Plan Review Details - Permit 07100508
Plan Review Stops For Permit 07100508
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-09-30 Cont ID  
Sent By rmcdouga Date 2009-12-15 Time 08:20 Rev Time 0.00
Received By kconrad Date 2009-12-15 Time 11:08 Sent To  
Notes
2009-12-15 11:09:47DRIVEWAY REVISION OK. SEE #09120311.
2009-09-30 08:25:31REVISED SHEETS A-4.1, A-5.1 AND A-5.2 SHOWING R-30 BATT
 INSULATION AT CEILING AND CONTINUOUS EAVE VENT IN LIEU
 OF ICYNENE IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-09-09 Cont ID  
Sent By rmcdouga Date 2009-09-09 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2009-09-09 Time 16:48 Sent To  
Notes
2009-09-09 16:51:10REVISED PRODUCT APPROVALS FOR DOORS, SH WINDOWS AND
 MULLIONS ARE OK. CHANGED FROM ANDERSON TO PGT (ALL ARE
 LARGE MISSLE IMPACT).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-09-09 Cont ID  
Sent By rmcdouga Date 2009-09-09 Time 12:32 Rev Time 0.00
Received By rmcdouga Date 2009-09-09 Time 12:32 Sent To  
Notes
2009-09-09 13:37:12BUILDING REVISIONS
  
 1) THE LETTER SUBMITTED TO CHANGE FROM ICYNENE SPRAY
 FOAM INSULATION WITH UNVENTED ATTIC IS DENIED. SUBMIT
 TWO SETS OF SIGNED AND SEALED REVISED DRAWINGS SHOWING
 THE R-30 BATT INSULATION IN THE CEILINGS AND THE ATTIC
 VENTILATION REQUIRED BY FBC R806. REVISED ENERGY
 CALCULATIONS ARE REQUIRED.
  
 2) THE CEILING FRAMING DETAIL AND 2X4 WOOD DOOR BUCK
 DETAIL ARE OK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-16 Cont ID  
Sent By rmcdouga Date 2008-01-16 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2008-01-16 Time 10:42 Sent To  
Notes
2008-01-16 10:43:12NEW SHEETS WITH ZONING CORRECTIONS REVIEWED FOR CODE
 COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-04 Cont ID  
Sent By rmcdouga Date 2008-01-04 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2008-01-04 Time 07:08 Sent To ENG
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By rmcdouga Date 2007-12-10 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2007-12-05 Time 06:52 Sent To  
Notes
2007-12-10 16:16:082004 FBC W/2007 REVISIONS
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL. ONE WALL OF THE STRUCTURE
 IS LESS THAN 6 FEET FROM THE PROPERTY LINE.
  
 3) THE PLANS ARE MISSING SHEET A-5.2. WHICH IS LISTED
 IN THE DRAWING INDEX ON A-0.
  
 4) SUBMIT FIREPLACE AND CHIMNEY DETAILS. SHOW
 COMPLIANCE WITH R1003 FOR MASONRY FIREPLACES OR R1004
 FOR FACTORY BUILT FIREPLACES AND R1001 FOR MASONRY
 CHIMNEYS OR R1002 FOR FACTORY BUILT CHIMNEYS. IF USING
 FACTORY BUILT APPLIANCES SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION.
  
 5) PROVIDE A WINDOW SCHEDULE ON THE PLANS. IDENTIFY THE
 TYPES OF WINDOWS AND THEIR LOCATIONS. FBC 106.1.1* CITY
 AMENDMENTS.
  
 6) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.2.
 FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR
 PERFORATED MEMBERS.
 R502.1.2.1 MATERIALS.
 DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ?-INCH
 (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD
 STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W
 PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY
 SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO
 THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY
 THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS
 SHALL BE MAINTAINED.
  
 7) PROVIDE A WINDOW SCHEDULE. SPECIFY THE WINDOW TYPE,
 SIZE AND LOCATION. FBC 106.1.1* CITY AMENDMENTS.
  
