| Notes |
| 2007-10-31 14:42:17 | ****************PROVISO**************** | | | FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | | GENERATOR PLACEMENT. | | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | | TO FINAL INSPECTION. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 3,750 CUBIC FEET REQUIRED. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|
|