Plan Review Details - Permit 07100621
Plan Review Stops For Permit 07100621
Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-01-31 Cont ID  
Sent By mperson Date 2008-01-31 Time 13:25 Rev Time 0.00
Received By mperson Date 2008-01-31 Time 13:25 Sent To PC
Notes
2008-01-31 14:07:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. PER FBC FUEL GAS TABLE 402.4(24) UNDILUTED PROPANE,
 THE PROPOSED 3/4" SCH. 40 METALLIC MAIN PIPE TO THE
 COOK LINE IS ONLY GOOD FOR 336,000 BTU'S. THE TOTAL
 BTU'S FOR THE PROPOSED GAS SYSTEM IS 345,000 BTU,S
 WHICH MEANS THE MAIN PIPE TO THE COOK LINE MUST BE 1".
 PLEASE REFERENCE TABLE 402.4(24) ATTACHED TO THESE
 COMMENTS INDICATING THIS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By mperson Date 2007-11-28 Time 10:37 Rev Time 0.00
Received By mperson Date 2007-11-28 Time 10:37 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By mperson Date 2007-11-05 Time 15:50 Rev Time 0.00
Received By mperson Date 2007-11-02 Time 15:50 Sent To PC
Notes
2007-11-02 17:01:23DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. DRAWINGS IN PENCIL ARE UNACCEPTABLE PER *106.1.3,
 QUALITY OF BUILDING PLANS.
  
 2. PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
 **NOTE: THERE WAS ONLY ONE SET OF MANUFACTURER'S
 SPECIFICATIONS FOR THE SUBMITTED GAS KITCHEN
 EQUIPMENT.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: THE MANUFACTURE SPECIFICATION SHEET FOR THE
 30,000 BTU BAKE OVENS IS NOT INDICATING A LISTING FROM
 A NATIONALLY RECOGNIZED TESTING LABORATORY FOR GAS. THE
 ETL INDICATED LISTING IS FOR ELECTRICAL.
  
 4. AN EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE IS
 REQUIRED FOR THE GAS SYSTEM WHERE A TYPE 1 HOOD IS
 INSTALLED IN A COMMERCIAL KITCHEN COOKLINE.
  
 **EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 A} PER MECHANICAL SECTION *507, COMMERCIAL KITCHEN
 HOODS SUB-SECTION *507.2.1, TYPE 1 HOODS. TYPE 1 HOODS
 SHALL BE INSTALLED WHERE COOKING APPLIANCES PRODUCE
 GREASE OR SMOKE, SUCH AS OCCURS WITH GRIDDLES, FRYERS,
 BROILERS, OVENS, RANGES AND WOK RANGES.
  
 B} PER BUILDING SECTION *904, ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS. SUB-SECTION *904.11.2,
 SYSTEMS INTERCONNECTION. THE ACTUATION OF THE FIRE
 SUPPRESSION SYSTEM SHALL AUTOMATICALLY SHUT DOWN THE
 FUEL OR ELECTRICAL POWER SUPPLY TO THE COOKING
 EQUIPMENT. THE FUEL AND ELECTRICAL, SUPPLY RESET SHALL
 BE MANUAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 16:23 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 16:23 Sent To G
Notes
2008-01-30 16:24:04TO "G" BOXD/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-28 Cont ID  
Sent By mperson Date 2007-11-28 Time 10:38 Rev Time 0.00
Received By mperson Date 2007-11-14 Time 12:24 Sent To  
Notes
2007-11-14 12:24:22TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 09:23 Rev Time 0.00
Received By mperson Date 2007-10-23 Time 16:17 Sent To  
Notes
2007-10-23 16:17:35TO "G" BOX