 8) THE WALL LEGEND ON A-1.1 AND A-1.2 SPECIFY WOOD
 FRAME EXTERIOR WALLS. HOWEVER, WALL SECTION 3 ON A-5.1
 SPECIFIES METAL STUDS ON THE SECOND FLOOR AT THIS
 LOCATION. PLEASE CORRECT. FBC 106.1.1* CITY
 AMENDMENTS.
  
 9) WALL TYPE B ON DETAIL 2 ON A-1.1 IS 3-5/8" 20 GA.
 METAL STUDS AND THE STRUCTURAL DRAWINGS SHOW WOOD FRAME
 BEARING WALLS. PLEASE CLARIFY. FBC 106.1.1* CITY
 AMENDMENTS.
  
 10) ON SHEET A-3.2 THE MARK FOR SECTION 3/A-5.1 APPEARS
 TO BE IN THE WRONG LOCATION. PLEASE CORRECT. FBC
 106.1.1* CITY AMENDMENTS.
  
 11) SHOW COMPLIANCE WITH R602.1.2 FIREBLOCKING
 REQUIRED.
 FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED
 DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO
 FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND
 BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING
 SHALL BE PROVIDED IN WOOD-FRAME CONSTRUCTION IN THE
 FOLLOWING LOCATIONS.
 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF THE RUN.
  
 12) DETAIL 8 ON A-6.2 SHOWS INSULATION AT THE CEILING
 AND THE WALL SECTION ON A-5.1 SPECIFIES ICYNENE
 INSULATION. PLEASE CLARIFY.FBC 106.1.1* CITY
 AMENDMENTS.
  
 13) STRUCTURAL NOTE D-2 ON ON S-1 INCORRECTLY SPECIFIES
 ASCE 7-05. ASCE 7-02 IS THE EDITION THAT IS REFERENCED
 BY THE 2004 FBC. PLEASE CORRECT. SEE FBC R CHAPTER 43.
  
 14) PROVIDE WINDOW AND DOOR BUCK DETAILS. SPECIFY THE
 FASTENERS AND SPACING.FBC 106.1.2* CITY AMENDMENTS.
  
 15) ON DETAIL 8 ON A-6.1, SPECIFY THE EMBED DEPTH OF
 THE 1/2 " BOLTS FOR THE GARAGE DOOR BUCKS. FBC 106.1.1*
 CITY AMENDMENTS.
  
 16) THE BOTTOM PORTION OF THE FIRST FLOOR DOOR SCHEDULE
 ON SHEET A-6.1 IS MISSING.
  
 17) SUBMIT TWO COPIES OF THE SOIL REPORT WITH THE
 EMBOSSED SEAL AND ORIGINAL SIGNATURE OF THE SOIL
 ENGINEER. SEE FS 471 AND FAC 61G15-23.002.
  
 18) THE A/C AREA ON THE ENERGY CALCULATION FORMS DO NOT
 CORRESPOND WITH THE PLANS. THE OWNER/AGENT IS REQUIRED
 TO SIGN AND DATE THE FORM. SEE FBC CHAPTER 13-6.
  
 19) ON S-2 THE UPLIFT VALUE SPECIFIED FOR THE SIMPSON
 H-1 IS INCORRECT. THE UPLIFT VALUE SHOULD BE 585# PER
 THE 2007 SIMPSON CATALOG.
  
 20) SPECIFY THE MAXIMUM SPACING OF THE VERTICAL WALL
 REINFORCING ON THE PLANS. FBC 106.1.2* CITY
 AMENDMENTS.
  
 21) ON SHEET S-4 THE MARK FOR 3/S-7 IS LOCATED WHERE
 THE FLOOR TRUSSES ARE PARALLEL TO THE CONCRETE BEAM AND
 DETAIL 3 ON S-7 SHOWS THE TRUSSES PERPENDICULAR TO THE
 CONCRETE BEAM. PLEASE CORRECT.
  
