGULATORS WITH THE
 REGULATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGIZED TESTING LABORATORY
 ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 09:06 Sent To G
Notes
2007-12-13 09:06:53TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 10:34 Rev Time 0.00
Received By mperson Date 2007-10-23 Time 16:34 Sent To  
Notes
2007-10-23 16:35:00TO "G" BOX