 22) ON S-5 THE UPLIFT FOR THE TRUSSES AT THE REAR PORCH
 ARE SPECIFIED AS 2237#, HOWEVER THE "C" CONNECTORS
 SPECIFIED ARE RATED FOR AN UPLIFT OF 1260#. PLEASE
 CORRECT. FBC 106.1.1* CITY AMENDMENTS.
  
 23) SPECIFY THE CONNECTORS FOR THE 2 PLY GIRDERS AT THE
 EXTERIOR MASONRY WALL AT THE REAR PORCH. FBC 106.1.2*
 CITY AMENDMENTS.
  
 24) SPECIFY THE CONNECTORS FOR THE 2 PLY GIRDERS AT THE
 EXTERIOR WOOD FRAME WALL AT THE FRONT PORCH. FBC
 106.1.2* CITY AMENDMENTS.
  
 25) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 ICYNENE INSULATION. FBC 106.1.1* CITY AMENDMENTS.
  
 26)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 27) THE SCHEDULE ON A-6.1 SPECIFIES A WOOD DOOR AT THE
 SIDE OF THE GARAGE, BUT THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR A STEEL DOOR. PLEASE CORRECT. SEE FAC
 RULE 9B-72.
  
 28) THE NOTE ON THE DOOR SCHEDULE ON A-6 STATES THAT
 ALL FRENCH DOORS ARE ALUMINUM AND THEN SPECIFIES WOOD
 DOORS. PLEASE CLARIFY.
  
 29) SUBMIT PRODUCT APPROVALS FOR THE SINGLE INSWING
 FRENCH DOOR AS REQUIRED BY FAC RULE 9B-72.
  
 30) PLEASE CLARIFY THE WINDOW TYPES ON THE PLANS. A
 PRODUCT APPROVAL WAS SUBMITTED FOR CASEMENT WINDOWS AND
 THERE DOES NOT APPEAR TO BE ANY ON THE PLANS.
  
 31) ON SHEET A-6.1 ONE OF THE ELEVATIONS APPEARS TO
 SHOW (2) FIXED WINDOWS MULLED TOGETHER. SUBMIT PRODUCT
 APPROVALS FOR THEM AS REQUIRED BY FAC RULE 9B-72.
  
 32) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT ENTRY DOOR IS FOR AN OUTSWING DOOR, HOWEVER, THE
 PLANS SHOW THIS DOOR AS AN INSWING DOOR. PLEASE
 CORRECT.
  
 33) THE MAXIMUM WIDTH LISTED IN THE PRODUCT APPROVAL
 FOR THE FRENCH WOOD SIDELITES IS 18-13/16", WHICH DOES
 NOT APPEAR TO BE WIDE ENOUGH TO WORK FOR THE FRONT
 ENTRY ASSEMBLY DIMENSIONS ON THE PLANS. PLEASE REVIEW.
  
 NOTE: IN ORDER TO EXPEDITE PLAN REVIEW PLEASE RETURN
 ONE SET OF THE OLD PLAN SHEETS AND A RESPONSE LETTER
 INDICATING HOW THE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-28 Cont ID  
Sent By dpalmer Date 2007-12-28 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-12-27 Time 16:53 Sent To M
Notes
2007-12-28 09:06:41 
 *** REDLINED PLANS***
  
 1) THE REQUESTED MINIMUM LIGHT FIXTURE(S) A MINIMUM OF
 ONE OUT FRONT OF DWELLING AND REAR OF DWELLING WAS NOT
 SHOWN ON PLANS. THIS WAS RED-LINED AS ONE FIXTURE AT
 EACH LOCATION OF SOME SORT WILL BE REQUIRED FORE EGRESS
 AND LIFE SAFETY BEFORE FINAL.
 210.70, 90.4, LS 101 7.8
  
 2) GE SYSTEM SHOWS STRUCTURAL STEEL, REDLINED TO FOOTER
 STEEL.
  
 3) ALL RECESSED LIGHTS TO BE INSTALLED SHALL MEET FBC
 13-606.1.ABC.1.2.4.
  
 4) LOW VOLTAGE SHOWN ON PLAN REQUIRES A SEPARATE
 PERMIT. PLANS SHOW PHONE AND CATV ONLY.
 ANY OTHER SYSTEMS INSTALLED (IE: ) SPEAKERS, WILL
 REQUIRED PLANS/LAYOUT OF LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER DIRECTLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 11:26 Sent To M
Notes
2007-10-20 11:26:40** DENIED **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2005 NFPA-70 (SHOWN)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTORS. THE PLANS CALL FOR SD ALONG WITH NOTES AND
 LEGEND WHICH STAND FOR SMOKE DETECTORS. PLEASE SEE BY
 DEFINITION OF A SD THIS IS A DEVICE WHICH ONLY DETECTS
 AND WOULD SIGNAL OTHER DEVICES FOR ALARM AND SOUNDING.
 PLEASE SEE HOWEVER THESE ARE BEING SHOWN CIRCUITED AS
 120V UNITS.
 PLEASE LOCATIONS OF SOUNDING DEVICES AND FIRE ALARM
 SYSTEM IF INDEED THESE ARE SMOKE DETECTORS.
 ** IF THESE ARE ACTUALLY 120VA UNITS WHICH DETECT AND
 SOUND AN ALARM, THEN THESE BY DEFINITIONS IN NFPA-72
 WOULD BE SA FOR SMOKE ALARMS. YOU CAN SEE IN THE FBC
 AND RESIDENTIAL CODES ALONG WITH NFPA THESE ARE
 INDICATED AS *ALARMS*.
 ** PLEASE ALSO SEE NOTE ON E-2 MENTIONS THE SMOKE
 DETECTORS ARE TO BE WIRED TO THE BATH OR KITCHEN
 LIGHTING CIRCUIT(S), HOWEVER AS SHOWN ON PLANS THESE
 ARE BEING WIRED TO THE BEDROOM LIGHTING CIRCUIT.
  
 IT IS NOT KNOWN TO THE OFFICE WHICH ACTUAL SYSTEM IS
 BEING INSTALLED HOWEVER SEEMS THIS ACTUALLY NEED TO BE
 ADJUSTED TO SHOW SA/SMOKE ALARMS. PLEASE ADJUST ANY
 NOTES, LEGEND ETC AS NEEDED.
  
 3) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE CALLING
 FOR 13 SMALL APPLIANCE CIRCUITS WHICH DOES NOT
 CORRELATE WITH THE PANEL SCHEDULE(S). THE OTHER
 APPLIANCES SUCH AS THE DISHWASHER, MICROWAVE ETC IS NOT
 TYPICALLY CALLED SMALL APPLIANCE CIRCUITS AND IS NOT
 SHOWN AS THIS ON PLANS OR PANEL SCHEDULES. THESE ARE
 DEDICATED CIRCUITS WHICH WOULD BE LISTED IN LOAD
 CALCULATIONS ACCORDINGLY.IT IS NOTED THAT THE SAME
 1500VA IS BEING USED WHICH IS OK.
 PLEASE SEE 210.52B1 AS AREAS WHICH ARE BREAKFAST AREAS
 AND THE LIKE ARE ALSO REQUIRED TO BE ON ONE *OR MORE*
 OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE BREAKFAST EATING AREA ALONG WITH BAR AREA
 WHICH IS CIRCUIT #22.
 210.11C1, 220.52
  
 4) NOTE: PLEASE VERIFY 210.4B FOR DISHWASHERS AND
 DISPOSALS. IF THESE UNITS ARE GOING TO BE FED FROM A
 DEVICE WITH THE SAME YOKE, THEN THE BREAKER FEEDING
 THIS SINGLE DEVICE/YOKE WOULD BE NEED TO BE A 2-POLE
 BREAKER.
 THIS IS ONLY NOTED FOR VERIFICATION AS PLANS DO SHOW
 TWO INDIVIDUAL SINGLE RECEPTACLES. **NO CHANGE IS
 NEEDED AND ONLY NOTED**
  
 5) NOTE: PLEASE SEE210.70 AND LS 101 7.8 AS AT LEAST
 ONE ELECTRICAL LIGHT FIXTURE IS REQUIRED OUTSIDE THE
 FRONT EGRESS FOR ILLUMINATION. THESE ARE ALL CURRENTLY
 SHOWN AS J-BOXES.
  
 6) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 7) NOTE: PLEASE SEE RECEPTACLE ON THE STAIR SIDE OF
 DINING ROOM NEEDS TO BE WITHIN 6FT OF THE EDGE OF THE
 WALL. THIS COULD BE REDLINED, HOWEVER PLEASE CORRECT AT
 TIME AS PLANS ARE IN NEED OF SOME OTHER ADJUSTMENTS.
  
 8) NOTE: PLEASE SEE 210.8A7 AS ALL 15/20AMP RECEPTACLES
 WITHIN 6FT OF LAUNDRY SINKS ARE ALSO REQUIRED TO HAVE
 GFI PROTECTION. THIS INCLUDES SINGLE RECEPTACLES SUCH
 AS THE WASHING MACHINE. THE PLANS APPEAR TO SHOW AS
 SINK IN THIS ROOM.
 THIS IS NEW IN THE 2005 NEC.
  
 9) NOTE: PLANS WERE SUBMITTED WITH AN AFFIDAVIT WHICH
 WAS DONE BY THE ARCHITECT AND A LICENSED PLAN REVIEWER
 HOWEVER THIS WAS NOT SUBMITTED AS A *PRIVATE PROVIDER*
 PROJECT PER FS 553.791. THIS WAS CONFIRMED ON THE FRONT
 COUNTER UPON SUBMISSION OF PLANS.
  
 ** PLEASE KNOW MANY OF THE ABOVE ITEMS COULD BE
 REDLINED HOWEVER PLANS ARE COMING BACK FOR
 CORRECTIONS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-01-17 Cont ID  
Sent By rchokshi Date 2008-01-17 Time 13:21 Rev Time 0.00
Received By rchokshi Date 2008-01-17 Time 13:21 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-01-14 Cont ID  
Sent By rchokshi Date 2008-01-14 Time 14:29 Rev Time 0.00
Received By rchokshi Date 2008-01-14 Time 14:26 Sent To B
Notes
2008-01-14 14:28:14FAILED FOR FOLLOWING REASONS:
  
 1. YOU ARE PUTTING AN APPROACH, DRIVEWAY, SIDEWALK &
 CUTTING A CURB IN CITY'S RIGHT OF WAY. THEREFORE, YOU
 NEED CITY'S RIGHT OF WAY APPROVAL FROM WINDEL PALMER
 494-1040, 1000 45TH STREET, ENG DEPT. ONCE WE HAVE AN
 APPROVAL FROM WINDEL PALMER, WE WILL REVIEW YOUR
 DRAWINGS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By rchokshi Date 2008-01-04 Time 14:12 Rev Time 0.00
Received By rchokshi Date 2008-01-04 Time 14:11 Sent To  
Notes
2008-01-04 14:12:44FAILED FOR FOLLOWING REASONS:
  
 1. YOU ARE PUTTING AN APPROACH, DRIVEWAY, SIDEWALK &
 MAY BE CUTTING A CURB IN CITY'S RIGHT OF WAY.
 THEREFORE, YOU NEED CITY'S RIGHT OF WAY APPROVAL FROM
 WINDEL PALMER 494-1040, 1000 45TH STREET, ENG DEPT.
 ONCE WE HAVE AN APPROVAL FROM WINDEL PALMER, WE WILL
 REVIEW YOUR DRAWINGS.
  
 2. MUST MEET CITY'S STANDARDS FOR APPROACH,
 SIDEWALK,DRIVEWAY ETC. A SHEET " TYPICAL PAVER
 STONE/CONCRETE DRIVEWAY APPROACH DETAILS" ENCLOSED FOR
 YOUR USE.
  
 RASIK CHOKSHI 805-6723

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 09:46 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 09:46 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-09-03 Cont ID  
Sent By kstevens Date 2009-09-03 Time 14:05 Rev Time 0.00
Received By kstevens Date 2009-09-03 Time 14:05 Sent To  
Notes
2009-09-03 14:06:07SENT TO RMCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 14:08 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 14:07 Sent To  
Notes
2009-09-02 14:17:12SENT TO R-5.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 15:06 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 15:06 Sent To ENG
Notes
2008-01-16 15:06:41TO "ENG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 08:43 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 08:43 Sent To Z
Notes
2008-01-10 08:43:54TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:23 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 16:23 Sent To Z
Notes
2007-12-21 16:23:48SENT TO ZONING'S INBOX MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 16:31 Sent To B
Notes
2007-11-27 16:31:50TO "RMCDOUGAL" DESK--PLANS BACK IN FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By rmcdouga Date 2007-12-10 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2007-10-17 Time 16:25 Sent To  
Notes
2007-10-17 16:25:48TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-02 Cont ID  
Sent By hmoser Date 2009-09-02 Time 14:36 Rev Time 0.00
Received By hmoser Date 2009-09-02 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-28 Cont ID  
Sent By tgordon Date 2007-12-28 Time 09:52 Rev Time 0.35
Received By tgordon Date 2007-12-28 Time 09:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 14:17 Rev Time 1.20
Received By tgordon Date 2007-10-22 Time 14:17 Sent To P
Notes
2007-10-22 14:51:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE STATE ON PLAN M-1 WHICH EXHAUST FAN IS TO BE
 INSTALLED IN THE FIRST FLOOR BATHROOM (EF-1 OR EF-2).
 SEE FBC/R R303.3 EXCEPT..
  
 2) PLEASE SHOW ON PAGE M-1 THE SIZE OF THE RETURN AIR
 TRANSFER DUCT TO BEDROOM 2. SEE FBC/R M1602.4.
  
 3) PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE
 GAS CLOTHES DRYER AND PROVIDE COMBUSTION AIR. SEE FBC/R
 G2407.1
  
 4) PLEASE PROVIDE FOR MAKEUP AIR FOR THE GAS CLOTHES
 DRYER. SEE FBC/R G2407.4.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 PREFABRICATED GAS FIREPLACE AND ALSO THE GAS GRILL IN
 THE COVERED PORCH. SEE FBC 106.1
 *** BE ADVISED THE GAS GRILL IN THE COVERED PORCH MAY
 REQUIRE AN APPROVED HOOD. SEE FBC/R M1504.1.
  
 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-09 Cont ID  
Sent By rmcdouga Date 2009-09-09 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2009-09-09 Time 15:25 Sent To  
Notes
2009-09-09 15:27:46REVISED SANATARY PLUMBING RISER DIAGRAM DRAWING ON 8.5"
 X 11" SHEET SK-2 IS OK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 09:43 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 09:06 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By jleech Date 2007-11-02 Time 09:08 Rev Time 0.00
Received By jleech Date 2007-11-02 Time 09:08 Sent To B
Notes
2007-11-02 09:20:39DENIED;
 1. PAGE P-1 MASTER SHOWER DRAIN IS MORE THAN 6' FROM
 TRAP TO VENTED LINE. SEE FBC- PLUMBING TABLE 906.1.
 2. SANITARY RISER DIAGRAM MASTER BATH. PIPE SIZE AFTER
 SHOWER MUST GO FROM 2" TO 3" SEE WET VENT TABLE 909.3.
 3. PORCH DRAINS ARE STORM WATER DRAIN NO TRAP OR TRAP
 PRIMER ARE REQUIRED PLEASE CORRECT.
 4. SHOW SECONDARY ROOF DRAINS OR SCUPPERS ON PLANS SEE
 CHAPTER 11 .
 5. SHOW SIZE OF GAS WATER HEATER AND HOW IT WILL BE
 VENTED WITH REQUIRED CLEARANCES FROM BURNABLES
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-14 Cont ID  
Sent By choops Date 2008-01-14 Time 09:57 Rev Time 0.00
Received By choops Date 2008-01-14 Time 09:57 Sent To ENG
Notes
2008-01-14 09:57:59***APPROVED - RESUB #2***
  
  
  
 SENT TO "ENG" - RC

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-26 Cont ID  
Sent By choops Date 2007-12-26 Time 15:40 Rev Time 0.00
Received By choops Date 2007-12-26 Time 15:40 Sent To E
Notes
2007-12-26 15:48:33***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)A LANDSCAPE PLAN SHALL BE PROVIDED SHOWING
 COMPLIANCE WITH SECTION 94-442 AND 94-445 OF THE ZLDRS.
 THE PROVIDED SITE PLAN SHOWS NO PROPOSED LANDSCAPING.
  
 2)PURSUANT TO SECTION 94-72(A)(3) OF THE ZLDRS:
 MAXIMUM BUILDING HEIGHT = 30 FEET.PLEASE INDICATE
 HEIGHT FROM GRADE TO THE MIDPOINT OF THE UPPERMOST
 ROOF'S PITCH.ADDITIONALLY SECTION 94-306(A) PROVIDES
 FOR AN ADDITIONAL 10% TO PROVIDE FOR ACCESSORIES.
 YIELDING AN TOTAL ALLOWABLE HEIGHT (FROM GRADE TO THE
 TOP OF ALL ACCESSORIES OF 33'.PLANS SHALL INDICATE
 COMPLIANCE WITH SUCH.HEIGHT DIMENSIONS ARE STILL NOT
 SHOWN FROM GRADE...READING THE INITIAL COMMENTS AND
 VIEWING THE SUBMITTED PLANS IT SHOULD BE QUITE OBVIOUS
 THAT YOU HAVE STILL NOT PROVIDED THE REQUESTED
 INFORMATION.DEPENDING ON THE DIFFERENCE BETWEEN GRADE
 AND THE FINISHED FLOOR ELEVATION, THE MAXIMUM ALLOWABLE
 BUILDING HEIGHT (INCLUDING ACCESSORIES (CHIMNEY)) COULD
 STILL BE EXCEEDED.PROVIDE BUILDING HEIGHT FROM GRADE
 TO THE UPPERMOST POINT OF THE CHIMNEY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By choops Date 2007-10-19 Time 14:27 Rev Time 0.00
Received By choops Date 2007-10-19 Time 14:27 Sent To E
Notes
2007-10-19 14:33:07***FAILED***
  
  
 1)PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS):MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.INDICATE SETBACK
 DIMENSIONS FROM THE PROPOSED A/C EQUIPMENT TO THE
 PROPERTY LINES.
  
 2)A LANDSCAPE PLAN SHALL BE PROVIDED SHOWING
 COMPLIANCE WITH SECTION 94-442 OF THE ZLDRS.
  
 3)AS PER SECTION 94-482(A) OF THE ZLDRS:REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBEDIN THIS ARTICLE.
 PLEASE INDICATE DIMENSIONS OF PROPOSED DRIVEWAY.
 ADDITIONALY, SPECIFY IF BRICK PAVERS ARE TO BE SEALED
 OR UNSEALED.
  
 4)PURSUANT TO SECTION 94-72(A)(3) OF THE ZLDRS:
 MAXIMUM BUILDING HEIGHT = 30 FEET.PLEASE INDICATE
 HEIGHT FROM GRADE TO THE MIDPOINT OF THE UPPERMOST
 ROOF'S PITCH.ADDITIONALLY SECTION 94-306(A) PROVIDES
 FOR AN ADDITIONAL 10% TO PROVIDE FOR ACCESSORIES.
 YIELDING AN TOTAL ALLOWABLE HEIGHT (FROM GRADE TO THE
 TOP OF ALL ACCESSORIES OF 33'.PLANS SHALL INDICATE
 COMPLIANCE WITH SUCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING